- LED is OFF = External IR relay is turned OFF
c. Both TRIAC an IR enabled
- LED is ON = External IR relay is turned ON
- LED is OFF = External IR relay is turned OFF
- LED is 0.5s OFF, 0.5s ON = IR communication error
d. External IR relay disabled
- LED is ON = modbus packet is sent
- LED is OFF = modbus packet is received
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
1. Make sure a device is in factory reset state before including. In doubt exclude before include.
2. If inclusion still fails, check if both devices use the same frequency.
3. Remove all dead devices from associations. Otherwise you will see severe delays.
4. Never use sleeping battery devices without a central controller.
5. Dont poll FLIRS devices.
6. Make sure to have enough mains powered device to benefit from the meshing
Association - one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another device is called association. In order to control a
different device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called association groups
and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the event happens all devices stored in the respective
association group will receive the same wireless command wireless command, typically a 'Basic Set' Command.
Association Groups:
Group Number
Maximum Nodes
Description
1
1
Lifeline
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock
further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be
the desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte
value the same logic applies: Values greater than 32768 may needed to be given as negative values too.
Parameter 7: Input switch function selection
Available configuration parameters for input switch I1
Size: 1 Byte, Default Value: 0
Setting
Description
0
disabled
2
IR external relay control – mono stable push button
3
IR external relay control – bi-stable switch
4
External relay control – mono stable push button
5
External relay control – bi-stable switch
Parameter 40: Reporting on power change
This parameter is valid for Active Power Total, Active Power Phase1, Active Power Phase2 and Active Power Phase3.
NOTE: if power change is less than 5 W, the report is not send (pushed).NOTE: Device is measuring also some disturbances even if on the output is no
load. To avoid disturbances:- If measured Active Power (W) is below e.g. 5W-> the reported value in this case is 0W
Size: 1 Byte, Default Value: 50
Setting
Description
0
reporting disabled
1 - 100
1% - 100% reporting enabled. Power report is send only when actual power in Watts (in real time changes for
more than set percentage comparing to previous Active Power, step is 1%.
Parameter 42: Reporting on time interval