14. Configuration Parameters
Parameter no. 10 - Activate / deactivate ALL ON / ALL OFF Functionality
Flush Shutter DC device responds to the commands ALL ON / ALL OFF that may be sent by the
primary or secondary gateway (hub) within the Z-Wave network.
Values (size is 2-byte dec):
•
default value 255
•
255 - ALL ON active, ALL OFF active.
•
0 - ALL ON not active, ALL OFF not active
•
1 - ALL ON not active, ALL OFF active
•
2 - ALL ON active, ALL OFF not active
Parameter no. 40
–
Watt Power Consumption Reporting Threshold for Q1 or Q2 Loads
Choose by how much the power consumption needs to increase or decrease to be reported.
Values correspond to percentages, so if 10 is set (by default), the device will report any power
consumption changes of 10 % or more, compared to the last reading.
Values (size is 1-byte dec):
•
default value 10
•
0 - Power consumption reporting disabled
•
1 - 100 = 1 % - 100 % Power consumption reporting enabled. New value is reported only
when the power consumption in real time changes by more than the percentage value
set in this parameter, compared to the previous power consumption reading, starting at
1 % (the lowest value possible).
Summary of Contents for FLUSH SHUTTER DC
Page 3: ...EN 3 18 Warning 58 19 Regulations 58...
Page 16: ...EN 16 4 Package Contents Flush Shutter DC Device Installation Manual...
Page 23: ...EN 23 After Qubino installation...
Page 29: ...EN 29 Step 2 Turn the fuse OFF Step 3 Connect the temperature sensor as shown below...
Page 30: ...EN 30 Step 4 Place the temperature sensor in the switch box Step 5 Turn the fuse ON...
Page 31: ...EN 31 Step 6 Re include the device to your network...
Page 32: ...EN 32 Step 7 Start using the temperature sensor in connection with your device...