Parameter 110: Temperature Sensor Offset Settings 

Set value is added to or subtracted from the actually measured value to adjust the temperature report sent by an 
external sensor. 
NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -150150 (-15.0 
C15.0 C, resolution 0.1 C) 
NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is -270 - 270 (-
27.0 F27.0 F, resolution 0.1 F) 
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be 
converted to Celsius degrees.  
Due to conversion algorithm please be advised that configuration value could drift when converting values back 
and forth.

 

Size: 2 Byte, Default Value: 0 

Setting 

Description 

-270 - 270 

Set value is added to or subtracted from the actually measured value to adjust the temperature 
report sent by an external sensor. 

Parameter 120: Temperature Sensor Reporting Threshold 

This configuration parameters sets reporting threshold between reported temperature and actual temperature 
for reporting temperature at association group 4. 
NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 0150 (0 C15.0 C, 
resolution 0.1 C) 
NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 0 - 270 (0 
F27.0 F, resolution 0.1 F) 
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be 
converted to Celsius degrees.  
Due to conversion algorithm please be advised that configuration value could drift when converting values back 
and forth.

 

Size: 2 Byte, Default Value: 5 

Setting 

Description 

0 - 270 

This configuration parameters sets reporting threshold between reported temperature and actual 
temperature for reporting temperature at association group 4. 

Technical Data 

Dimensions 

115 x 96 x 22 mm 

Weight 

50 gr 

Hardware Platform 

ZM5202 

EAN 

3830062071710 

IP Class 

IP 20 

Voltage 

230V 

Load 

10A 

Device Type 

Thermostat - HVAC 

Network Operation 

Always On Slave 

Z-Wave Version 

6.81.03 

Certification ID 

ZC10-19086722 

Z-Wave Product Id 

0x0159.0x0005.0x0054 

Summary of Contents for FLUSH ON/OFF THERMOSTAT 2

Page 1: ...the device to the power supply with the temperature sensor already connected 3 Toggle the switch connected to the I1 terminal 3 times within 3 seconds The device has to get On Off signal 3 times meani...

Page 2: ...tically turn the device on if the temperature is too low antifreeze Automatically turn the device on off based on Hysteresis Works on 110 240 VAC or 24 30 VDC Prepare for Installation Reset Please rea...

Page 3: ...esent in the wiring Take extra precautions to avoid accidentally turning the device on during installation Step 2 Installing the device Connect the device exactly according to the diagrams shown below...

Page 4: ...o communicate with the devices of this network This process is called Inclusion Devices can also be removed from a network This process is called Exclusion Both processes are initiated by the primary...

Page 5: ...eeping battery devices without a central controller 5 Dont poll FLIRS devices 6 Make sure to have enough mains powered device to benefit from the meshing Association one device controls an other devic...

Page 6: ...the previous Wattage reading starting at 1 the lowest value possible Parameter 42 Watt Power Consumption Reporting Time Threshold for Q Set value refers to the time interval with which power consumpt...

Page 7: ...OTE1 Antifreeze is activated only in heating mode and it uses hysteresis of 0 5C NOTE2 If configuration parameter 78 Scale selection is set to Celsius then valid interval is 125125 12 5 C12 5 C resolu...

Page 8: ...to Fahrenheit note that Fahrenheit values will be converted to Celsius degrees Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth...

Page 9: ...ion parameters sets reporting threshold between reported temperature and actual temperature for reporting temperature at association group 4 NOTE1 If configuration parameter 78 Scale selection is set...

Page 10: ...turer Specific V2 Meter V4 Notification V8 Powerlevel Security Security 2 Sensor Multilevel V7 Supervision Thermostat Mode V3 Thermostat Operating State Thermostat Setpoint V3 Transport Service V2 Ver...

Page 11: ...work Association is a control relationship between a controlling device and a controlled device Wakeup Notification is a special wireless message issued by a Z Wave device to announces that is able to...

Reviews: