StorNext QM1200, QS1200 or QS2400 Base System - Replacing a Drive

April 2015

Quantum Corporation

- 3 -

Removing a Drive from the Drive Tray 

1.

Gather support data about your storage array by using one of these methods:

Use the storage management software to collect and save a support bundle of your storage array. From the 
Array Management Window, select 

Monitor >> Health >> Collect Support Data

. Then name and specify a 

location on your system where you want to store the support bundle.

Use the command line interface (CLI) to run the 

save storageArray supportData

 command to 

gather comprehensive support data about the storage array. For more information about this command, 
refer to 

Command Line Interface and Script Commands

. Running this command can temporarily impact 

performance on your storage array.

2.

Did the Recovery Guru direct you to replace a failed drive?

Yes

 – Continue.

No

 – Run the Recovery Guru to identify the failed component.

3.

Put on antistatic protection.

4.

Unpack the drive.

a.

Set the new drive on a flat, static-free surface near the base system.

b.

Save all packing materials in case you need to return the drive.

ATTENTION  Possible equipment damage 

– You must replace the drive within three minutes after 

removal to prevent 

the possibility of overheating the equipment.

ATTENTION  Possible loss of data access

 – 

Never insert drives into the base system without first confirming 

that the drive firmware level is compatible with the other drives. Inserting a drive with an incorrect firmware 
level can cause loss of data access. For information about the supported drive firmware levels, contact your 
Customer and Technical Support representative.

ATTENTION  Possible loss of data access

 – 

Magnetic fields can destroy all data on the drive and cause 

irreparable damage to the drive circuitry. To avoid the loss of data access and damage to the drives, always 
keep drives away from magnetic devices.

ATTENTION  Possible hardware damage

 – 

To prevent electrostatic discharge damage to the tray, use proper 

antistatic protection when handling tray components.

NOTE  

Install only drives that are specifically designed for your base system and that have been specifically 

tested and qualified in the factory.

Summary of Contents for StorNext QM1200

Page 1: ...StorNext QM1200 QS1200 or QS2400 Base System Replacing a Drive 6 67542 02 Rev B 6 67542 02 B...

Page 2: ...tum the Quantum Logo Backup Recovery Archive It s What We Do Be Certain Be Quantum Certain DLT the DLT Logo DLTSage DLTtape the DLTtape Logo DXi DXi Accent Dynamic Powerdown FastSense FlexLink GoProte...

Page 3: ...drive in two ways The Recovery Guru directs you to replace a failed drive You locate the failed drive by checking the amber Service Action Required LEDs in three locations Base system Drive drawer Dr...

Page 4: ...ustration of the QS2400 service action required LED Figure 2 QS2400 service action required LED 1 Service Action Required LED Amber Drive Status LEDs Figure 3 provides an illustration of the drive sta...

Page 5: ...drive on a flat static free surface near the base system b Save all packing materials in case you need to return the drive ATTENTION Possible equipment damage You must replace the drive within three m...

Page 6: ...ED to locate the failed drive Figure 4 and Figure 5 You can also check the Drive Service Action Required LED on the drive Figure 6 Figure 4 QM1200 QS1200 Service Action Required LED 1 Service Action R...

Page 7: ...drive the blue Drive Service Action Allowed LED must be on Figure 6 Item1 7 Remove the failed drive from the base system a Pull the drive handle to the left for a drive in the QM1200 or QS1200 base s...

Page 8: ...to lock the drive securely in place As the drive spins up the Drive Power LED might blink intermittently which indicates that data is being restored to the new drive 2 Check the Drive Power LED and th...

Page 9: ...contact your Customer and Technical Support representative No Go to step 6 6 Remove the antistatic protection 7 Gather support data about your updated storage array by using one of these methods Use t...