7.2 Monitorable and Editable Registers Table
7.2.1 Monitorable and Editable Parameters and Variables
Address
Type
Description
0x0000
BITMAP Bitmap configuration flag:
Bit0.
Default configuration
Bit1.
TRIP latch Enabled
Bit2.
Probe T1 Enabled
Bit3.
Probe T2 Enabled
Bit4.
Probe T3 Enabled
Bit5.
Probe T4 Enabled
Bit6.
Unit of Measure = °F
Bit7.
Buzzer on Alarm Enabled
Bit8.
Bit9.
Bit10.
Bit11.
Bit12.
Bit13.
Bit14.
Bit15.
0x0001
INT
FAN Probes 1/2/3 (°C o °F) Set-Point
0x0002
INT
FAN Probe 4 (°C o °F) Set-Point
0x0003
INT
ALARM Probes 1/2/3 (°C o °F) Set-Point
0x0004
INT
ALARM Probe 4 (°C o °F) Set-Point
0x0005
INT
TRIP Probes 1/2/3 (°C o °F) Set-Point
0x0006
INT
TRIP Probe 4 (°C o °F) Set-Point
0x0007
BYTE
Hysteresis (°C o °F)
0x0008
BYTE
FCD (°C/s or °F/s) Set-Point
0x0009
BYTE
Alarm Delay (s)
0x000A
BYTE
TRIP Pulse Duration (s)
0x000B
WORD
Auto Ventilation Period (h)
0x000C
BYTE
Auto Ventilation Time (min)
0x000D
DWORD Partial Working Hours (Reset only)
0x000E
0x000F
INT
Max Temperature T1 (°C o °F) (Reset only)
0x0010
INT
Max Temperature T2 (°C o °F) (Reset only)
0x0011
INT
Max Temperature T3 (°C o °F) (Reset only)
0x0012
INT
Max Temperature T4 (°C o °F) (Reset only)
0x0013
WORD
Number of Activation of Relays FAN (Reset only)
0x0014
WORD
Number of Activation of Relays ALARM (Reset only)
0x0015
WORD
Number of Activation of Relays TRIP (Reset only)
0x0016
WORD
Number of Activation of Relays FAULT (Reset only)