The relay A2 (signaled by the ALARM LED) switches when the probe reaches the alarm temperature.
Enabling this
relay can
be delayed
by setting a
time
in the user menu
.
The relay
A3 (
signaled by LED
TRIP
) switches when
one of the probes
reaches a temperature of
release
.
The working mode of this relay can be controlled by the user menu:
Standard mode: It is active when you reach the alarm condition and remains active until the
condition persists.
Latching mode: Keeps the alarm indefinitely, even to the end of the cause of the alarm.
Pulse mode: It is activated for a predetermined time and then returns to the rest condition.
The relay A4 (indicated by LED FAULT) is always on and going off to signal a DQ61 fault condition or a
fault condition in one or more probes.
A1
A2
A3
A4
26
27
28
29
30
31
32
33
34
35
36
37
Figure 6
Relay in its rest position; DQ61 ON
A1
A2
A3
A4
26
27
28
29
30
31
32
33
34
35
36
37
Figure 7
Fan activated; Fault DQ61 and/or fault probe
5.8 Buzzer features
The buzzer is activated at the reach of alarm set-point (ALARM), which also activates the relay A2, and beeps
intermittently slow until the end of cause for alarm.
The buzzer sounds intermittently fast, when it reaches the release set-point (TRIP) which activates the relay
A3.
The buzzer sounds a continuous tone to indicate the fault condition of a Pt100 probe.
The MUTE key mute the buzzer when alarm is active. In the state of silencing the buzzer wakes up in the
presence of new alarm events.
The activation of the buzzer on alarm can be inhibited by the service menu.
.
Type of sound
Cause reported
Continuous
One or more probes are faulty
Intermittent slow
Active alarm relay (ALARM)
Intermittent fast
Active tripping relay (TRIP)