Activation interval of the fan (independent of temperature)
.
Default 0 hours.
You can set a value between 0 and 1000h. Setting the value 0, to disable this function: The fan will turn
on anyway as a result of exceeding the alarm FAN temperature; setting a value other than 0, for
example. 6h, the fan will turn on every 6 hours and will remain on for the time set to the next parameter
(P13).
FAN ON Time (See parameter P12).
.
Default 5 minutes.
Determines how long the fan stays on if the parameter P12 is different from 0.
Probe 1 Enable.
.
Default YES.
Setting the value to NO exclude the alarm probe 1, while remaining visible indication of its temperature
on the display.
This condition is indicated on the status line with the message
“Alarms probe T1 OFF”.
The parameters from P14 to P17 allow you to use DQ61 with a number of probes between 1 and 4
without having to worry about the alarms generated by the probes that may be missing.
Probe 2 Enable.
.
Default YES.
Setting the value to NO exclude probe 2 alarm, while the temperature on the display remains visible.
This condition is indicated on the status line with the message
“Alarms probe T2 OFF”.
Probe 3 Enable.
.
Default YES.
Setting the value to NO exclude probe 3 alarm, while the temperature on the display remains visible.
This condition is indicated on the status line with the message
“Alarms probe T3 OFF”.
Adjusting the display brightness in the working mode
.
.
Default 240.
Adjusting the display brightness in the stand-by mode
.
.
Default 60.
The parameters P8 and P19 are connected to each other in the following way:
P18 can be set between P19+1 and 255;
P19 can be set between 0 and the value of P18-1.
ID. MODBUS.
.
Default 1. (Allowed values: from 1 to 247).
If the RS485 MODBUS option is not installed, the value indicated is
and will not be editable.
RS485 MODBUS Baud rate.
.