QUALITROL AKM345 GEN3 OTIWTI
TM
Instruction Manual
40-08847-00-Rev001
www.qualitrolcorp.com
Page 21 of 34
5.3.5
Remote Output
The AKM345 GEN3 can be equipped with powered outputs: 4-20mA, 2 x 4-20mA, or 4-20mA & 0-5VDC. These
outputs are scaled evenly across the specified dial range.
The wiring for these remote outputs is designated as follows:
•
71 = Output Return
•
72 = Output 1
•
73 = Not Used
•
74 = Output 2
•
75 = Output Screen
•
NOTE:
terminal block arrangement may differ depending on other options selected, but terminal
designation will remain the same
Powered Remote Output Wiring Example
An additional non-powered output is available as a Pt100 resistance signal. The Pt100 signal will correspond to
the temperature as per the Pt100 resistance curve.
The wiring for the Pt100 output is designated as follows:
•
71 = R2
•
72 = R1
•
73 = R3
•
NOTE:
terminal block arrangement may differ depending on other options selected, but terminal
designation will remain the same
Pt100 Output Wiring Example