background image

AKM 345 Gen2 Instruction Manual 

(Rev No. ECN-27992)

 

 

 

4

www.qualitrolcorp.com

5.1.  Instructions for Adjusting Matching Resistance 

1.  Check or calculate current in A from Your Current Transformer (at bushing) at 100 % 

transformer load. 

2.  Check the required Winding Temperature gradient in °C or K. 

3.  Use the graph in Fig.3 for the CT current and gradient to determine the required 

resistance setting in Ohms. Take note of this value. 

4.  Connect a multi meter, (Example: Fluke) set for resistance measurement to the 

terminals 5-5 inside the WTI. 

5.  Adjust the matching resistance TD50 or TD76 until you reach the required resistance 

value. For TD50/5A see section 5.4.  

6.  Secure the lock nut on the matching resistance for this setting. 

7.  Check operation and make final adjustments if necessary. 

8.  Please consult Customer Service for additional information. 

 

 

 
Figure 3 – Temperature Gradient Graph 

 

1.2

1.3

1.41.5

1.6

1.7

 

1.8

 

1.9

 

2

2.1
2.2

1

 

1.1

2,3

2,4

2,5

2,6

0.40

 

0.60

 

0.80

 

1.00

 

1.20

 

1.40

 

1.60

 

1.80

 

°C

Temperature Gradient – Adjustment Graph

-

Re

sistance, Oh

ms

 

Summary of Contents for AKM 34/Gen2 OTI

Page 1: ...Instruction Manual www qualitrolcorp com IST 103 1 EN AKM 345 Gen2 Oil Temperature Indicator AKM OTI Type 34 Winding Temperature Indicator AKM WTI Type 35 Document ID IST 103 1 EN...

Page 2: ...ed without the express prior written permission of Qualitrol QUALITROL endeavors to ensure the accuracy and quality of its published materials however no warranty expressed or implied is provided QUAL...

Page 3: ...g the AKM345 Double Gradient Option 6 5 3 1 Background 6 5 3 2 Wiring Recommendations 6 5 4 Using the 5 Amp Internal CT Option 6 5 5 Setting the Matching Resistance 7 5 5 1 Method A 7 5 5 2 Method B 7...

Page 4: ...ount 10 Figure 8 Cover Hinge Side View 11 Figure 9 Front Cover Removal 11 Figure 10 Switch Selection 12 Figure 11 2 to 4 Switches w Optional Heater and Remotes 13 Figure 11 1 2 to 4 Switches w Optiona...

Page 5: ...ontents Contents iii www qualitrolcorp com Figure 15 5 4 20mA 0 5V DC Suggested Wiring TD119 5 24 Figure 15 6 4 20mA 0 10V DC Suggested Wiring TD119 5 25 Figure 15 7 Suggested Wiring TD66 CU10 PT100 2...

Page 6: ...nsion space in oil filled pockets The non vibration mountings included must be used to prevent mechanical wear out caused by transformer vibrations Installation shall prevent instrument casing tempera...

Page 7: ...alarm set point as described above Adjust the multi turn adjusting screw located beneath the switch scale plate fully clockwise At this point the differential will be set at 5 C When turned fully anti...

Page 8: ...D76 TD50 5 Amp Max Cont Input at 100 Load 2 2 A from CT 2 65 A from CT 5 0 A from CT Adj Range 0 80 of Input Current from CT 45 85 of Input Current from CT 0 35 of Input Current from CT Insulation 2kV...

Page 9: ...value 4 Connect a multi meter Example Fluke set for resistance measurement to the terminals 5 5 inside the WTI 5 Adjust the matching resistance TD50 or TD76 until you reach the required resistance val...

Page 10: ...djustment of Heating Current Keep cover mounted feed a stable current and wait 45 min before reading winding temperature Gradient C for bulb type 11 12 15 and 18 10 12 14 16 18 20 22 24 26 28 30 Oil t...

Page 11: ...ater current Switching between the heater currents is performed external to the thermometer 5 3 2 Wiring Recommendations The potentiometers are wired to the 56 and 57 terminal block positions The CT i...

Page 12: ...et R5 5 value which will provide the desired heater current see Section 5 1 instructions Re connect the white separable connector After the matching resistance has been set and the white connector is...

Page 13: ...been set and the white connector is re mated the winding simulation input current is wired to the terminal block at the 5 5 positions as shown TD50 POT HEATER CT BLK OUT 2 2A BLK WHT IN 5A WHT WHITE C...

Page 14: ...qualitrolcorp com 6 Mounting Styles and Dimensions 6 1 Seismic Mount Figure 5 Siesmic Mount Special mounting for high amplitude low frequency conditions 6 2 Universal Mount Figure 6 Universal Mount A...

Page 15: ...M 345 Gen2 Instruction Manual Rev No ECN 27992 10 www qualitrolcorp com 6 3 Anti Vibration Standard Mount Figure 7 Anti Vibration Standard Mount Standard mounting highest instrument isolation availabl...

Page 16: ...Removal 4 09 104 11 93 303 3 68 93 11 88 302 Figure 8 Cover Hinge Side View Figure 9 Front Cover Removal Cable glands M25 max 3 and M20 max 2 After unlocking the front cover lift the front cover up fu...

Page 17: ...A 125 VDC 0 5 A 0 05 A 250 VDC 0 25 A 0 03 A GW STANDARD SWITCH MBO GOLD DPDT Figure 10 Switch Selection MBO Magnetic Blow Out high DC switching minimum Electrical Operations 100 000 Cycles all other...

Page 18: ...www qualitrolcorp com 9 Terminal Block Arrangements Figure 11 2 to 4 Switches w Optional Heater and Remotes Figure 11 1 2 to 4 Switches w Optional Heater and Remotes TD50 5 Amp Figure 11 2 2 to 4 Swi...

Page 19: ...Rev No ECN 27992 14 www qualitrolcorp com Figure 12 5 to 6 Switches only Figure 13 5 to 6 Switches w Optional heater and Remotes For options not shown please consult Configuration Form or contact QUA...

Page 20: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 15 www qualitrolcorp com 10 Pocket Well Installation Figure 14 Pocket Well Installation...

Page 21: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 16 www qualitrolcorp com 11 Probe Types...

Page 22: ...into white after saturation If condensation is occurring inside the instrument replacement of the capsules will be necessary part number 47126 12 2 Mountings with Rubber Dampers Seismic Type and Univ...

Page 23: ...r dial measurement range Load 500 max at 24V DC User adjustable output can be used to calibrate output directly to load consult factory Accuracy Relative to local indication 2 C Ambient temperature 40...

Page 24: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 19 www qualitrolcorp com Figure 15 4 20mA Suggested Wiring TD111...

Page 25: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 20 www qualitrolcorp com Figure 15 1 0 1mA Suggested Wiring TD119 1...

Page 26: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 21 www qualitrolcorp com Figure 15 2 0 5mA Suggested Wiring TD119 2...

Page 27: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 22 www qualitrolcorp com Figure 15 3 0 10mA Suggested Wiring TD119 3...

Page 28: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 23 www qualitrolcorp com Figure 15 4 0 20mA Suggested Wiring TD119 4...

Page 29: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 24 www qualitrolcorp com Figure 15 5 4 20mA 0 5V DC Suggested Wiring TD119 5...

Page 30: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 25 www qualitrolcorp com Figure 15 6 4 20mA 0 10V DC Suggested Wiring TD119 5...

Page 31: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 26 www qualitrolcorp com Figure 15 7 Suggested Wiring TD66 CU10 PT100...

Page 32: ...LITROL produces thousands of different types of products on demand each customized to customers unique requirements QUALITROL Field Services QUALITROL provides on site commissioning start up and compr...

Reviews: