background image

Page  6

7019-205C

September 1, 2008

R

Santa Fe Pellet Insert

Location of the appliance and chimney will affect 
performance. 

• 

Install through the warm airspace enclosed by the building 
envelope. This helps to produce more draft, especially 
during lighting and die-down of the fire.

•  Penetrate the highest part of the roof. This minimizes the 

effects of wind loading.

•  Locate termination cap away from trees, adjacent 

structures, uneven roof lines and other obstructions.

•  Minimize the use of chimney offsets. 

• 

Consider the appliance location relative to floor and ceiling 
and attic joists.

B. Locating Your Appliance & Chimney

D. Negative Pressure

 

 

Negative pressure can 

cause spillage of combustion fumes and soot. 

Negative pressure results from the imbalance of air avail-
able for the appliance to operate properly. It can be stron-
gest in lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)

• Range 

hoods

• 

Combustion air requirements for furnaces, water heaters 
and other combustion appliances

• Clothes 

dryers

•  Location of return-air vents to furnace or air conditioning

•  Imbalances of the HVAC air handling system

•  Upper level air leaks such as: 

 - 

Recessed 

lighting

 - 

Attic 

hatch

 - 

Duct 

leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

• 

Ensure adequate outdoor air for all combustion appliances 
and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

• 

Attic mounted duct work and air handler joints and seams 
taped or sealed

C. Draft

Draft is the pressure difference needed to vent appliances 
successfully. When an appliance is drafting successfully, all 
combustion byproducts are exiting the home through the 
chimney.

Considerations for successful draft include:

•  Preventing negative pressure

•  Location of appliance and chimney

OT

 

Hearth & Home Technologies assumes no 

responsibility for the improper performance of the chimney 
system caused by:

Inadequate draft due to environmental conditions

Downdrafts

Tight sealing construction of the structure

Mechanical exhausting devices

CAUTION

•  Do NOT connect this unit to a chimney flue servicing 

another appliance.

•  Do NOT connect to any air distribution duct or system.

Summary of Contents for Santa Fe Pellet Insert SANTAFEI-B

Page 1: ...tarts to glow you are over ring Reduce feed rate Over ring will void your warranty Comply with all minimum clearances to com bustibles as speci ed Failure to comply may cause house re Check building c...

Page 2: ...Type UM 84 HUD FOR USE ONL WITH PELLETI ED WOOD OR SHELLED FIELD CORN FUEL Route power cord away from unit Do not route cord under or in front of appliance DANGER Risk of electrical shock Disconnect p...

Page 3: ...hout Outside Air 14 C Full Reline with Outside Air 15 Section 6 Mobile Home 16 Section 7 Appliance Set Up A Leveling System 17 B Outside Air Kit 17 C Grille Installation 18 D Door Handle Installation...

Page 4: ...installation must conform with local codes In the absence of local codes you must comply with the ASTM E1509 2004 ULC S628 93 ULC ORD C 1482 M1990 UM 84 HUD D Electrical Rating 115 VAC 60 Hz Start 4...

Page 5: ...of the vent termination T O If burning shelled field corn you must use ap proved venting specifically designed for corn to prevent corro sion or degradation Follow the instructions from the venting ma...

Page 6: ...vel air leaks such as Recessed lighting Attic hatch Duct leaks To minimize the effects of negative air pressure Install the outside air kit with the intake facing prevailing winds during the heating s...

Page 7: ...been met 8 The masonry chimney is inspected by a profes sional and is clean or the factory built metal chimney is installed according to the manufac turer s instructions and clearances 9 The chimney...

Page 8: ...ces A Appliance Dimensions Figure 8 3 Front View Figure 8 1 Top View Figure 8 2 Side View 21 1 2 546mm 28 7 8 733mm 23 5 8 600mm 8 203mm C L 12 3 4 324mm 8 5 8 219mm 23 584mm 25 3 8 645mm Panel A B St...

Page 9: ...design preference A C B D C B 0 in Clearance To Exposed Section And Face B Clearance To Combustibles UL and ULC Inches Millimeters A Top of Hopper Top Vent 2 0 51 Rear Vent 2 5 64 B Side of Hopper To...

Page 10: ...ace trim 4 3 4 121 D Insert side to maximum 2 1 4 inch 57mm face trim 10 254 Location Inches Millimeters A Rear Width 24 610 B Depth 16 406 C Height 23 1 4 591 D Front Width 29 1 4 743 Figure10 1 C Ma...

Page 11: ...he installation of the insert only when a 1 4 6mm inch airspace is provided between the insert and the oor of outer wrap Figure 11 1 Measure and mark the metal oor for cutting With a drill make a star...

Page 12: ...on WARNING B Venting Termination Requirements 1 Termination must exhaust above air inlet elevation It is recommended that at least 60 inches 1524mm of verti cal pipe be installed when appliance is ven...

Page 13: ...essure as 1 foot of horizontal pipe and a foot of horizontal pipe is twice as restrictive as a foot of vertical pipe D Pipe Selection Chart The table below can help you calculate the equivalent feet o...

Page 14: ...ney must be 6 inch 152mm UL103 HT WARNING CAUTION Never draw outside combustion air from Wall oor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations re ect typical installa...

Page 15: ...lk ing materials to seal any edge to prevent future serviceability NOTE Check clearances carefully for this type of installation to ensure adequate room for outside air venting Check building codes pr...

Page 16: ...device 5 Refer to clearances to combustibles and oor protection requirements on pages 9 10 for listings to combus tibles and appropriate chimney systems 6 Use silicone to create an effective vapor ba...

Page 17: ...ar assembly 4 Slide trim ring over ex pipe and run pipe through wall 5 Attach hose to outside termination cap with second hose clamp 6 Secure termination cap to outside surface 7 Secure trim ring to i...

Page 18: ...flat installed on the grilles and after the grilles are installed on the appliance they are then finger bent into position 4 Attach the 4 grille bracket covers to the lower 4 grilles and the top 3 gr...

Page 19: ...2 screws on the top and bottom of the face Figure 19 1 2 Pull the face away from the door by rotating the face toward you from the hinge side rst Carefully push the door handle through the opening on...

Page 20: ...xtremely dif cult once trim has adhered to tape Do a dry run rst without removing paper from tape 6 Place cut edge of trim under top lip and into position on scissors Place side pieces on rst and then...

Page 21: ...re are 2 screws for each leg Figure 21 2 2 Open the hopper lid by pulling toward you This will make it easier to set the panels in place Secure the panels to the insert 2 screws per leg as shown in Fi...

Page 22: ...n Optional Firepot Top Log Installation Figure 22 1 Figure 22 2 Figure 22 3 Figure 22 4 Place the log over the repot The charred area on the log is turned toward the back not the front The log will be...

Page 23: ...at is located too close to the appliance you may need to set the temperature setting slightly higher to maintain the desired tem perature in your home 3 There is a 4 screw terminal block located on th...

Page 24: ...e is like most modern furnaces when the thermostat calls for heat your appliance will automatically light and deliver heat When the room is up to temperature and the thermostat is satis ed the red cal...

Page 25: ...l to increase the feed rate and ame height or towards the symbol to decrease the feed rate and ame height 3 Re tighten the wing nut F Feed Rate Adjustment Instructions D Starting Your First Fire 1 A t...

Page 26: ...e appliance With appliance door open Firepot oor open Cleaning slide plates open Do NOT store fuel Closer than required clearances to com bustibles to appliance Within space required for loading or as...

Page 27: ...system is clean Make sure front door is closed Replace control box Call light on No re Partially burned fuel in repot Firepot clean out plate not closed Firepot is dirty missed ignition Check that rep...

Page 28: ...ng loss of vacuum Empty hopper of fuel Use a wet dry vacuum cleaner to remove remaining fuel from hopper including feed tube Check feed chute for obstructions Loosen 2 screws and jiggle feed assembly...

Page 29: ...ting system Remove stainless steel baf e from rebox to clean ash from on top of baf e Clean behind rear brick panels Change fuel brand to pre mium Check that repot clean out plate is fully closed Redu...

Page 30: ...ccur if appliance is not cool before unplugging Risk of shock if appliance not unplugged before servicing appliance CAUTION A Proper Shutdown Procedure Cleaning or Inspection Frequency Daily Weekly Mo...

Page 31: ...on page 26 4 Cleaning Ash Drawer Frequency Weekly or every 5 bags of fuel By Homeowner Locate the ash drawer underneath the repot and slide the ash drawer straight out Empty into a non combustible co...

Page 32: ...rick set 8 Cleaning the Glass Frequency When clear view of the repot is obscure By Homeowner a Appliance must be completely cool before cleaning glass b Use a damp paper towel or any non abrasive glas...

Page 33: ...ust venting system The venting system may need to be cleaned at least once a year or more often depending upon the quality of your fuel or if there is a lot of horizontal pipe sections Ash will build...

Page 34: ...build up exceeds more than half way up the repot By Homeowner Poor quality pellet fuel or lack of maintenance can create conditions that make the repot ll quickly with ashes and clinkers This conditio...

Page 35: ...for shipping purposes only This can be removed once the appliance is installed Lift up blower from the magnet and remove g Re install in reverse order Wing nut plate installed for shipping purposes on...

Page 36: ...igniter wires are clear of any movement i e ash drawer repot cleaning rod cleaning slide plates etc f Re install the ash drawer and then re install the side panel and re connect the power a The door...

Page 37: ...ability Figure 37 4 6 The baf e does not completely cover the top of the rebox There is an opening on the left as shown in Figure 37 5 Tabs Figure 37 4 Figure 37 5 H Baffle Brick Set Removal 1 Follow...

Page 38: ...1 2008 R Santa Fe Pellet Insert Figure 38 2 Hook on left side Tab on right side Figure 38 3 Figure 38 4 Figure 38 5 Lift brick pull forward at an angle and drop down into notches Figure 38 1 Re instal...

Page 39: ...nd red lights have been obtained 15 Thermostat The appliance is designed to run on a 12 volt AC thermostat The heat anticipator if present should be set on the lowest setting available When describing...

Page 40: ...ack of the auger tube in the center of the appliance and has a reset button To access it remove the right side panel If the re tries to burn back into the feed system or push exhaust up the feed tube...

Page 41: ...Junction Box Front Exhaust Collar Power Cord Recpticle Terminal Block Center 2 Screws for Thermostat Wires or Remote 110 Outlet for Remote Control Only unfused Fuse Red Call Light Outside Air Inlet C...

Page 42: ...aning Rod 7019 009 6 Thermocouple Cover 812 1322 7 Igniter Bracket Not Replaceable 8 Igniter SRV7000 226 9 Thermocouple 812 4470 10 Thermocouple Clamp 7001 203 42 Firepot 414 5200 53 Thumb Screw 7000...

Page 43: ...ription 13 Face Right 14 Access Panel 15 Outer Skin Side 16 Snap Disc 3 17 Snap Disc 1 18 Blower Exhaust 19 Exhaust Transition 20 Flue Collar 21 Blower Convection 22 Feed Motor 23 Feed Motor Bracket D...

Page 44: ...019 013 39 Door Hinge Assembly SRV7019 014 2 Door Handle Black Nickel 7019 174 4 Door Latch Assembly 7019 015 3 Door Pin 3 16 x 1 2 7000 229 Door Handle Assembly includes handle set screw pin SRV7019...

Page 45: ...nap Disc 1 110oF Convection Blower 230 1220 27 Snap Disc 2 250oF Fuel Delivery Interrupt Automatic Reset SRV7000 268 16 Snap Disc 3 250oF Burn Back Protector Manual Reset 230 1290 9 Thermocouple 14 in...

Page 46: ...Panel Trim Small 30 h x 40 w Gold SP SFI3040 GD Panel Trim Large 33 h x 50 w Black Nickel SP SFI3350 NB Panel Trim Large 33 h x 50 w Gold SP SFI3350 GD Trim for Door Black Nickel DT SF NB Trim for Do...

Page 47: ...R September 1 2008 7019 205C Page 47 Santa Fe Pellet Insert Date of Service Performed By Description of Service E Service And Maintenance Log...

Page 48: ...Page 48 7019 205C September 1 2008 R Santa Fe Pellet Insert Date of Service Performed By Description of Service E Service And Maintenance Log Cont d...

Page 49: ...R September 1 2008 7019 205C Page 49 Santa Fe Pellet Insert F Homeowner s Notes...

Page 50: ...Conditions Exclusions and limitations 9 01 08 CONDITIONS EXCLUSIONS LIMITATION OF LIABILITY This warranty applies to the original owner and is transferable up to two years from date of purchase to th...

Page 51: ...lorine uorine or other damaging chemicals the appliance is subject to prolonged periods of dampness or condensation or there is any damage to the appliance or other components due to water or weather...

Page 52: ...6053165 6145502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 6769426 6774802 6796302 6840261 6848441 6863...

Reviews: