background image

August 13, 2018 

 

 

 

 

7062-197G 

 

 

 

         

                  15

Explorer I

Trim Collar 

Chimney Section 

with 2 inch 

(51mm) 

Clearance to 

Combustibles

Chimney 

Connector 

Fire Clay Flue 

Liner 

with Airspace 

Masonry 

 Chimney 

Wall Band to 

Secure Chimney 

Section 

Wood Studs Used 

for Framing - Spaced 

2 inch (51mm) 

clearance from 

Masonry Chimney

Wall Spacer 

Solid Pack Chimney with Metal Supports as a Thimble

Figure 15.1

Fire Risk.

Do NOT pack insulation or other combustibles 

between spacers.

• 

ALWAYS maintain specified clearances around 

venting and spacers.

• 

Install spacers as specified.

Failure to keep insulation or other material away 

from vent pipe may cause fire.

WARNING

Chimney Flue

Liner

Fireclay

Liner or

Equivalent

Masonry Chimney

Constructed to NFPA 211

Wall Spacer

Wall Band

Trim Collar

Chimney

 Connector

1 inch (25mm) Air

Space to Chimney

Section

Min. Clearance

2 inch (51mm)

Min. Chimney Clearance to

Wall Spacer and

Combustibles - 2 inch (51mm)

Chimney Section

Figure 15.2

Solid Pack Chimney with Metal Supports as a Thimble 

(Cont’d)

Flue Gas

Direction

Crimped

End

Toward

Appliance

Secure pipe sections with a

minimum of 3 screws

Figure 15.3   Chimney 

Connector  (Appliance Pipe)

G. Installing Chimney Components

Chimney Connector

Single wall connector or appliance pipe.  

This must be at least 24 gauge mild steel or 26 gauge blue 

steel.  The sections must be attached to the appliance and 

to each other with the crimped (male) end pointing toward 

the appliance.  All joints, including the connection at the flue 

collar, should be secured with 3 sheet metal screws.  Make 

sure to follow the minimum clearances to combustibles.   

Where passage through the wall, or partition of combustible 

construction is desired in Canada, the installation shall 

conform to CAN/CSA-B365.

Factory-built listed chimney connector (vented).

A listed connector (vented) must be used when installing 

this appliance in a mobile home.  The listed connectors 

must conform to each other to ensure a proper fit and seal.

WARNING

Fire Risk.

Follow Chimney Connector Manufacturer’s 

Instructions for Proper Installation.

ONLY use connector:

• 

Within the room, between appliance and ceiling or 

wall.

Connector shall NOT pass through:

•  Attic or roof space

•  Closet or similar concealed space

•  Floor or ceiling

Maintain minimum clearances to combustibles

NOTE:

 Optional Fire Screen, Part SCR-7062, can only 

be used in FULL Vertical installations.

H. Proper Draft

To be sure that your Quadra-Fire insert burns properly, the 

chimney draft (static pressure) should be approximately 

-0.10 inches water column (W.C.) during a high burn and 

-0.04 inches W.C. during a low burn, measured 6 inches 

(152mm) above the top of the insert after one hour of 

operation at each burn setting.

Summary of Contents for EXPLORER I

Page 1: ...endeur ou visitez www quadrafire com If the information in these instructions is not followed exactly a fire could result causing property damage personal injury or death WARNING Do not store or use g...

Page 2: ...Chimney Termination Requirements 12 C 2 10 3 Rule 12 D Chimney Height Rise and Run 13 E Venting Components 13 F Chimney Systems 13 G Installing Chimney Components 15 H Proper Draft 15 5 Appliance Set...

Page 3: ...the water in the fuel A range of BTU outputs based on EPA Default Efficiency and the burn rates from the low and high EPA tests using Douglas Fir dimensional lumber The peak BTU out of the appliance i...

Page 4: ...affle and other interior components NOTE Hearth Home Technologies manufacturer of this appliance reserves the right to alter its products their specifications and or price without notice Improper inst...

Page 5: ...himney heights Ideal performance is with height of chimney between 14 16 feet 4 26 4 88m measured from the base of the appliance C Negative Pressure Negative pressure results from the imbalance of air...

Page 6: ...ing winds during the heating season Ensure adequate outdoor air for all combustion appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate vi...

Page 7: ...iance and given to the party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this check...

Page 8: ...2 Side View with vertical flue 10 3 4 274mm 17 3 4 451mm 27 3 4 705mm 25 1 2 650mm 26 7 8 683mm Figure 8 3 Top View 3 77mm 13 3 8 342mm 1 4 7mm 3 8 12mm 25 1 2 648mm 28 5 8 728mm Figure 8 4 Side View...

Page 9: ...pecified High temperatures or hot embers may ignite concealed combustibles Figure 9 1 Figure 9 4 Figure 9 3 Figure 9 2 Figure 9 5 Figure 9 6 Corner hearth pad dimensions with single wall pipe Corner h...

Page 10: ...A N A 53 1 2 1359 N A DOUBLE WALL PIPE N A 8 203 24 607 11 279 N A N A 53 1 2 1359 N A For alcove only Six inch diameter listed Double wall air insulated connector pipe with UL103 HT listed factory b...

Page 11: ...space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind...

Page 12: ...or when there are other factors that affect flue draft B Chimney Termination Requirements Follow manufacturer s instructions for clearance securing flashing and terminating the chimney Figure 12 1 12...

Page 13: ...isted Chimney Storm Collar Wall Support Roof Brace if required Thimble Figure 13 1 Prefabricated Exterior Chimney E Venting Components Chimney Connector It is also known as flue pipe or appliance pipe...

Page 14: ...y Figure 14 2 2 Entry hole to masonry chimney must be lined with an 8 inch 203mm minimum diameter clay liner or equivalent secured with refractory mortar 3 Construct a 17 inch x 17 inch 432mm x 432mm...

Page 15: ...is must be at least 24 gauge mild steel or 26 gauge blue steel The sections must be attached to the appliance and to each other with the crimped male end pointing toward the appliance All joints inclu...

Page 16: ...aterials from packing box 2 Floor Rear Installation Cut a 4 inch 102mm hole in outside wall or floor to accommodate outside air piping Use 4 inch 102mm aluminum metal flex or rigid piping to directly...

Page 17: ...gnet under the bottom left rear corner See Owner s Manual for detailed operating instructions for the blower and snap disc Figure 17 1 Shock Risk Do NOT remove grounding prong from plug Route cord awa...

Page 18: ...m appliance 4 Phillips screws as shown in Figure 18 1 3 Remove rotate 180 degrees and install cast flue transition in the horizontal position as shown in Figures 18 1 and 18 2 4 Install convection shr...

Page 19: ...ion requirements must be followed precisely 9 Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure NOTE Of...

Page 20: ...20 7062 197G August 13 2018 Explorer I Date of Service Performed By Description of Service 7 Reference Materials A Service Maintenance Log...

Page 21: ...39 Outside Air Shield SRV33271 Y Firescreen SCR 7062 FASTENERS Avk Rivnut Repair Kit 1 4 20 3 8 16 Rivnut Tools RIVNUT REPAIR Y Nut Ser Flange Small 1 4 20 Pkg of 24 226 0130 24 Y Screw Pan Head Phili...

Page 22: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: