9
7033-361B
November,
2021
Figure 9.1
Figure 9.3
Figure 9.2
D. Clearances to Combustibles
G
D
E
H
C
A
I
B
F
F
J
J
G
G
L
L
K
K
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS in Millimeters
Note: A, C, and F Dimensions are to the center of the flue collar
3100 Millennium AU Wood Appliance
INSTALLATION
345 175 668 360
76
225 800 1062 300
DOUBLE WALL PIPE
A
B
C
D
E
F
G
H
756 1197
I
J
1469
K
L
NOTE: Service Space
In order to replace the tube channel assembly a clearance of 483mm is required on the right side of appliance in order
to remove the tubes with the appliance in place.
If space is not available, the appliance will have to be disconnected from the chimney to proceed with the tube
replacement.