CONFIGURATION
Page 22
Q23 Expansion Module
Configuration Jumpers
The following list describes the function of each of the configuration jumpers on the Q23 Module:
J1
This jumper selects the output voltage range for Analog output channel No. 6. Open is 0 to 5V/0 to 20mA
output range whilst closed is 0 to 10V output range.
J2
This jumper selects the output voltage range for Analog output channel No 5. Open is 0 to 5V/0 to 20mA
output range whilst closed is 0 to 10V output range.
J3
This 2 way jumper selects the output mode of Analog output channel No 6. Pins 1 & 2 closed is current
output mode whilst 2 & 3 closed is voltage output mode.
J4
This 2 way jumper selects the output mode of Analog output channel No 5. Pins 1 & 2 closed is current
output mode whilst 2 & 3 closed is the voltage output mode.
J5
This 2 way jumper selects the single ended input range of Analog input channel No. 2. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.
J6
This 2 way jumper selects the single ended input mode of Analog input channel No. 2. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.
J7
This 2 way jumper selects the single ended input range of Analog input channel No. 1. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.
J8
This 2 way jumper selects the single ended input mode of Analog input channel No. 1. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.
J9
This 2 way jumper selects the single ended input range of Analog input channel No. 3. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.
J10
This 2 way jumper selects the single ended input mode of Analog input channel No. 3. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.
J11
This 2 way jumper selects the single ended input range of Analog input channel No. 4. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.
J12
This 2 way jumper selects the single ended input mode of Analog input channel No. 4. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.
J13
This 2 way jumper selects the single ended input range of Analog input channel No. 5. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.
J14
This 2 way jumper selects the single ended input mode of Analog input channel No. 5. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.
J15
This 2 way jumper selects the single ended input range of Analog input channel No. 6. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.
J16
This 2 way jumper selects the single ended input mode of Analog input channel No. 6. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.
J17
This 2 way jumper selects the input mode of Analog input channels No’s 1 & 2. Pins 1 & 2 closed is one
differential input channel. Pins 2 & 3 closed is two single ended input channels.
J18
This 2 way jumper selects the input mode of Analog input channels No’s 3 & 4. Pins 1 & 2 closed is one
differential input channel. Pins 2 & 3 closed is two single ended input channels.
J19
This 2 way jumper selects the input/output mode of Analog channel 5. Pins 1 & 2 closed is output mode,
whilst 2 & 3 closed is input mode.
J20
This 2 way jumper selects the input/output mode of Analog channel 6. Pins 1 & 2 closed is output mode,
whilst 2 & 3 closed is input mode.
J21
This jumper selects the single ended/differential input mode for Analog input channels 1 & 2. Closed is
single ended input for channel 1, whilst open is differential input for channels 1 & 2.
J22
This jumper selects the single ended/differential input mode for Analog input channels 3 & 4. Closed is
single ended input for channel 3, whilst open is differential input for channels 3 & 4.
J23
This jumper selects the remote power control function enabled/disabled. Closed is power always ON,
while open is power controlled by the remote power control line.
Summary of Contents for Q23
Page 1: ...Q23 Expansion Module Owners Manual...
Page 2: ......
Page 4: ......
Page 5: ...REVISION DETAILS 1 01 Nov 2001 Original 1 02 Oct 2010 Updated logo and typos...
Page 6: ......
Page 28: ......
Page 32: ......
Page 40: ......
Page 48: ......