QOLSYS IQSmoke Installation Manual Download Page 4

4

INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide

4.  Reinstall  the  detector  onto  the  mounting  base  by  turning  the 

detector clockwise until the mating marks align.

5.  After  the  power-up  sequence  the  green  LED  should  blink  about 

once every 12 seconds to indicate normal operation. If the batteries 
are  not  installed  correctly,  the  detector  will  not  operate  and  the 
batteries may be damaged. If the detector does not power-up, check 
for correct batteries installation and for a fully charged batteries.

6.  Test the detector (as described later).

CONSTANT EXPOSURES TO HIGH OR LOW TEMPERATURES OR HIGH 
HUMIDITY MAY REDUCE BATTERY LIFE.

PROGRAMMING

Refer to the appropiate compatible control panel programming guide 
for  the  proper  procedure  required  to  enroll  the  wireless  smoke/heat 
into the system.

RECOMMENDED LOCATIONS FOR SMOKE HEAT ALARM

According  to  National  Fire  Protection  Association  (NFPA)  the  major 
threat  from 

fi

 re  in  a  dwelling  unit  occurs  at  night  when  everyone  is 

asleep.  The  principal  threat  to  persons  in  sleeping  areas  comes  from 

fi

 res in the remainder of the unit; therefore, a smoke detector(s) is best 

located between the bedroom areas and the rest of the unit. In units 
with only one bedroom area on one 

fl

 oor, the smoke detector(s) should 

be located as shown in Figure 2. In dwelling units with more than one 
bedroom  area  or  with  bedrooms  on  more  than  one 

fl

 oor,  more  than 

one smoke detector is required, as shown in Figure 3.
In  addition  to  smoke  detectors  outside  of  the  sleeping  areas,  the 
device  should  be  installed  on  each  additional  story  of  the  dwelling 
unit, including the basement. These installations are shown in Figure 
4.  The  living  area  smoke  detector  should  be  installed  in  the  living 
room or near the stairway to the upper level, or in both locations. The 
basement smoke detector should be installed in close proximity to the 
stairway leading to the 

fl

 oor above. Where installed on an open-joisted 

ceiling, the detector should be placed on the bottom of the joists. The 
detector should be positioned relative to the stairway so as to intercept 
smoke coming from a 

fi

 re in the basement before the smoke enters the 

stairway.
Smoke detectors are optional where a door is not provided between 
living  room  and  recreation  room  (Figure  5).  The  smoke  from  a 

fi

 re 

generally rises to the ceiling, spreads out across the ceiling surface, and 
begins  to  bank  down  from  the  ceiling.  The  corner  where  the  ceiling 
and wall meet is an air space into which the smoke could have dif

fi

 culty 

21

Guide d'installation du détecteur de chaleur et de fumée sans 

fi

 l INST APD0595 A140618

Des changements ou modi

fi

 cations non autorisés pourraient entraîner l’annulation 

de l’autorisation d’exploiter l’équipement.
Cet appareil est conforme à la partie 15 de la réglementation de la FCC et aux normes 
RSS sur les appareils exempts de licence d'Industrie Canada. Son fonctionnement 
est  soumis  aux  deux  conditions  suivantes

 

:  (1)  Ce  dispositif  ne  doit  pas  causer 

d’interférences nuisibles, et (2) cet appareil doit accepter toute interférence reçue, y 
compris les interférences pouvant causer un fonctionnement inopiné de l’appareil.
Cet  équipement  a  été  testé  et  déclaré  conforme  aux  limites  applicables  aux 
périphériques numériques de classe B, selon la partie 15 de la réglementation de 
la FCC. Ces limites ont été conçues pour fournir une protection raisonnable contre 
les interférences nuisibles en milieu résidentiel. Cet équipement produit, utilise et 
peut émettre de l’énergie de fréquence radio. Si l’équipement n’est pas installé et 
utilisé conformément aux instructions fournies, il peut provoquer des interférences 
néfastes aux communications radio. Cependant, la possibilité qu'une interférence 
se produise dans une installation particulière n’est pas totalement exclue. Si cet 
équipement  ne  produit  pas  d'interférences  nuisibles  à  la  réception  radio  ou 
télévision, ce qui peut être déterminé en éteignant et en rallumant l’équipement, 
il  est  recommandé  à  l’utilisateur  d'essayer  de  remédier  aux  interférences  en 
appliquant l’une ou plusieurs des mesures suivantes

 

:

•  Réorientez ou déplacez l’antenne de réception.
•  Augmentez la distance qui sépare l’équipement du récepteur
•  Branchez  l’équipement  à  une  prise  située  sur  un  circuit  différent  de  celui 

auquel le récepteur est connecté.

•  Consultez le revendeur ou un technicien radio/TV expérimenté pour obtenir 

de l’aide

«

 

Pour votre information, la norme NFPA 72 du code national d’alarme incendie 

stipule que

 

:

«

 

Détection requise 11.5.1

 

»

«

 

Lorsque cela est requis par les lois, des codes ou normes applicables pour un type 

spéci

fi

 que d’habitation, les détecteurs de fumée simples et multipostes approuvés 

seront installés de la manière suivante

 

:

1.  Dans les chambres à coucher et chambres d'amis
2.  À l’extérieur de chaque chambre à coucher d'une maison d'habitation, à 6,4

 

(21

 

pieds) de toute porte donnant sur une chambre à coucher, la distance 

étant mesurée le long d’un chemin de circulation

3.  À chaque niveau d’une maison d’habitation, y compris les sous-sols
4.  À chaque niveau d’un foyer résidentiel et d'un établissement de soins (petit 

établissement), y compris les sous-sols et excepté les vides sanitaires et les 
combles inachevés

5.  Dans la salle de séjour d'une suite d'amis
6.  Dans la salle de séjour d’un foyer résidentiel et d'un établissement de soins.

(Réimprimé avec la permission de la norme NFPA 72®, du code national d’alarme 
incendie Copyright © 2007 National Fire Protection Association, Quincy, MA 02269. 

Summary of Contents for IQSmoke

Page 1: ...ns an integrated fixed 41 F temperature freeze sensor that will send a warning signal based on temperature detected This detector is designed to provide protection with 70 foot spacing capability The detector can send alarm tamper and battery condition messages to the system s receiver Refer to the wireless system s instruction for the maximum number of transmitters that can be supported CONTENTS ...

Page 2: ...oke Heat Alarm contains a sounder which generates the ANSI S3 41 temporal 3 pattern in an alarm condition In alarm a message is also sent to the control panel and the detector s ID is displayed at the console During an alarm condition pressing the detector s hush button will silence the sounder see table below The mounting base installation is simplifi ed by the incorporation of features compatibl...

Page 3: ...anel will display a loss of supervision message Low Battery Detection The Wireless Smoke Heat Alarm is powered by 3 AAA Duracell Procell or 3 AAA Energizer E92 batteries included The detector regularly checks for a low battery If a low battery is detected the transmitter sends a low battery message to the control panel which displays the detector s ID at low battery In addition the yellow LED of t...

Page 4: ...ions non autorisés pourraient entraîner l annulation de l autorisation d exploiter l équipement Cetappareilestconformeàlapartie15delaréglementationdelaFCCetauxnormes RSS sur les appareils exempts de licence d Industrie Canada Son fonctionnement est soumis aux deux conditions suivantes 1 Ce dispositif ne doit pas causer d interférences nuisibles et 2 cet appareil doit accepter toute interférence re...

Page 5: ...incluses trois 3 piles AAA PC2400 Duracell Procell ou trois 3 piles AAA Energizer E92 Liste de matériels homologués réglementaires UL 217 Garantie deux 2 ans Accessoires inclus Trousse de matériel de montage INFORMATIONS RÉGLEMENTAIRES 5 penetrating In most fires this dead air space measures about 0 1m 4in along the ceiling from the corner and about 0 1m 4in down the wall Detectors should not be p...

Page 6: ...échapper même si elles sont averties suffisamment tôt pour qu une évacuation soit possible Pour ces personnes d autres stratégies tellesquedesmesuresdeprotection uneévacuationouunsecoursassistéseraient nécessaires Un détecteur alimenté par piles doit avoir des piles du type spécifié en bon état et convenablement installées Les détecteurs de fumée doivent être régulièrement testés pour s assurer qu...

Page 7: ...ur L extérieur du détecteur peut être essuyé avec un chiffon humide Après nettoyage réinstallez et testez votre détecteur à l aide du bouton de test Si le nettoyage ne restaure pas le fonctionnement normal de l alarme le détecteur doit être remplacé 7 INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide TESTING THE DETECTOR NOTE Before testing notify the central station that the detector s...

Page 8: ... or 2 minutes Planning and practicing for fire conditions with a focus on rapid exit from the residence are important Drills should be held so that all family members know the action to be taken SAFETY TIPS Make a home escape plan Draw a map of your home showing all doors and windows Discuss the plan with everyone in your home 17 Guide d installation du détecteur de chaleur et de fumée sans fil IN...

Page 9: ... DE FUM E SgIL NgY A PAS DE PORTE ENTRE LE SALON ET LA SALLE DE JEUX NSTALLATION D UN D TECTEUR DE FUM E REQUISE NTR E HAMBRE 3ALON 3ALLE Ë MANGER AVE NTR E HAMBRE 100 4 i Fig 5 QVWDOODWLRQ GDQV XQH PDLVRQ j GHPL QLYHDX Fig 4 8Q GpWHFWHXU LQVWDOOp j FKDTXH pWDJH 9 INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide Know at least two ways out of every room if possible Make sure all doors a...

Page 10: ...a base de montage en tournant le détecteur dans le sens horaire jusqu à ce que les repères soient alignés 5 Après la mise sous tension la DEL verte devrait clignoter une fois toutes les 12 secondes environ pour indiquer un fonctionnement normal Si les piles ne sont pas correctement installées le détecteur ne fonctionnera pas et les piles risquent d être endommagées Si vous ne parvenez pas à mettre...

Page 11: ...lacez les piles dès que les bips sonores recommencent Assurez vous de remplacer les anciennes piles par des neuves INSTALLATION ET REMPLACEMENT DES PILES Pour remplacer les piles 1 Déposez le détecteur de son socle de fixation en le tournant dans le sens antihoraire Enlevezlespilesetmettez lesaurebutselonlesréglementations locales 2 Afin de garantir une mise hors tension appropriée attendez 20 sec...

Page 12: ...r le bouton pour l arrêter pendant 5 à 10 minutes Test de fumée Clignote en rouge chaque seconde ANSI S3 41 temporel 3 appuyez sur le bouton pour l arrêter pendant 5 à 10 minutes Tester le détecteur Clignote en rouge chaque seconde ANSI S3 41 temporel 3 Alarme de gel Clignote en jaune 3 fois toutes les 4 secondes Désactivé Défaut du détecteur Clignote en jaune toutes les 4 secondes Un bip sonore t...

Reviews: