UG-1084
ePAQ-9405
User’s Guide
Copyright © 2017 QEI
Status
17
9.1 Status Keying Source
+
-
The status keying voltage source on TB3 pins 9/10 (+) and 11/12 (-) is factory
configured for one of three options as follows:
Keying source comes from an internal ePAQ 24Vdc isolated power source.
Keying source comes from the ePAQ input power source. For example, if the ePAQ is
running on 48Vdc, then the status keying source will be 48Vdc.
No keying source provided. TB3C-9/10 and TB3C-11/12 may be used as tie points for
the user provided keying voltage source.
9.2 Status Connection Diagram
Summary of Contents for DIO-9110