background image

 

 

 

 

UG-1084 

ePAQ-9405 

User’s Guide 

December 2018 

Summary of Contents for DIO-9110

Page 1: ...UG 1084 ePAQ 9405 User s Guide December 2018 ...

Page 2: ...escribed to improve reliability function or design QEI does not assume liability arising out of the application or use of any product or circuit described herein neither does it convey any license under its patent rights nor the rights of others This manual and all data contained constitutes proprietary information of QEI and shall not be reproduced copied or disclosed to others or used as the bas...

Page 3: ...ser s Guide ePAQ 9405 User s Guide Revisions i Revisions Revision Description Date A Initial Release April 19 2016 B Client and Server updates April 29 2016 C Formatting Update June 6 2017 D Changed QEI Address Dec 7 2018 ...

Page 4: ......

Page 5: ...7 1 Port 1 J3 USB Maintenance Panel 9 7 2 Port 2 J4 RS 232 9 7 3 Port 3 J5 Fiber Optic 10 7 4 Port 4 TB5 RS485 10 7 5 Port 5 J6 or J7 Ethernet 100BaseFX 100BaseT 11 7 6 Port 6 J1 or J2 or TB4 Irig B Time Sync 12 8 Controls 13 8 1 Momentary Form 1C Controls 13 8 2 Momentary Form 1X or 1A Controls 14 8 3 Latching Form 1C Control Connections 15 9 Status 16 9 1 Status Keying Source 17 9 2 Status Conne...

Page 6: ...Connection Ethernet Port 27 15 5 Security 27 15 6 Help for Test Panel Commands 28 15 7 DATE and TIME Commands 29 15 8 Reading Analog Values RA 29 15 9 Reading Status Values RS 30 15 10 Reading Accumulator Values RC 31 15 11 Relay Control 32 15 11 1On Relay Operation CN 32 15 11 2Off Relay Operation CF 33 15 12 Communication Checks 33 15 12 1CONFIG Command 33 15 12 2PRX Command 34 15 13 Displaying ...

Page 7: ...s with 1 msec Sequence of Events SOE and time tagging in critical environments where highly secure operation is required Local diagnostics and configuration are accomplished via a Maintenance Port USB connection to a PC The maintenance port is used to send read configuration settings and perform diagnostic functions Features include a real time clock with power failure backup circuitry no battery ...

Page 8: ...inal block TB5 Port 5 100BaseFX Interface Ethernet IEEE 802 3u compliant Protocols IP TCP UDP Bit Rate Up to 100 Mbps Connector ST multimode J6 Port 5 10 100BaseT Interface Ethernet IEEE 802 3 compliant Auto MDI MDI X Protocols IP TCP UDP Bit Rate Up to 100 Mbps Connector Shielded RJ45 J7 Port 6 Irig B Interface Interface Fiber Optic RS485 BNC Protocol Irig B Connectors ST multimode J1 3 pin termi...

Page 9: ...2 Options Important See ordering information and Keying Source section elsewhere in this guide Analog Point Interface Addressability 4 points Scaling options 0 1mA 0 20mA 0 5Vdc Power Input Voltage 12 24 48 125VDC 120 240 277VAC Note 1 Current 18VA max Connector 6 pin terminal block TB1 Note 1 277VAC Tol 5 Max Other Inputs 10 Environment Temperature 40 to 85o C Humidity 5 to 95 70o C non condensin...

Page 10: ...40 or 277Vac Input power connections are made at terminal block TB1 H L L H TB1 PIN Name Description 1 Chassis Connection 2 Chassis Connection 3 L DC Neg AC Neut 4 L DC Neg AC Neut 5 H DC Pos AC Line 6 H DC Pos AC Line 4 Switches 4 1 Power Switches The ePAQ 9405 includes front panel mounted toggle switches for power on off and local remote functions A front panel fuse is also provided L R FUSE POW...

Page 11: ... bank of four DIP switches is available through the front panel Dip switches are used for application specific options see the appropriate ConfigWiz 2 0 addendum for further information The exception is switch 1 which is used for safe boot mode OPTIONS FRONT PANEL LABEL Options Dip switch bank of 4 switches Switch 1 UP Safe Mode Boot on power cycle as follows Ethernet IP default set to 100BaseT po...

Page 12: ...There are six LEDs arranged as three Trip Close pairs for the three control points LED Name Function CONTROL 1 3 Control Relay Output Indication LEDs For each LED pair Left LED indicates TRIP relay coil is energized Right LED indicates CLOSE relay coil is energized 6 2 Status LEDs There are twelve LEDs for the twelve status points 6 12 5 11 4 10 3 9 2 8 1 7 STATUS LED Name Function STATUS 1 12 Sta...

Page 13: ...CTIVITY IRIG B Activity LED This LED turns on whenever a valid IRIG B time sync message is received by the ePAQ via unmodulated Fiber J1 or RS485 TB4 input or via modulated input J2 6 4 L R Local Remote LED A single LED turns on whenever the Local Remote switch is in the Local position F U E F U S S E F U S E POWER FUSE L R LED Name Function L R Local mode indication LED This LED turns on whenever...

Page 14: ...d Ethernet ports High Speed Link Network Activity L A HS R T R T RS 232 J4 Tx Rx Tx Rx J5 J6 10 100 J7 ETHERNET PORT 5 COMM PORT 3 PORT 2 PORT 4 R T RS 485 LED Name T R Dual LED arrays indicate TX and RX data for communications ports 2 3 and 4 The arrays are located to the left of each port The upper LED of each array indicates data transmitted out from the port The lower LED indicates data receiv...

Page 15: ... 1 via ConfigWiz 2 0 to download configurations and flashload program link files 2 via Hyperterminal or other such terminal emulator program to gain access to included test panel functions For a list of available functions refer to the Test Panel section in this user guide J3 MAINT PORT 1 7 2 Port 2 J4 RS 232 An 8 pin RJ45 connector pin 1 bottom left is used for connections to an external communic...

Page 16: ...er using ST connectors A wide variety of communications bit rates can be supported R T Tx Rx J5 COMM PORT 3 J5 ST Jacks Signal Name TX Transmit data output RX Received data input 7 4 Port 4 TB5 RS485 This port is a standard 2 wire RS 485 and conforms to the RS 485 specification It uses surge suppression circuitry to clamp any input voltage transient and noise to chassis ground The port is capable ...

Page 17: ...X 100BaseT This single port accepts either a multimode fiber transceiver with ST connectors J6 or a shielded RJ45 jack for CAT5 cable J7 It supports either 100BaseFX Ethernet over fiber or 100BaseT Ethernet over copper Do not use both connectors at once L A HS Tx Rx J6 10 100 BASET J7 ETHERNET PORT 5 J6 ST Jacks Signal Name TX Transmit data output RX Received data input ...

Page 18: ... RJ45 PIN Signal Name 1 TX 2 TX 3 RX 4 5 6 RX 7 8 7 6 Port 6 J1 or J2 or TB4 Irig B Time Sync This single port accepts input from an Irig B receiver for time syncing the internal ePAQ 9405 timeclock Time sync Input can come from an either an unmodulated or modulated Irig B source J2 Rx Tx J1 ACTIVITY IRIG PORT 6 IRIG RS 485 ...

Page 19: ...r of momentary relays one for trip and one for close or as a single latching relay trip close See the ordering information to choose controls as momentary or latching on a per point basis 8 1 Momentary Form 1C Controls Momentary Form 1C control points use two sets of form 1C SPDT contacts one set for Trip the other set for Close at the terminal blocks For the illustration above T Trip LED C Close ...

Page 20: ...M TB2B 2 Control Point 2 Close N O TB2B 3 Control Point 3 Close N C TB2B 4 Control Point 3 Trip COM TB2B 5 Control Point 3 Trip N O TB2B 6 Control Point 3 Trip N C TB2B 7 Control Point 3 Close COM TB2B 8 Control Point 3 Close N O TB2B 9 Control Point 3 Close N C 8 2 Momentary Form 1X or 1A Controls Momentary Form 1A or 1X Double Make control points use two sets of form 1A SPST contacts one set for...

Page 21: ... Trip COM TB2A 2 Control Point 1 Trip N O TB2A 4 Control Point 1 Close COM TB2A 5 Control Point 1 Close N O TB2A 7 Control Point 2 Trip COM TB2A 8 Control Point 2 Trip N O TB2B 1 Control Point 2 Close COM TB2B 2 Control Point 2 Close N O TB2B 4 Control Point 3 Trip COM TB2B 5 Control Point 3 Trip N O TB2B 7 Control Point 3 Close COM TB2B 8 Control Point 3 Close N O Connection Name TB2A 4 Control P...

Page 22: ...g configuration 6 12 5 11 4 10 3 9 2 8 1 7 STATUS 1 2 3 4 ANALOG 9 1 Connection Name TB3A 1 Status Point 1 TB3A 2 Status Point 1 TB3A 3 Status Point 2 TB3A 4 Status Point 2 TB3A 5 Status Point 3 TB3A 6 Status Point 3 TB3B 9 Status Point 11 TB3B 10 Status Point 11 TB3B 11 Status Point 12 TB3B 12 Status Point 12 TB3C 9 Keying Voltage Source TB3C 10 Keying Voltage Source TB3C 11 Keying VoltageSource ...

Page 23: ...ee options as follows Keying source comes from an internal ePAQ 24Vdc isolated power source Keying source comes from the ePAQ input power source For example if the ePAQ is running on 48Vdc then the status keying source will be 48Vdc No keying source provided TB3C 9 10 and TB3C 11 12 may be used as tie points for the user provided keying voltage source 9 2 Status Connection Diagram ...

Page 24: ...ble See the ordering information to choose the appropriate analog scaling configuration 6 12 5 11 4 10 3 9 2 8 1 7 STATUS 1 2 3 4 ANALOG 10 1 Analog Connections Connection Name TB3C 1 Analog Point 1 TB3C 2 Analog Point 1 TB3C 3 Analog Point 2 TB3C 4 Analog Point 2 TB3C 5 Analog Point 3 TB3C 6 Analog Point 3 TB3C 7 Analog Point 4 TB3C 8 Analog Point 4 ...

Page 25: ... CD A special ePAQ 9405 Template is required to configure the ePAQ 9405 using the ConfigWiz 2 0 software See the ConfigWiz 2 0 Users Guide UM 2018 and the ePAQ 9405 Addendum for more specific configuration information 11 1 Communications Protocols The following Server and Client Protocols are included in the ePAQ 9405 Servers DNP 3 up to 3 Servers Modbus up to 3 Servers QUICS up to 2 Servers Event...

Page 26: ...cal Outline L A HS R T R T 16 15 14 6 12 5 11 4 10 3 9 2 8 J3 J2 Rx Tx RS 232 J1 J4 Tx Rx Tx Rx J5 J6 10 100 BASET J7 ACTIVITY IRIG PORT 6 ETHERNET PORT 5 COMM PORT 3 PORT 2 PORT 4 MAINT PORT 1 IRIG R T H L L H 1 CONTROL 2 3 1 7 STATUS 13 POWER FUSE L R RS 485 RS 485 OPTIONS HBT PWR ...

Page 27: ...e 1 05 12Vdc keying w internal non isolated keying voltage source Note 2 06 24Vdc keying w internal non isolated keying voltage source Note 2 07 48Vdc keying w internal non isolated keying voltage source Note 2 08 125Vdc keying w internal non isolated keying voltage source Note 2 09 24Vdc keying w internal isolated 24Vdc keying voltage source Note 3 C Relay Point 1 Option 0 None 1 Two Momentary KU...

Page 28: ...ltage source is provided by the customer An isolated or non isolated source can be used The TB3C right most end terminals may be used as tie points for the customer s keying voltage The proper keying voltage option must be selected to match the customer provided keying voltage source Note 2 Internal non isolated keying voltage source is tapped from the DIO 9110 input voltage source and appears at ...

Page 29: ...line no connection with the Master Subsystem testing of status analog accumulator pulse count and control points The test panel can also serve as a troubleshooting aid for the Remote Subsystem hardware and or firmware The test panel is designed to be used by qualified service personnel having a background in digital telemetry and SCADA systems and must be familiar with the ePAQ and its intended us...

Page 30: ...g points displayed can consist of the 4 hardware analog points connections at ePAQ terminal block TB3C as well as other analog points within the overall subsystem 15 3 2 Status Monitoring In this mode of operation the test panel will display the status on or off of every point on one 1 to four 4 selected 16 point status groups at a time as they are being processed within the ePAQ 9405 Subsystem St...

Page 31: ...e PC s HyperTerminal or other communications program The USB driver makes the ePAQ USB connection appear to the PC as a COM port connection Before installing the driver check which COM ports are already installed on your Windows XP system using Windows Device Manager This information will be needed when establishing a new HyperTerminal session for test panel communications after the driver is inst...

Page 32: ...ed begins flashing 3 Connect the USB cable from the ePAQ to the PC 4 Start the PC HyperTerminal program 5 When prompted for New Connection name use ePAQ 9405 or similar 6 When prompted for connection parameters Connect To box display for Connect Using select the COM port this will be a new COM port number that was created after the installation of the ePAQ USB driver Click on OK to go to the COM P...

Page 33: ... the ConfigWiz 2 0 software See the ConfigWiz 2 0 Guide for further information 5 The Port number is always 57222 6 After entering this information press the enter key on the PC and verify that a prompt is returned from the ePAQ 7 Save the HyperTerminal session for future use File Save As 15 5Security Test Panel security can be set up using the ConfigWiz 2 0 configuration software Using ConfigWiz ...

Page 34: ...se as backups Using the test panel SAVE and RESTORE commands each configuration file can be stored in non volatile memory and recalled when needed Using ConfigWiz 2 0 the user can assign a unique ID string for each configuration file This ID string will appear at the test panel user prompt to let the user know which configuration file is active All the commands to read the database have a similar ...

Page 35: ...6 Current Date is Thu 09 21 2000 3 To enter or view the current time type TIME enter The following will be displayed Current Time Is 15 52 20 Enter New Time 4 To enter New Time type the new time in the format shown at the cursor To accept the current time type enter 5 Then the new time if entered and the date will be displayed Current Time Is 15 53 20 Current Date Is Thu 09 21 2000 15 8 Reading An...

Page 36: ... the ENTER key the analog points previously entered will scroll upwards to the next line on the display and all values will be frozen not updated Then repeat step 1 by entering RA space and the desired analog point numbers This procedure can be continued to examine every analog point in the RTU if desired To monitor accumulators with timing PDMs and reference analogs perform step 1 by entering RA ...

Page 37: ...dditional status groups points are to be examined press the ENTER key the status group points previously entered will scroll upwards to the next line on the display and all values will be frozen Then repeat step 1 by entering RS and the desired status group numbers This procedure can be continued to examine every status group in the RTU if desired NOTE Over a Remote test panel connection this comm...

Page 38: ...you will be prompted to re enter a valid username and password combination 15 11Relay Control CAUTION THE FOLLOWING PROCEDURE WILL ENERGIZE RELAYS CONNECTED TO CONTROL POINTS MAKE CERTAIN THAT EITHER IT IS SAFE TO COMMAND THE POINT OR THAT THE FIELD DEVICE IS DISCONNECTED FROM THE RELAY NOTE When connected to the test panel via a Remote connection Relay Control commands are not available for secur...

Page 39: ... system documentation for further information 15 12Communication Checks Several test panel commands are associated with ePAQ communications testing The test panel can be used to identify port configuration and to monitor communications between the ePAQ and Master Station 15 12 1 CONFIG Command This command is used to check some of the communications port configuration information including port ty...

Page 40: ... timeout has elapsed When you attempt to exit from this command by pressing Enter you will be prompted to re enter a valid username and password combination Example Type PRX 2 enter The Test Panel will display the messages between the Master and RTU Port 1 in hexadecimal format 02 a84b00a6 02 25a24b00d4060000d03600000ba56000098760000d496000dcb6000090d600 02 f60000fe160100a2360100ee56d146c076010080...

Page 41: ...o display the version of software residing in the ePAQ type VER enter Example VER enter Display QEI ePAQ 9405 Link 80 013XXX XXX 3 22 16 Chksum 6320d4ca 15 15 TP Command This command invokes a software monitor which is useful in diagnosing different types of problems Example Type TP 15 enter Display Software Monitor running at level 15 The ePAQ will print error and informational messages if any on...

Page 42: ...propriate There are several forms of this command as follows 15 16 1 SOE Just entering SOE will cause all saved SOE events to be displayed on the test panel most recent first The listing can be terminated at any point by hitting any key 15 16 2 SOE point number This form of the command will only display SOE events from the specified status point number You must include the square brackets Therefor...

Page 43: ...ble 0 Len 34 Maxlen 34 1c 1 Owner System 10 Table 0 Len 12c Maxlen 12c 1d 3 Owner ConfigWiz 9 Table 9 Len 838 Maxlen 838 20 11 Total Table Len 4676 15 18 SEC Security Logger This command list certain events associated with security features of the ePAQ 9405 Such events may include log in attempts successful and unsuccessful test panel issued controls unit re starts ePAQ 9405_A SEC 10 10 07 2008 14...

Page 44: ...Displays Network Information such as MAC address IP and Gateway adressses ePAQ 9405_A ETH Mac Addr 0 bd 33 6 68 22 IP 192 168 0 95 NM 255 255 255 0 GW 192 168 0 1 Cfg 1 0 0 15 20 PROFILE Command Enables software profiler used mainly for QEIdebug Lists amount of processor usage per task ePAQ 9405_A PROFILE Profiling at 10000 msec Intervals Exec 20 Dnp QUICS 19 SOE Logger 03 COM 09 TPanel 05 Max 52 ...

Page 45: ...configuration file This ID string will appear at the test panel user prompt to let the user know which configuration file is active ePAQ 9405_A SAVE B 15 22 RESTORE A or B Command See section above This command will restore either of the two backup configuration that were saved using the SAVE command above NOTE A restart is required after restoring a configuration file 15 23 12BIT 16BIT Commands T...

Reviews: