QBD COOLING SYSTEMS INC.
QBD.COM
29
-
Always use QBD supplied OEM parts only. Use of non-OEM
parts will not only void the warranty but may also lead to a fire,
explosion, serious injury or death.
------------------------------------------------------------------------------------------
-
Only trained and certified technician, for Hydrocarbon
systems, should service these coolers.
------------------------------------------------------------------------------------------
-
Use extreme caution and follow all local/regional codes for
transportation or relocation of Hydrocarbon coolers.
Blowing Fuse
-
Power cord is cut and
grounding out
-
Defective compressor
-
Defective overload
-
High Voltage
-
Low Voltage
-
Replace power cord
-
Replace compressor
-
Replace overload
-
Correct voltage condition
-
Ensure cooler plugged into dedicated
supply with properly sized circuit.
(Correct voltage condition)
Suction line frosted
-
Evaporator fan not working
-
Overcharged system
-
Determine reason or replace if
required
-
Correct the charge
Leaking water
-
Very humid conditions
-
Blocked drain
-
Door not sealed properly /
top door seal
-
Clear blocked drains
-
Repair/replace door gaskets,
realign/seal doors
Evaporator freeze up
-
Temperature controller set
too cold
-
Blocked/restricted air flow
-
Defective evap motor/
running at low speed
-
Blocked drain
-
Low refrigerant charge
-
Open door or door not
sealed properly
-
Defective or open gasket on
cooling deck
-
Deck not in locked position.
-
Adjust to higher temperature setting
(lower number)
-
Remove source of blockage
-
Replace evap motor
-
Clear blocked drain
-
Repair/recharge system
-
Repair/seal air leaks. Replace
defective or damaged gasket
-
Lock deck in position and secure
with locking bar
Controller
miscommunication
-
Internal controller failure
-
Voltage spike
-
Replace controller & probe