Heat meter calculator QALCOMET HEAT 1
PEQMH1V01
22
Setting up parameter values:
- before setting up the parameters test mode should be deactivated (Test: off). Test mode is
described in paragraph 8.7.
- product number is individual and unchangeable,
- 1, 5, 6, 7, 10, 11, 12, 16E, 17, 18 parameter values have to be ordered individually for each
particular device, they are customized during manufacturing and unchangeable after installation.
Parameters marked with “*” should be programmed
as shown in Fig. 7.2:
Select the parameter to be modified, then press and
hold button
until parameter value starts blinking
–
alteration mode is entered. Parameter codes, meanings and
acceptable limits are listed in Appendix A.
Select required digit by pressing button
. Shortly
pressing button
, set the required value. Save changes by
holding button
pressed and return to display mode. All
parameters marked with “*” in Fig. 7.1 can be modified in
the same way.
Parameters marked with “**” should be
programmed as shown in Fig. 7.3:
Select the parameter to be modified, then enter
measurement channel selection mode by holding down
button
. Choose flow, temperature or pressure channels,
and select required measurement channel number by
shortly pressing button
, then activate or deactivate
selected measurement channel by shortly pressing button
. Parameter codes, meanings and acceptable limits are
listed in Appendix A.
Save changes by holding button
pressed and
return to previous display mode. All parameters marked
with “**” in Fig. 7.1 can be modified in the same way.
Sequence of displayed parameters may vary depending on selected measurement scheme and
number of sensors installed.
Note.
The displayed parameters listing order can vary or some parameters aren’t displayed
depending on regional user requirements.
Customer number
Entering customer ID:
-
- select symbol
position,
-
- change
value
Fig. 7.2.
Setting up parameters marked with “*”
(for example, Customer number )
Calendar
1-st pressure
measurement channel
- ON/OFF
2-nd pressure
measurement channel
- ON/OFF
Fig. 7.3.
Setting up parameters marked with “**”
(for example: pressure measurement
channel)
Summary of Contents for HEAT 1
Page 6: ...Heat meter calculator QALCOMET HEAT 1 PEQMH1V01 6...
Page 39: ...Heat meter calculator QALCOMET HEAT 1 PEQMH1V01 39...
Page 40: ...Heat meter calculator QALCOMET HEAT 1 PEQMH1V01 40...
Page 41: ...Heat meter calculator QALCOMET HEAT 1 PEQMH1V01 41...
Page 42: ...Heat meter calculator QALCOMET HEAT 1 PEQMH1V01 42...
Page 52: ...Heat meter calculator QALCOMET HEAT 1 PEQMH1V01 52...