INSTaLLaTIoN aND oPeraTIoN MaNUaL SoLar MoDULeS GeNeraTIoN 3 (G3) – HaNWHa Q CeLLS aUSTraLIa PTY LTD

INSTaLLaTIoN aND oPeraTIoN MaNUaL SoLar MoDULeS GeNeraTIoN 3 (G3) – HaNWHa Q CeLLS aUSTraLIa PTY LTD

2

3

DocumeNt ReVisioN 06
this installation manual is valid for Australia and New Zealand as of January 1st 2014 for Q.PRo-G3,  
Q.PRo BLK-G3, Q.PLus-G3, Q.PeAK-G3 solar modules, and replaces all earlier versions. 

technical parameters and the design are subject to change. the data sheets and customer information valid at the point in time 
when the relevant module was manufactured apply to the installation, mounting, and maintenance procedures for the respective solar 
modules. 

With solar modules from Hanwha Q CeLLS australia Pty Ltd 
(hereafter referred to as "Q CeLLS") you can directly transform 
the sun’s limitless energy into environmentally-friendly solar 
electricity.

In order to ensure the maximum performance of your Q CeLLS 
solar modules, please read the following instructions care-
fully and observe all guidelines. Non-compliance may result 
in damage and/or physical injury.

this installation manual provides instructions for the safe 
installation of crystalline solar modules.

 

Ä

Please read these instructions carefully before proceeding 
with your installation.

 

Ä

Please retain these instructions for the life of the solar 
modules.

 

Ä

Please ensure that this installation manual is available 
to the operator at all times.

 

Ä

this installation manual should be given to all subsequent 
owners or users of the solar modules.

 

Ä

All supplements received from the manufacturer should 
be included.

 

Ä

Please observe all other applicable documents.

Intended Use

this manual is valid for Australia and New Zealand. 
these instructions contain information regarding the safe 
handling and use of quality crystalline solar modules from 
Q ceLLs and for their installation, mounting, wiring, and 
maintenance. 

Symbols and Labels

the following symbols and labels are used throughout the 
installation manual for ease of use. 

SYMBoL

DeSCrIPTIoN

 

Ä

 

Procedure with one or more steps. 

• 

 

Lists of items

ensure that when carrying out a pro-
cedure, you check the results of said 
procedure.
  

Prohibited.
 

Beware of possible danger or damage. 
categories:

• 

Danger: Risk of fatal injury

• 

Attention: Risk of serious injury 
or damage to property

• 

Note: Risk of damage to product

Safety regulations

the solar module operator is responsible for compliance 
with all applicable statutory requirements and 
regulations. 

 

Ä

the following regulations and standards must be upheld 
at all times during the installation, operation, and 
maintenance of the solar modules: 

• 

installation and operation manual.

• 

Other applicable documents (such as country-specific 

regulations for pressure equipment, operational safety, 
hazardous goods, and environmental protection).

• 

Regulations and requirements specific to the system.

• 

Applicable  country-specific  laws,  regulations,  and 

provisions governing the planning, installation, and 
operation of solar power systems and work on roofs.

• 

Valid international, national, and regional regulations 
governing work with direct current, especially those 
applicable to the installation of electrical devices and 
systems, and regulations issued by the respective 
energy provider governing the parallel operation of 
solar power systems.

• 

Accident-prevention regulations.

Qualified & Skilled Personnel

Both the operator and installer are  responsible for 
ensuring that installation, maintenance, connection to 
the grid, and dismantling are carried out by trained and 

qualified  specialists  with  approved  training  certificates 

(issued by a state or federal organisation) for the 
respective specialist trade.

in Australia, electrical work may only be performed by a 
cec accredited licensed electrician complying with valid 
accident prevention regulations, and regulations of the 
local energy provider(s).

in New Zealand, electrical work may only be performed 
by a skilled electrician complying with valid accident 
prevention regulations, and regulations of the local 
energy provider(s).

TaBLe of CoNTeNTS

1  INTroDUCTIoN  

3

2 PLaNNING  

5

2.1  Technical specifications 

 

5

2.2 requirements 

 

7

2.3  Mounting options  

8

2.4  electrical layout  

10

3 INSTaLLaTIoN 

 

11

3.1  Safety and transport  

11

3.2  Preparation of installation  

13

3.3  Module installation  

14

4  eLeCTrICaL CoNNeCTIoN  

15

4.1 Safety 

 

15

4.2  electrical installation safety  

16

4.3  Connection of modules  

17

4.4  after installation  

18

5 GroUNDING 

 

19

6  faULTS aND DefeCTS  

19

7 DISPoSaL 

 

19 

8  MaINTeNaNCe aND CLeaNING  

20

1 INTroDUCTIoN

Summary of Contents for Q.Peak-G3

Page 1: ...Valid for Australia and New Zealand Q Pro G3 Q PRO BLK G3 Q Peak G3 Q PLUS G3 Installation and Operation Manual ...

Page 2: ...procedure Prohibited Beware of possible danger or damage Categories Danger Risk of fatal injury Attention Risk of serious injury or damage to property Note Risk of damage to product Safety Regulations The solar module operator is responsible for compliance with all applicable statutory requirements and regulations Ä Ä The following regulations and standards must be upheld at all times during the i...

Page 3: ... for the functionality and safety of the modules Ä Ä Please observe the instructions for any other sys tem components that may be part of the complete solar power system It may be necessary to carry out a structural analysis for the entire project Ä Ä If your questions are not satisfactorily answered in the manual please contact your system supplier Additional information can be found on our websi...

Page 4: ...ened to the ground the roof or the façade Forces acting on the module are relayed to the mounting substructure Ensures sufficient rear ventilation of the module Guarantees long term stability Has electrochemical series that prevent corrosion among different metals Allows for stress free expansion and contraction due to temperature fluctuations Ä Ä Ensure that no mechanical stresses e g caused by v...

Page 5: ...ounting options Specifications Module type Mounting option Clamping range1 Mm Allowed static load2 PA TEST LOAD acc IEC 61215 PA Q PRO G3 Q PRO BLK G3 Q PEAK G3 Q PLUS G3 CL1 Push 245 345 346 445 3500 2400 5400 Pull 245 345 346 445 5650 4000 CL3 Push 245 445 5700 Pull 245 345 346 445 4000 4000 CL4 Push 0 300 2000 Pull 0 300 2000 FB1 Push 3500 Pull 3100 FB2 Push 4000 Pull 3100 IP1 Push 3700 Pull 37...

Page 6: ...ground leaks or defective insulation Ä Ä Ensure that the maximum reverse current load capacity indicated in the data sheet is observed In order to limit reverse currents that may occur we recommend using the following safety options 1 Layout with a limited number of parallel connected strings Refer to AS NZS 5033 2012 including all relevant amendments for parallel string overcurrent protection req...

Page 7: ... packaging until installation Ä Ä Store the modules securely in cool and dry rooms The packaging is not weatherproof Danger Risk of fatal injury due to electric shock Ä Ä Do not install damaged modules Ä Ä Inform your dealer of any damages immediately 3 1 Safety and transport 3 Installation Note Module damage may occur Ä Ä Never lift or move the module with the connection cables or junction box Ä ...

Page 8: ... in windy or wet weather Danger Risk of fatal injury due to electric shock Ä Ä Only use dry insulated tools Ä Ä Do not carry out the installation alone Only install undamaged modules and components Ä Ä Do not drill any other holes 3 2 Preparation of installation 3 Installation Ä Ä Maintain an interval of at least 10 mm between two modules 10mm 1 0 m m Option 2 Ä Ä Install the module at the 4 mount...

Page 9: ...e wiring with extreme caution Ä Ä Ensure that the modules are disconnected at the inverter prior to separation Ä Ä Be sure to observe the specified time intervals after switching off the inverter High voltage components need time to discharge Danger Risk of fatal injury due to electric shock Ä Ä Never open the junction box Ä Ä Do not remove bypass diodes Danger Risk of fatal injury due to electric...

Page 10: ...c shock Ä Ä Ensure that all electrical components are in a proper dry and safe condition A module with 1 160 mm long cable can be wired as a 2nd next neighbor 2nd next neighbor Wiring without a return cable Standard wiring with a return cable Inverter Inverter 1 2 4 3 Connection of modules 4 ELECTRICAL CONNECTION Ä Ä Ensure that all necessary safety and functional tests have been carried out accor...

Page 11: ...e Maintenance Ä Ä The system should be inspected by an installer annually to check the following all system components sit securely and are corrosion free the connection is secure and all electrical components are clean and undamaged Cleaning WARNING Risk of injury due to hot and live modules Ä Ä Only clean modules that have cooled down Ä Ä Do not carry or wear any electrically conductive parts WA...