13
ENFORCER V11 INSTALLATION GUIDE
CONNECTING EXPANSION MODULES
Connecting a wired zone expander
Up to 4 wired zone expanders can be connected to the Enforcer.
- + D3 D4
---485 BUS
---
0V +12V
AU
X
ALARM TA
MPER
EOL INPUT 1 COM
ALARM TA
MPER
EOL INPUT 2 COM
ALARM TA
MPER
EOL INPUT 3 COM
ALARM TA
MPER
EOL INPUT 4 COM
ALARM TAMPER
EOL INPUT 5 COM
ALARM TAMPER
EOL INPUT 6 COM
ALARM TAMPER
EOL INPUT 7 COM
ALARM TAMPER
EOL INPUT 8 COM
POWER
OK
FA
U
LT
HOLD OFF
1
2
4
8
16
32
RESE
T
PGM STB BELL
Z33 COM +12V Z34
D1- D2+ D3
D4
Please note: The above shows the I/O board connected to a EURO-ZEM8, a EURO-ZEM8+ is connected in
the same way. If using a EURO-ZEM8+PSU, the D2+ MUST NOT be connected.
ZEM address 0
Zones 35-42
ZEM address 1
Zones 43-50
ZEM address 2
Zones 51-58
ZEM Address 3
Zones 59-66
Connecting a wireless zone expander
1 wireless zone expander can be connected to the Enforcer however, this expander can take the place of 4
addresses potentially expanding the system by 32 wireless peripherals.
IMPORTANT NOTE: The wireless ZEM must be addressed as ‘Device B’ via the jumper headers.
PGM STB BELL
Z33 COM +12V Z34
D1- D2+ D3
D4
- + D3 D4
T
T
The wireless ZEM allows a maximum 32 wireless zones to be learnt. These 32 zones are programmed as 4 different
ZEMs (addresses), and each having 8 wireless zones assigned.
Example
Wired and wireless zone expanders can be installed together on a system and, as long as they are addressed
uniquely, they will work alongside each other. For instance, if you wish to use 24 wireless zones and 8 wired zones,
you can program the wireless ZEM as ZEM addresses 00, 01 and 02 in the menu item ‘
i
nstAll
ZeM
’ and learn 24
zones to the system using the ‘
W
iReless
d
eviCe
C
ontRol
’
menu. Then address a wired ZEM as ZEM 03.
Summary of Contents for ENFORCER V11
Page 1: ...Document SAP 102028845 01 ENFORCER V11 INSTALLATION GUIDE...
Page 16: ......