background image

13

ENFORCER V11 INSTALLATION GUIDE

CONNECTING EXPANSION MODULES

Connecting a wired zone expander

Up to 4 wired zone expanders can be connected to the Enforcer. 

-             +           D3         D4

---485 BUS

---

0V       +12V

AU

X

ALARM                TA

MPER

EOL            INPUT 1          COM

ALARM                TA

MPER

EOL            INPUT 2          COM

ALARM                TA

MPER

EOL            INPUT 3          COM

ALARM                TA

MPER

EOL            INPUT 4          COM

ALARM                TAMPER

EOL            INPUT 5          COM

ALARM                TAMPER

EOL            INPUT 6          COM

ALARM                TAMPER

EOL            INPUT 7          COM

ALARM                TAMPER

EOL            INPUT 8          COM

POWER

OK

FA

U

LT

HOLD OFF

1

2

4

8

16

32

RESE

T

PGM STB BELL

Z33 COM +12V Z34

D1- D2+ D3

D4

Please note: The above shows the I/O board connected to a EURO-ZEM8, a EURO-ZEM8+ is connected in 

the same way. If using a EURO-ZEM8+PSU, the D2+ MUST NOT be connected.

ZEM address 0

Zones 35-42

ZEM address 1 

Zones 43-50 

ZEM address 2

Zones 51-58

ZEM Address 3

Zones 59-66

Connecting a wireless zone expander

1 wireless zone expander can be connected to the Enforcer however, this expander can take the place of 4 
addresses potentially expanding the system by 32 wireless peripherals.

IMPORTANT NOTE: The wireless ZEM must be addressed as ‘Device B’ via the jumper headers.

PGM STB BELL

Z33 COM +12V Z34

D1- D2+ D3

D4

-      +    D3   D4

T     

T

 

The wireless ZEM allows a maximum 32 wireless zones to be learnt. These 32 zones are programmed as 4 different 
ZEMs (addresses), and each having 8 wireless zones assigned. 

Example

Wired and wireless zone expanders can be installed together on a system and, as long as they are addressed 
uniquely, they will work alongside each other. For instance, if you wish to use 24 wireless zones and 8 wired zones, 
you can program the wireless ZEM as ZEM addresses 00, 01 and 02 in the menu item ‘

i

nstAll

 ZeM

’ and learn 24 

zones to the system using the ‘

W

iReless

 d

eviCe

 C

ontRol

 menu. Then address a wired ZEM as ZEM 03.

Summary of Contents for ENFORCER V11

Page 1: ...Document SAP 102028845 01 ENFORCER V11 INSTALLATION GUIDE...

Page 2: ...input This refers to a detector or sensor connected to the system whether this be wired or wireless Output PGM PG An output is a signal from the panel to instruct another device to operate This is usu...

Page 3: ...k plate 8 Front 8 Connecting the Control Panel Battery 9 Important Installation Notes 9 Input Output Board 10 Connecting Arming Devices 10 Connecting keypads 10 Connecting internal proximity readers 1...

Page 4: ...es 1 32 1x wireless expander zones 35 66 Wired zones max 34 2x zones on I O board zones 33 34 4x wired expanders zones 35 66 Total zones 66 Outputs max 38 3x outputs on I O board 1x output module 4 on...

Page 5: ...ge cut off value 8 5V Type NiMH 8 cell 2200mAh rechargeable battery CIE current when operating on battery backup 90mA ENVIRONMENT Physical dimensions W x H x D 220 x 160 x 50mm Weight 1025g Operating...

Page 6: ...OEM8R8T EURO OEM16R PSU Fuses 2x F500mA 250V SYSTEM ANALYSIS ADDITIONAL DEVICES Keypads Up to 3 Readers Up to 3 External sirens 2 Wireless arming stations 4 Please note Compliance labelling should be...

Page 7: ...the front on the opening screws at the bottom if required Shown above MAINS AND EARTH WIRING It is important that the electrical earth connection is connected when connecting the 230VAC mains supply t...

Page 8: ...ulated housing 5 The rear tamper adjustment screw This should be used if the tamper from the front of the Enforcer isn t sitting flush to the back plate E g if the Enforcer is installed on an uneven s...

Page 9: ...disconnect device such as an un switched fused spur or plug and socket with approved cover to prevent accidental disconnection from mains supply is incorporated in the premises installation wiring It...

Page 10: ...obe output for a wired external siren Z33 Wired zone 33 COM Common terminal for Z33 and Z34 and 12VDC auxiliary supply 12V 12VDC auxiliary supply Z34 Wired zone 34 CONNECTING ARMING DEVICES Connecting...

Page 11: ...l or entry control please refer to the peripheral instructions for connection details Connecting external proximity readers PGM STB BELL Z33 COM 12V Z34 D1 D2 D3 D4 If an additional external reader is...

Page 12: ...per return either zone 33 or 34 on the I O board Note the zone must be programmed as tamper The resistor value will correspond to the value selected in Wiring Choice IMPORTANT NOTE The external siren...

Page 13: ...3 Zones 59 66 Connecting a wireless zone expander 1 wireless zone expander can be connected to the Enforcer however this expander can take the place of 4 addresses potentially expanding the system by...

Page 14: ...35 42 ZEM address 01 43 50 ZEM address 02 51 58 ZEM address 03 59 66 Please note Wireless zones 35 66 can take upto 5 minutes to become active when armed Connecting an output expander 1 remote output...

Page 15: ...GE SAFETY EN 62368 1 2014 A11 2017 Audio video information and communication technology equipment Safety requirements RE DIRECTIVE ETSI EN 300 220 1 EMC Receiver Class 1 Environmental Category 1 CERT...

Page 16: ......

Reviews: