40
actuation.
module (BMS module).
9
Turn on the BMS. The one
and the following of the
battery module’s Status LED
lighting red or not lighting.
This battery module has
failure;
Its communication cable
failure;
Its Address Distribution
failure.
Change this battery
module;
Check the
communication cable;
Check by professional
stuff.
10
Single Cell is over voltage/
low voltage.
(Check through the monitor
or maintenance software.)
Cell voltage sampling
failure.
Cell failure;
Check the wires of cell
sampling module;
Change this battery
module.
11
Battery module shows the
temperature is -40
℃
.
(Check through the monitor
or maintenance software.)
The wires of temperature
sampling failure.
Check the wires of
temperature sampling
module. Or change this
battery module.
12
Another failure
Cell failure or electrical
board failure.
Can’t find out failure point
or can’t check. Please
contact with seller or sells
agent.
5.2 Replacement of main component
Danger:
The PowerCube-M2 is a high voltage DC system, operated by qualified and
authorized person only.
Danger:
Before replace the main component must shut off the maintenance battery
string’s power. Must confirm the
D+
and
D-
terminal are without power. The turn off
progress refer to chapter 3.6.5.
5.2.1 Replacement of Battery Module
A new battery module can be add onto an existing system at any time. Please make sure the new
battery module has an equivalent voltage level (OCV) compare to existing modules. In a serial
connection system, the new module, even has a higher SOH, will follow the system worst SOH
condition module to perform.