Page 13 / 15
PV500-67 03/17
4.2 TYPICAL PARAMETERS FOR ACCESS OVER MODBUS:
Setpoint: Modbus Register 40864
Set
Set point,
This is the typical system setpoint. Read/Write.
Modbus network ID or Address. Modbus Register 40852
Adr
Serial address 0÷247
This is the Modbus address. You should configure this with the keypad.
Temperature of Probe: Modbus Registers 40257
(TP1) Probe 1 temperature
Degrees F (40257)
This is the operating probe that Set references. Read only.
Output Relays (Burner ON): Modbus Coil 543
Statas of Relay, if it is ON the signal for burner is also ON.
Alarms: Modbus Coil 538
Alarms are not typically used on this device.
CONTROL, ON/OFF (Enable/Disable) Modbus Coil 513
ON=257 or 0x0101, OFF=1 or 0x0001
In the OFF state, no heating signal will be present, no alarms, all relay outputs are open, and no temperature are
displayed. The di
splay will show the word “OFF”. It is still possible to read the probe temperatures and other parameters
over Modbus.
This is a write only register. Reading this register will provide invalid results.
5. SERIAL CONFIGURATION
5.1 PORT SETUP
Baud Rate:
9600bps (Not adjustable)
Data Length:
8 bit (Not adjustable)
Parity:
None (Not adjustable)
Stop Bits:
1 (Not adjustable)
Start/Stop:
Silent interval of 3 characters minimum
Minimum Time Between Retry:
500 msec