TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Page 27 of 30
PV7069-T 01/05/16
Part number 129209
rr1
0.3 & 0.5
Maximum shift of St1
-100÷100°F
Pr2
Pr2
0x321
802
tt2
0.3 & 0.5
Outdoor temperature threshold to open all the loads
-40÷230°F
Pr2
Pr2
0x322
803
Ht2
0.3 & 0.5
Differential for restart working of controller
-45 ÷ -1 °F
Pr2
Pr2
0x323
804
DIGITAL INPUTS
i1P
0.3 & 0.5
Digital input 1 polarity
CL÷OP
Pr3
Pr2
0x324
805
i2P
0.3 & 0.5
Digital input 2 polarity
CL÷OP
Pr2
Pr2
0x325
806
i2d
0.3 & 0.5
Digital input 2 alarm delay
0÷255 min.
Pr3
Pr2
0x326
807
i3P
0.3 & 0.5
Digital input 3 polarity
CL÷OP
Pr2
Pr2
0x327
808
i3d
0.3 & 0.5
Digital input 3 alarm delay
0÷255 min.
Pr3
Pr2
0x328
809
DISPLAY
cF
0.3 & 0.5
Temperature measurement unit
°C ÷ °F
Pr3
Pr2
0x329
810
rES
0.3 & 0.5
Resolution (integer/decimal point) only for °C
in ÷ de
Pr3
Pr2
0x32A
811
dS2
0.3
Default showing for display #2 Top (red)
Pb2, Pb3
Pr2
0x32B
812
dS2
0.5
Default showing for display #2 Top (red) Pb3 will
display yellow EXT, Ani will display yellow Valve/M
Pb1,Pb2,Pb3,AnI
Pr2
0x32B
812
dS1
0.3
Default showing for display #1 Bottom (Yellow)
Pb1; tiM
Pr2
0x32C
813
dS1
0.5
Default showing for display #1 Bottom (Yellow) Pb3
will display yellow EXT, Ani will display yellow Valve/M
Pb1,Pb2,Pb3,AnI, TiM
Pr2
0x32C
813
ALARMS
Alc
0.3 & 0.5
Temperature alarms configuration: dependent on St1
or independent
rE÷Ab
Pr3
Pr2
0x32D
814
ALL
0.3
minimum temperature alarm for Pb1 (Alarm LA flash
only)
-40÷230°F
Pr2
Pr2
0x32E
815
ALL
0.5
minimum temperature alarm for Pb1 (Alarm LA flash
and signal on 3329)
-40÷230°F
Pr2
Pr2
0x32E
815
Alu
0.3
MAXIMUM temperature alarm for Pb1 (Alarm HA
flash only)
-40÷230°F
Pr3
Pr2
0x32F
816
Alu
0.5
MAXIMUM temperature alarm for Pb1 (Alarm HA
flash and signal on 3329)
-40÷230°F
Pr3
Pr2
0x32F
816
AFH
0.3 & 0.5
Differential for temperature alarm recovery
1÷45°F
Pr2
Pr2
0x330
817
ALd
0.3 & 0.5
Temperature alarm delay
0÷255 min.
Pr2
Pr2
0x331
818
dAo
0.3 & 0.5
Delay of temperature alarm at start up 1 = 10 min
disp 0.1
0 ÷ 23h 50 min.
Pr2
Pr2
0x332
819
ANALOGUE INPUTS
oF1
0.3 & 0.5
First probe calibration
-21÷21°F
Pr3
Pr2
0x333
820
P2P
0.3 & 0.5
Second probe presence
No; Yes
Pr2
Pr2
0x334
821
oF2
0.3 & 0.5
Second probe calibration
-21÷21°F
Pr3
Pr2
0x335
822
P3P
0.3 & 0.5
Third probe presence
No; Yes
Pr2
Pr2
0x336
823
oF3
0.3 & 0.5
Third probe calibration
-21÷21°F
Pr3
Pr2
0x337
824
TIME AND DATE