TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 22 of 30
PV7069-T 03/17
Part number 129209
ALL POINTS INCLUDING ADVANCE:
Relay2
Read Only
Status of Relay2 (Output 3)
MODBUS
Holding Register
2049
42050:1
BACNET
Relay2
205051
LONWORKS
nvoRelay2_#
This is Bit 1 of the Relay status word. It is the output #2 relay. BACNET and LONWORKS have this broke out
into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0002,
if result = 0, relay is off. If result = 2, relay is on.
Relay3
Read Only
Status of Relay3 (Output 3)
MODBUS
Holding Register
2049
42050:2
BACNET
Relay3
205052
LONWORKS
nvoRelay3_#
This is Bit 2 of the Relay status word. It is the output #3 relay. BACNET and LONWORKS have this broke out
into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0004,
if result = 0, relay is off. If result = 4, relay is on.
ALARM STATUS ALL
Read Only
ALL ALARMS STATUS
MODBUS
Holding Register
3328
43329
BACNET
DIA
332900
LONWORKS
nvoDIA_#
Alarm word, each bit represent separate alarms.
Alarm_LA
Read Only
Status of low temperature Alarm
MODBUS
Holding Register
3328
43329:0
BACNET
Alarm_LA
332950
LONWORKS
nvoAlarm_LA_#
Low water temperature alarm. Probe 1 is lower than temperature in ALL point. This is Bit 0 of the ALARM
STATUS ALL word. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0001 = 0x0001 Alarm is active. = 0x0000 Alarm is not active.
Alarm_HA
Read Only
Status of high temperature Alarm
MODBUS
Holding Register
3328
43329:1
BACNET
Alarm_HA
332951
LONWORKS
nvoAlarm_HA_#
High water temperature alarm. Probe 1 is higher than temperature in ALU point. This is Bit 1 of the ALARM
STATUS ALL word. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0002 = 0x0002 Alarm is active. = 0x0000 Alarm is not active.
Alarm_P1
Read Only
Status of Probe 1 Alarm
MODBUS
Holding Register
3328
43329:2
BACNET
Alarm_P1
332952
LONWORKS
nvoAlarm_P1_#
Probe 1 alarm. This can be a disconnected, open or shorted probe. This will shut down heating operation. This
is Bit 2 of the ALARM STATUS ALL word. Flashes ‘P1’ on TempTrac display. In BACNET and LONWORKS,
this is broken out into a state logic point.
For MODBUS ALARMS && 0x0004 = 0x0004 Alarm is active. = 0x0000 Alarm is not active.