TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 17 of 30
PV7069-T 03/17
Part number 129209
TYPICAL POINTS:
Probe 2
Read Only
Probe 2 in degrees F
MODBUS
Holding Register
258
40259
BACNET
Probe2
25900
Deg-F
LONWORKS
nvoProbe2_#
Deg_F
Optional probe on some devices, usually installed on most devices. If installed and enabled, returns the
temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 15 and common 17.
Probe 3
Read Only
Probe 3 in degrees F
MODBUS
Holding Register
260
40261
BACNET
Probe3
26100
Deg-F
LONWORKS
nvoProbe3_#
Deg_F
Optional probe on some devices, not usually installed on most devices. If installed and enabled, returns the
temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 16 and common 17.
Burner Runtime
Read/Write
Burner Runtime Hours 0-65535
MODBUS
Holding Register
848
40849
BACNET
BURNER_HOURS_ou1
84900
Hours
LONWORKS
nvoBrnHr_ou1_ #
nviBrnHr_ou1_#
Hours
NOTE: Number of hours the burner has been enabled. Once it reaches 9999. This can be written to, as a way
to reset it.
Modulation Rate
Read Only
Monitor the modulation signal
MODBUS
Holding Register
262
40263
BACNET
Modulation_FR
26300
LONWORKS
nvoMod_FR_#
Modulation rate on the analog output 4-20ma is represented as 0-100. This feature was introduced in Firmware
0.5 (5) and is not available from older TempTrac modules already in the field.
Burner_Relay1
Read Only
Status of burner, Relay1 (Output 1)
MODBUS
Holding Register
2049
42050:0
BACNET
Burner_Relay1
205050
LONWORKS
nvoBrn_Rel1_#
This is Bit 0 of the Relay status word. It is the relay that controls the main heating output. Typically the Burner
Status. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break
it out yourself. Read value, BITWISE AND with 0x0001, if result = 0, relay is off. If result = 1, relay is on.
Alarm_AL2
Read Only
Status of digital input #2 Alarm
MODBUS
Holding Register
3328
43329:11
BACNET
Alarm_AL2
332961
LONWORKS
nvoAlarm_AL2_#
Digital Input #2 alarm. On some products, this is a general failure to operate alarm. See product specific
information. This is Bit 11 of the ALARM STATUS ALL word.
Flashes ‘AL2’ or ‘LP’ on TempTrac display. In
BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0800 = 0x0800 Alarm is active. = 0x0000 Alarm is not active.