TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 19 of 30
PV7069-T 03/17
Part number 129209
ALL POINTS INCLUDING ADVANCE:
Hy1
Read
Setpoint Differential
MODBUS
Holding Register
772
40773
BACNET
Hy1
77300
delta-degrees-Fahrenheit
LONWORKS
nvoHy1_#
Differential. (if Hy1 is negative) The heater will begin heating when Probe #1 must fall this far below St1
setpoint, and stay on until the heater reaches St1 setpoint.
(If Hy1 is positive) The heater will come on when Probe #1 falls to or below St1 setpoint, and will not turn off
until it has reached this far above St1 Setpoint. BACNET and LONWORKS, this point is configured as a read
only, with MODBUS, there is no protection from changing this value.
St4
Read Only
Modulation Start
MODBUS
Holding Register
792
40793
BACNET
St4
79300
No Units
LONWORKS
nvoSt4_#
Starting point of modulation. Related to the St1 setpoint. If Probe 1 is above St1 + St4, then Modulation signal
will be low fire. If Probe 1 falls below (St1 + St4) then the analog output signal will modulate based on the setting
in the SR register. This is set to No Units in BACNET because it can relative to St1 or is can be independent
value. Typically it is configured as relative to St1. BACNET and LONWORKS, this point is configured as a read
only, with MODBUS, there is no protection from changing this value.
SR
Read
Modulation bandwidth
MODBUS
Holding Register
793
40794
BACNET
SR
79400
delta-degrees-Fahrenheit
LONWORKS
nvoSR_#
Normally this is a negative number. Number of degrees of change in Probe 1 that will modulate from 0 to 100%.
St1 + St4 = low fire, St1 + St4 + SR = High Fire. Temperatures above low fire will be low fire, temperatures
below high fire will be high fire. In-between, the output will modulate from 4-20mA (0-100%) BACNET and
LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this
value.
Probe 1
Read Only
Controlling Probe Degrees F
MODBUS
Holding Register
256
40257
BACNET
Probe1
25700
Deg-F
LONWORKS
nvoProbe1_#
Deg_F
Probe that provides control of heating. Location can vary depending on equipment and application. See section
that discussed the various equipment to determine actual location of probe. Connection on TempTrac is green
screw terminals 14 and common 17.
Probe 2
Read Only
Probe 2 in degrees F
MODBUS
Holding Register
258
40259
BACNET
Probe2
25900
Deg-F
LONWORKS
nvoProbe2_#
Deg_F
Optional probe on some devices, usually installed on most devices. If installed and enabled, returns the
temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 15 and common 17.
Probe 3
Read Only
Probe 3 in degrees F
MODBUS
Holding Register
260
40261
BACNET
Probe3
26100
Deg-F
LONWORKS
nvoProbe3_#
Deg_F
Optional probe on some devices, not usually installed on most devices. If installed and enabled, returns the
temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 16 and common 17.