5. ZPGLP-SERIES W/O CIRCULATOR (PIPE N’ GO)

PIPING INSTALLATION

DOMESTIC WATER PIPING

1.

Connect the cold water supply to the pipe labeled COLD
WATER

2.

Connect the HOT WATER piping to the domestic hot water
system.

3.

Make an 8-inch “heat trap” on the HOT WATER outlet as
shown in the diagram. This will reduce standby losses from
heat migrating up the piping.

4.

When all domestic water piping is complete, open the cold
water supply and allow some water to enter the tank.  Look and
listen for signs of leaks and repair as necessary before
continuing.

Note:

If installing on a city supply, ensure a dedicated Thermal

Expansion tank is used.

5.

Install a blowdown tube on the T&P relief valve outlet.  Plumb

to within 6 inches above a floor drain or as directed by
plumbing code.

BOILER PIPING

1.

Plumb the circulator or zone valve on the BOILER SUPPLY line.
If using a separate circulator, the pump flange can be mounted
directly to the threaded pipe marked BOILER SUPPLY.
Alternately, the circulator can be placed anywhere on the boiler
supply line.

2.

Pipe the BOILER RETURN connection to the boiler return line.  

Be sure the return line is NOT
plumbed to the suction side of any

heating circulators.  This may require moving the heating
circulator off the boiler tapping on packaged boilers.
Failure to do so will result in overheating and tank
damage when the heating system is in operation.

3.

Install a weighted flow check on the boiler return line.  This is

not necessary on systems utilizing a zone valve to control the
water heater temperature.

4.

After completing the boiler piping, slowly open the boiler fill
valve and pressurize the water heater loop.  Check for leaks
and repair as necessary. Proceed to the appropriate wiring
section in this manual.

Aquastat

LEFT SIDE  . . . . . . . . . . . . .1”
RIGHT SIDE  . . . . . . . . . . .1”
TOP  . . . . . . . . . . . . . . . . . .9”

REAR . . . . . . . . . . . . . . . . .1”
FLOOR  . . . . . . . . . . . . . . .0”
FRONT  . . . . . . . . . . . . . . .1”

Clearance From Combustible Surfaces

LEFT

12”

RIGHT

12”

FRONT

30”

HEAD ROOM

9”

REAR

1”

Recommended Clearance for Servicing

-6-

Cold Water

Inlet

T&P Relief

Valve Outlet

Hot Water

Outlet

Boiler Supply

Boiler Return

Summary of Contents for PIPE N' GOTD-41ZPGLP

Page 1: ...F THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE AS APPLICABLE THIS IS THE SAFETY ALERT SYMBOL IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS OBEY ALL SAFETY MESSAGES TH...

Page 2: ...heater will be supplied just as another zone This means that if all space heating zones call for hot boiler water at the same time the water heater may not be supplied with enough hot boiler water to...

Page 3: ...e the existing diaphragm expansion tank 3 REQUIRED COMPONENTS AND ACCESSORIES CHECKLIST SHUTOFF VACUUM RELIEF THERMAL EXPANSION MODEL CIRCULATOR ZONE VALVE VALVE BREAKER VALVE TANK DRAIN PRO 41ZPG Inc...

Page 4: ...bing code BOILER PIPING 1 Plumb the BOILER SUPPLY line The circulator and flow check are factory installed 2 Pipe the BOILER RETURN connection to the boiler return line Be sure the return line is NOT...

Page 5: ...Thermal Expansion Tank PIPING MODELS WITH PRE INSTALLED CIRCULATOR W INTEGRAL FLOW CHECK 5...

Page 6: ...ed directly to the threaded pipe marked BOILER SUPPLY Alternately the circulator can be placed anywhere on the boiler supply line 2 Pipe the BOILER RETURN connection to the boiler return line Be sure...

Page 7: ...Thermal Expansion Tank PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED Thermal Expansion Tank PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR 7...

Page 8: ...he unit Ensure that the proper conduit and connections are used per your local code In lieu of local code the National Electric Code should be followed DHW AQUASTAT FACTORY WIRED LINE OUT CANCELS ON C...

Page 9: ...LIVE NEUT PR OUT PR IN 1 2 3 4 L1 L2 Indirect Aquastat L1 L2 B2 B HONEYWELL L8148J W MILLIVOLT GAS VALVE WHITE RODGERS 8J48A W 24V GAS VALVE CIRCULATOR RELAY BOX Indirect Aquastat L2 LIVE NEUT PR OUT...

Page 10: ...al Control models select the appropriate diagram from the following pages Always disconnect power before wiring the control Ensure that the proper conduit and connectors are used per your local code I...

Page 11: ...X Boiler Aquastat Zone Outputs Priority or DHW Zone Thermostat Inputs Typical Multi Zone Relay Circulator Aquastat AQUASTAT AQUASTAT ZONE VALVES SCHEMATIC 3 PRIORITY W CIRCULATORS SCHEMATIC 4 3 WIRE...

Page 12: ...12 AQUASTAT BOILER CONTROL SCHEMATIC 5 HONEYWELL L8148E...

Page 13: ...considered normal and will clear as hot water is used 3 START HEATER Turn power on to the unit The knob should be rotated to the 120 F mark The circulator and boiler should start momentarily If not ch...

Page 14: ...plumbing 2 Reduce temperature setting 3 Re insert temperature sensor 4 Repair or replace 5 Clean repair or replace Noise from water heater 1 Air in boiler loop 2 Faulty circulator pump 3 Thermal expa...

Page 15: ...eries Heat Exchanger w Gasket and Nuts Pump not included 41 Gallon 2700 5007 41 Gallon 2700 5007 80 Gallon 2700 5009 80 Gallon 2700 500 Flange Gasket Only 2704 403 2704 403 Aquastat Well Assembly 2700...

Page 16: ...ter heater must be electrically grounded Electrical supply must come from the boiler side of boiler s emergency shut off switch in order to prevent unsafe boiler operation Chlorine Aggressive Water Th...

Page 17: ...ns ALL IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE SPECIFICALLY DISCLAIMED Limitations of Remedies THE REMEDIES CONTAINED IN THIS WA...

Page 18: ...18 Notes...

Page 19: ...19 Notes...

Page 20: ...20 Part 9040 658 9 06...

Reviews: