PurePro PIPE N' GOTD-41ZPGLP Installation & Operation Manual Download Page 14

-14-

PROBLEM

POSSIBLE CAUSES

SOLUTION

No hot water

1. No power to unit

2. Air in heat exchanger loop

3. Faulty circulator or zone valve

4. Faulty BoilerMate thermostat

5. Faulty Smart Control

6. Boiler inoperable

1. Check circuit breaker, boiler emergency switch

and boiler reset switch

2. Purge air.  Ensure circulator is on Boiler Supply.

Check air vents

3. Check circulator and zone valve. Repair or

replace if necessary

4. Check continuity while rotating knob.  Circuit

should open and close.

5. If blank, check power. Check continuity across

two orange and two blue leads while green light
is on. If none, open control and replace fuses or
replace control.

6. Check boiler system. Boiler must operate to

generate hot water

Insufficient hot water

1. Demand exceeds capacity

2. Temperature too low
3. Boiler lacks sufficient output

4. Fouled heat exchanger

5. Insufficient heat exchanger flow

1. Check sizing based on household size and boiler

output

2. Increase temperature setpoint
3. Wire for priority.  If problem persists add storage

or increase tank size.

4. Check Boiler Supply/Boiler Return during cold

startup.  If difference is less than 20F, clean heat
exchanger as outlined below. Install water
treatment equipment to prevent recurrence.

5. Check for undersized or faulty circulator, stuck or

undersized zone valve. Ensure all shutoff valves
are open.  Check for stuck flow check valve.
Purge boiler loop to remove air.

Water too hot

1. Improper plumbing

2. Temperature set too high
3. Temperature sensor not fully inserted
4. Stuck zone valve
5. Flow check valve stuck open

1. If Boiler Return is plumbed to the suction-side of

a heating circulator, overheating will occur when
the home's heat is on.  Fix plumbing.

2. Reduce temperature setting
3. Re-insert temperature sensor
4. Repair or replace
5. Clean, repair or replace

Noise from water heater

1. Air in boiler loop

2. Faulty circulator pump
3. Thermal expansion

4. Normal noise during initial fill

1. Purge boiler loop. Check air elimination

equipment.

2. Repair or replace pump
3. Ensure the proper thermal expansion tank is

installed and adjusted properly

4. When first pressurized, a creaking or hissing

sound is normal. After pressurizing, the noise
should stop.  Always check for leaks.

Relief valve dripping or opening

1. No thermal expansion tank
2. Thermal expansion tank set improperly

3. City pressure too high

4. System over temperature

5. Faulty relief valve

1. Install the proper thermal expansion tank
2. Ensure precharge air pressure matches static

water pressure

3. Install a Pressure Reducing Valve (PRV) if city

pressure is over 80psi

4. Determine cause of over temperature condition

and correct problem

5. Replace relief valve

Discolored water at faucet

1. Poor water quality

2. Sediment or suspended particles

1. Have water tested for contaminants.  Typical

problems are:
Blue/green color = copper discoloration due to
low pH
Black staining/sulfur odor = hydrogen sulfide
White deposits = hard water
Red staining = high iron levels

2. Install sediment filter, purge unit more often to

avoid future problems

Boiler will not operate when
calling for hot water

1. Improper or loose wiring

2. Boiler high limit has been reached

3. Problem with boiler system

1. Check connections against wiring diagrams in

this manual

2. Boiler will periodically cycle on and off during

operation

3. Have boiler diagnosed for proper operation

Circulator or zone valve will not
operate when calling for hot
water

1. Improper or loose wiring

2. Faulty circulator pump

1. Check connections against wiring diagrams in

this manual

2. Repair or replace pump

9. TROUBLESHOOTING

Summary of Contents for PIPE N' GOTD-41ZPGLP

Page 1: ...F THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE AS APPLICABLE THIS IS THE SAFETY ALERT SYMBOL IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS OBEY ALL SAFETY MESSAGES TH...

Page 2: ...heater will be supplied just as another zone This means that if all space heating zones call for hot boiler water at the same time the water heater may not be supplied with enough hot boiler water to...

Page 3: ...e the existing diaphragm expansion tank 3 REQUIRED COMPONENTS AND ACCESSORIES CHECKLIST SHUTOFF VACUUM RELIEF THERMAL EXPANSION MODEL CIRCULATOR ZONE VALVE VALVE BREAKER VALVE TANK DRAIN PRO 41ZPG Inc...

Page 4: ...bing code BOILER PIPING 1 Plumb the BOILER SUPPLY line The circulator and flow check are factory installed 2 Pipe the BOILER RETURN connection to the boiler return line Be sure the return line is NOT...

Page 5: ...Thermal Expansion Tank PIPING MODELS WITH PRE INSTALLED CIRCULATOR W INTEGRAL FLOW CHECK 5...

Page 6: ...ed directly to the threaded pipe marked BOILER SUPPLY Alternately the circulator can be placed anywhere on the boiler supply line 2 Pipe the BOILER RETURN connection to the boiler return line Be sure...

Page 7: ...Thermal Expansion Tank PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED Thermal Expansion Tank PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR 7...

Page 8: ...he unit Ensure that the proper conduit and connections are used per your local code In lieu of local code the National Electric Code should be followed DHW AQUASTAT FACTORY WIRED LINE OUT CANCELS ON C...

Page 9: ...LIVE NEUT PR OUT PR IN 1 2 3 4 L1 L2 Indirect Aquastat L1 L2 B2 B HONEYWELL L8148J W MILLIVOLT GAS VALVE WHITE RODGERS 8J48A W 24V GAS VALVE CIRCULATOR RELAY BOX Indirect Aquastat L2 LIVE NEUT PR OUT...

Page 10: ...al Control models select the appropriate diagram from the following pages Always disconnect power before wiring the control Ensure that the proper conduit and connectors are used per your local code I...

Page 11: ...X Boiler Aquastat Zone Outputs Priority or DHW Zone Thermostat Inputs Typical Multi Zone Relay Circulator Aquastat AQUASTAT AQUASTAT ZONE VALVES SCHEMATIC 3 PRIORITY W CIRCULATORS SCHEMATIC 4 3 WIRE...

Page 12: ...12 AQUASTAT BOILER CONTROL SCHEMATIC 5 HONEYWELL L8148E...

Page 13: ...considered normal and will clear as hot water is used 3 START HEATER Turn power on to the unit The knob should be rotated to the 120 F mark The circulator and boiler should start momentarily If not ch...

Page 14: ...plumbing 2 Reduce temperature setting 3 Re insert temperature sensor 4 Repair or replace 5 Clean repair or replace Noise from water heater 1 Air in boiler loop 2 Faulty circulator pump 3 Thermal expa...

Page 15: ...eries Heat Exchanger w Gasket and Nuts Pump not included 41 Gallon 2700 5007 41 Gallon 2700 5007 80 Gallon 2700 5009 80 Gallon 2700 500 Flange Gasket Only 2704 403 2704 403 Aquastat Well Assembly 2700...

Page 16: ...ter heater must be electrically grounded Electrical supply must come from the boiler side of boiler s emergency shut off switch in order to prevent unsafe boiler operation Chlorine Aggressive Water Th...

Page 17: ...ns ALL IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE SPECIFICALLY DISCLAIMED Limitations of Remedies THE REMEDIES CONTAINED IN THIS WA...

Page 18: ...18 Notes...

Page 19: ...19 Notes...

Page 20: ...20 Part 9040 658 9 06...

Reviews: