2. PRE-INSTALLATION CHECKLIST

IMPORTANT STEPS AND DECISIONS REQUIRED BEFORE INSTALLATION

-2-

1. TABLE OF CONTENTS

M

THIS PRODUCT MUST BE INSTALLED AND MAINTAINED
BY A LICENSED PROFESSIONAL. IN ADDITION TO THE
INSTRUCTIONS IN THIS MANUAL, FOLLOW ALL
APPLICABLE LOCAL AND STATE CODES OR IN THE
ABSENCE OF SUCH CODES, THE CURRENT EDITIONS OF
THE NATIONAL PLUMBING CODE AND THE NATIONAL
ELECTRIC CODE.

M

DRIP PAN AND DRAIN: This appliance should not be
installed in an area where leakage of the tank or
connections can result in damage to the area adjacent to
the appliance or to lower floors of the structure. When
such locations cannot be avoided, a suitable drain pan,
adequately drained and kept clear, must be installed under
the appliance.

M

CAUTION: Determine whether your water is corrosive or
acidic, and that there are no suspended solids, toxic or
other substances or abnormally high chlorine levels in the
water that could damage or affect the water heater or the
rest of your plumbing system.

USE GLYCOL ONLY WITH DOUBLE-
WALLED HEAT EXCHANGER

MODELS. Glycol is a poisonous substance. To avoid
seepage or leakage of glycol to surfaces where humans or
animals can ingest it, use glycol only in double-walled
units, so that any leaks will most likely be released to the
atmosphere.  However, a leak to a surface area may still
occur, so any use of glycol must be monitored closely and
humans and animals should be protected from contact
with the unit.

Do not connect the water heater
domestic supply with baseboard or

other space heating units or elements. Any contaminants
in the baseboard units will contaminate the potable water
in the water heater and also adversely affect its
performance.

M

Wiring Options. Select either a Non-Priority or Priority
System:

Two options are available when wiring the controls of the water
heater in the space heating system (boiler and distribution
elements).

1. Non-Priority System -

The controls of the water heater

must be wired as a separate heating zone with a
standard zone valve or a separate circulator dedicated to
the water heater "zone".

NOTICE: 

In this non-priority option, the water heater will be

supplied just as another zone. This means that if all space
heating zones call for hot boiler water at the same time, the

water heater may not be supplied with enough hot boiler water
to "recover" adequately. The delivery of domestic hot water will
be diminished. In many, but not all  cases, this is not a problem
because the routine oversizing of boiler output is adequate for
both loads.

2. Priority System

- Under this wiring option the water

heater will be supplied before space heating.

In limited circumstances, space
heating can be lost in the home in this

priority mode. Any demand for space heating is postponed
until the water heater has reached its set temperature.
This delay in supplying the space heating zones is usually
not noticed by the inhabitants of the living spaces.
However, in the event of certain malfunctions such as
circulator or thermostat failure, space heating could be
delayed indefinitely. If undetected and uncorrected,
freezing damage to piping could result.

Select Circulator versus Zone Valve

The flow of hot boiler water to the water heater can be
controlled with either a motorized zone valve or a circulator.

1.

Separate circulator.

The recommended way to provide

adequate flow through the water heater heat exchanger is
to use a separate dedicated circulator with a minimum
flow rate of 5 gpm.  This option may be used even though
the heating system utilizes zone valves.

2.

Zone valve

(system flow of 4-8 gpm).  If a zone valve is to

be used, a minimum flow rate of 5 gpm with all zones in
use is required. A full-port zone valve should be used.

All installations require a low-water cut-off or automatic fill valve

on your boiler system to reduce the risk of boiler water loss. 

Steam boiler installations require a low-water cut-off which is
also required by most codes.

Installation of a vacuum breaker is required to prevent damage

to the water heater when drained. There must be no valves
installed between the vacuum breaker and water heater.

2. Pre-Installation Checklist...............................................

2

3. Required Components and Accessories Checklist.......

3

4.  ZPG - Series Piping Installation ....................................

4

5. ZPGLP -Series Piping Installation .................................

6

6. ZPG - Series Wiring.......................................................

8

7.  ZPGLP - Series Wiring ................................................

10

8. Startup Procedure .......................................................

13

9. Troubleshooting ...........................................................

14

10. Replacement Parts ......................................................

15

11. General Safety Information..........................................

16

12. Product Warranty.........................................................

17

Summary of Contents for PIPE N' GOTD-41ZPGLP

Page 1: ...F THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE AS APPLICABLE THIS IS THE SAFETY ALERT SYMBOL IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS OBEY ALL SAFETY MESSAGES TH...

Page 2: ...heater will be supplied just as another zone This means that if all space heating zones call for hot boiler water at the same time the water heater may not be supplied with enough hot boiler water to...

Page 3: ...e the existing diaphragm expansion tank 3 REQUIRED COMPONENTS AND ACCESSORIES CHECKLIST SHUTOFF VACUUM RELIEF THERMAL EXPANSION MODEL CIRCULATOR ZONE VALVE VALVE BREAKER VALVE TANK DRAIN PRO 41ZPG Inc...

Page 4: ...bing code BOILER PIPING 1 Plumb the BOILER SUPPLY line The circulator and flow check are factory installed 2 Pipe the BOILER RETURN connection to the boiler return line Be sure the return line is NOT...

Page 5: ...Thermal Expansion Tank PIPING MODELS WITH PRE INSTALLED CIRCULATOR W INTEGRAL FLOW CHECK 5...

Page 6: ...ed directly to the threaded pipe marked BOILER SUPPLY Alternately the circulator can be placed anywhere on the boiler supply line 2 Pipe the BOILER RETURN connection to the boiler return line Be sure...

Page 7: ...Thermal Expansion Tank PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED Thermal Expansion Tank PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR 7...

Page 8: ...he unit Ensure that the proper conduit and connections are used per your local code In lieu of local code the National Electric Code should be followed DHW AQUASTAT FACTORY WIRED LINE OUT CANCELS ON C...

Page 9: ...LIVE NEUT PR OUT PR IN 1 2 3 4 L1 L2 Indirect Aquastat L1 L2 B2 B HONEYWELL L8148J W MILLIVOLT GAS VALVE WHITE RODGERS 8J48A W 24V GAS VALVE CIRCULATOR RELAY BOX Indirect Aquastat L2 LIVE NEUT PR OUT...

Page 10: ...al Control models select the appropriate diagram from the following pages Always disconnect power before wiring the control Ensure that the proper conduit and connectors are used per your local code I...

Page 11: ...X Boiler Aquastat Zone Outputs Priority or DHW Zone Thermostat Inputs Typical Multi Zone Relay Circulator Aquastat AQUASTAT AQUASTAT ZONE VALVES SCHEMATIC 3 PRIORITY W CIRCULATORS SCHEMATIC 4 3 WIRE...

Page 12: ...12 AQUASTAT BOILER CONTROL SCHEMATIC 5 HONEYWELL L8148E...

Page 13: ...considered normal and will clear as hot water is used 3 START HEATER Turn power on to the unit The knob should be rotated to the 120 F mark The circulator and boiler should start momentarily If not ch...

Page 14: ...plumbing 2 Reduce temperature setting 3 Re insert temperature sensor 4 Repair or replace 5 Clean repair or replace Noise from water heater 1 Air in boiler loop 2 Faulty circulator pump 3 Thermal expa...

Page 15: ...eries Heat Exchanger w Gasket and Nuts Pump not included 41 Gallon 2700 5007 41 Gallon 2700 5007 80 Gallon 2700 5009 80 Gallon 2700 500 Flange Gasket Only 2704 403 2704 403 Aquastat Well Assembly 2700...

Page 16: ...ter heater must be electrically grounded Electrical supply must come from the boiler side of boiler s emergency shut off switch in order to prevent unsafe boiler operation Chlorine Aggressive Water Th...

Page 17: ...ns ALL IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE SPECIFICALLY DISCLAIMED Limitations of Remedies THE REMEDIES CONTAINED IN THIS WA...

Page 18: ...18 Notes...

Page 19: ...19 Notes...

Page 20: ...20 Part 9040 658 9 06...

Reviews: