PUREGLOW ANNABELLE Installation And User Instructions Manual Download Page 6

DEBRIS COLLECTION SPACE

The mounting depth of this appliance is 180mm.

In accordance with BS 5871 part 2, minimum debris collection volumes are required behind the installed appliance. These are shown in the
table below and as dimension X on the fireplace diagram shown previously.

CLAY/CEMENT LINES OR BLOCK FLUE WHICH IS NEW, UNUSED, OR PREVIOUSLY ONLY USED WITH A GAS FIRE.

X Dimension = 20mm

UNLINED  FLUE OR CHIMNEY WHICH HAS BEEN PREVIOUSLY USED FOR A SOLID FUEL OR OIL BURNING APPLIANCE

X Dimension = 60mm

VENTILATION

No purpose provided ventilation is normally required for this appliance. The requirements of other appliances operating in the same room or
space must be taken into consideration when assessing ventilation.

If spillage is detected when commissioning the appliance, then amongst other problems there may be insufficient natural ventilation for cor-
rect operation of the flue. If the appliance does not spill with the windows open, but spillage is detected with the windows closed, this demon-
strates a lack of natural ventilation. If spillage is still detected with the windows open, the flue is at fault. Installation of an air brick is the best
solution to lack of ventilation. Any ventilation fitted must comply with BS 5871 part 2 and BS 5440 part 2. Vents fitted under or within the
immediate vicinity of the appliance must not be used as adverse effects to the operation of the ODS may occur.

Spillage detected during commissioning is almost always a result of poor flue performance that cannot be corrected by any amount of venti-
lation.

For Republic of Ireland ventilation may be required, see IS 813, ICP3, IS 327, and any other rules in force.

PREFABRICATED FLUE BOXES

This appliance can be fitted into a number of proprietary flue boxes provided that the minimum dimensions given in the diagram below are
complied with.

Constructional Note: The frame of the fire, any back panel or
other infill panels, and the flue box must be sealed together
so that there is no possibility of leakage between them.
Adequate clearances to combustible materials (e.g. false
chimney breast construction) must be maintained.

The manufacturers’ instructions for fitting the prefabricated
box shall be complied with at all times.

To fit the fire using the cable fixing kit, some minor adaption
may be necessary for certain flue boxes. A check should be
made to ensure the firebox does not obscure the flue box
outlet.

The firebox, base of the flue box, and hearth below may be
drilled to allow plugs and screws to secure installation.

It is important that the sealing requirements of the appliance
are met at all times and that the flue box is well sealed to any
back or infill panel.

Note: The DEPTH dimension is inclusive of any back or infill
panel.

UNPACKING THE APPLIANCE

Stand the carton the right way up, cut the strapping bands and remove the top endcap. Read 

all the instructions before continuing to unpack

or install this appliance.

Remove the box containing the firefront, and the bags containing the ceramic components. Remove the cardboard packing pieces, and any
other bags or boxes containing fittings or other parts. When all loose parts have been removed, the outer sleeve may be lifted off to reveal
the appliance. Check that the components supplied correlate with the component checklist given in section 7.1. Please dispose of all the pack-
aging materials at your local recycling centre.

4

4.1

5.0

125mm min internal dia
twin wall flue

560mm min
opening height

375mm min
opening width

250mm min
depth

6.0

7.0

© 2009 Pure Glow Limited 

Summary of Contents for ANNABELLE

Page 1: ...C 11 09 Country s of destination GB IE FULL DEPTH RADIANT GAS FIRE FOR USE WITH CHLOE JULIET NEW WAVE HEAT WAVE MEDIA CHURCHILL ANNABELLE ZARA CARMEN CARMEN HIW Pure Glow Limited Stourvale Road Lye St...

Page 2: ...he appliance is designed for installation on to a non combustible hearth of at least 300mm depth This appliance is factory set for operation on the gas type and at the pres sure stated on the applianc...

Page 3: ...ce with the Gas Safety Installation and Use Regulations 1998 the relevant British Standards for Installation Codes of Practice and in accordance with the Manufacturers Instructions The installation sh...

Page 4: ...is installed into and the one venting the gases into the air A suitable terminal may be fitted such as class GC1 as regulations allow This appliance has been tested for use in a pre cast block flue co...

Page 5: ...e back of the appliance must have a 50mm mini mum clearance between it and the back wall of the opening or any other obstruction The area immediately above the outlet must form a smooth path into the...

Page 6: ...BRICATED FLUE BOXES This appliance can be fitted into a number of proprietary flue boxes provided that the minimum dimensions given in the diagram below are complied with Constructional Note The frame...

Page 7: ...rebox on it s back Lay the tapered panel onto the rear face of the firebox The side panels should be fitted by inserting their front edges into the pre fitted retaining brackets on the front face of t...

Page 8: ...is good Angle the firebox or adjust the spigot outlet as described in the Fitting the Firebox section Ensure that it slides in correctly the sealing face sits flat and square to the wall or infill pan...

Page 9: ...should be posi tioned as close to the correct layout as possible Before finally fitting cables ensure the self adhesive sealing strips are in position on the back of the appliance frame The fireframe...

Page 10: ...control knob in slightly and continue turning anti clockwise to the high position The main burner should light after a few seconds To decrease the setting to LOW turn the control knob clockwise to the...

Page 11: ...highest setting and any communicating doors open Finally repeat with all doors open DO NOT allow the fire to be used until the test is satisfactorily passed BRIEFING THE CUSTOMER All instructions mus...

Page 12: ...ing leg and lift assembly clear The injector pipe can now be checked for debris Remove the nut retaining the injector elbow Blow through the elbow to remove any debris The valve is not field serviceab...

Page 13: ...me and then cuts off Excessive room draught or flue pull rectify Loose or faulty thermocouple rectify ODS system in operation Firebox grommet seal not fitted rectify Lint in pilot aeration hole clean...

Page 14: ...his fire the coals or pebbles must be of the correct type and laid out in accordance with the relevant section of these instructions Failure to do so could create a hazard or lead to soot ing Before t...

Page 15: ...ge test must be taken into consideration when assessing ventilation requirements this will have been car ried out by your registered installer For Republic of Ireland ventilation may be required see I...

Page 16: ...he second row of coals in order to complete the third row The coals may be orien tated as desired to achieve a realistic effect Keep the spacing between the coals even and uniform The two coals at the...

Page 17: ...orts The fuel bed layout is now complete The fire is designed to operate correctly with the pebbles supplied when assembled according to the instructions Never add to the six teen pebbles or change th...

Page 18: ...ld be the problem and removal of the draught should resolve this The fire can then be re lit in accordance with the previous section A grommet seal may also be missing from the firebox causing abnorma...

Page 19: ......

Reviews: