INSTALLATION REQUIREMENTS

This appliance MUST NOT be installed into a room containing a bath or shower, or where steam may be
present. The fire has been designed to fit into a builders’ opening or fireplace conforming to BS 1251 (and
meeting certain dimensional requirements), or a suitable flue box complying with the constructional
requirements of BS 715. The flue box must be installed onto a suitable non-combustible insulating surface at least
12mm thick, covering the entire base area of the box.

The flue must have an effective height of at least three metres, as measured from the hearth to the top of the flue.
Any flue damper plates or restrictors should be removed and no other restriction fitted to the flue. Where removal
is not practical, the restriction must be fixed in the fully open position.

A natural draught flue system is required, and if previously used for solid fuel or oil burning, the flue and chimney
must be swept prior to appliance installation. Pre-cast flues must be checked for mortar fangs and correct
installation of joints, flue sections in loft space and terminals. The flue must be checked before installation by
using a smoke pellet or similar to ensure proper draw and that leakage is not evident at any joints. Repair and
re-test as necessary before the appliance is installed.

The flue must be connected to only one fireplace, and the flue must not vent more than one appliance (i.e. not
shared with a gas back boiler). There must be no opening in the flue apart from the one that the appliance is
installed into, and the one venting the gases into the air. A suitable terminal may be fitted, such as class GC1, as
regulations allow.

This appliance has been tested for use in a pre-cast block flue complying with BS 1289. In accordance with BS
1289 part 1, pre-cast flues built with directly plastered faces (front or rear) are not correctly installed as to ensure
proper operation with 

any type of gas fire. In some instances of this flue construction, temperature cracking of

the surface plaster may occur through no fault of the appliance. An air gap or some form of insulation material
should be installed to prevent normal flue temperatures from damaging wall surfaces.

This appliance is suitable for use with a “lightweight” surround and back panel of 150

O

C minimum rating.

2

2.0

3.0

APPLIANCE DATA

Manual Control Version

Slide Control Version

Gas Group

G20 Natural Gas CAT I2H

G20 Natural Gas CAT I2H

Inlet Pressure

20 mbar (+/- 2.0mbar)

20 mbar (+/- 2.0mbar)

Max Energy Input (gross)

6.8 kW

6.8 kW

Min Energy Input (gross)

3.5 kW

3.5 kW

Pilot Energy Input (gross)

166 W

166 W

High Burner Pressure (cold)

15.8 mbar (+/- 1.5mbar)

14.5 mbar (+/- 1.5mbar)

Low Burner Pressure (cold)

5.1 mbar (+/- 0.75mbar)

4.5 mbar (+/- 0.75mbar)

Main Injector Burner

Stereo size 81/Bray cat. 82/420

Stereo size 82

Gas Inlet Connection

8mm Inlet Restrictor Elbow

8mm Inlet Restrictor Elbow

Gas Control Valve

Dungs BM 733/NGC 6802D

Teddington TESA 3173/001

Ignition

Integral Piezo spark

Integral Piezo spark

Spark Gap

3.5 to 4.5mm

3.5 to 4.5mm

Weight

20 Kg

21 Kg

Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge, and is
for decorative purposes.

© 2009 Pure Glow Limited 

Summary of Contents for ANNABELLE

Page 1: ...C 11 09 Country s of destination GB IE FULL DEPTH RADIANT GAS FIRE FOR USE WITH CHLOE JULIET NEW WAVE HEAT WAVE MEDIA CHURCHILL ANNABELLE ZARA CARMEN CARMEN HIW Pure Glow Limited Stourvale Road Lye St...

Page 2: ...he appliance is designed for installation on to a non combustible hearth of at least 300mm depth This appliance is factory set for operation on the gas type and at the pres sure stated on the applianc...

Page 3: ...ce with the Gas Safety Installation and Use Regulations 1998 the relevant British Standards for Installation Codes of Practice and in accordance with the Manufacturers Instructions The installation sh...

Page 4: ...is installed into and the one venting the gases into the air A suitable terminal may be fitted such as class GC1 as regulations allow This appliance has been tested for use in a pre cast block flue co...

Page 5: ...e back of the appliance must have a 50mm mini mum clearance between it and the back wall of the opening or any other obstruction The area immediately above the outlet must form a smooth path into the...

Page 6: ...BRICATED FLUE BOXES This appliance can be fitted into a number of proprietary flue boxes provided that the minimum dimensions given in the diagram below are complied with Constructional Note The frame...

Page 7: ...rebox on it s back Lay the tapered panel onto the rear face of the firebox The side panels should be fitted by inserting their front edges into the pre fitted retaining brackets on the front face of t...

Page 8: ...is good Angle the firebox or adjust the spigot outlet as described in the Fitting the Firebox section Ensure that it slides in correctly the sealing face sits flat and square to the wall or infill pan...

Page 9: ...should be posi tioned as close to the correct layout as possible Before finally fitting cables ensure the self adhesive sealing strips are in position on the back of the appliance frame The fireframe...

Page 10: ...control knob in slightly and continue turning anti clockwise to the high position The main burner should light after a few seconds To decrease the setting to LOW turn the control knob clockwise to the...

Page 11: ...highest setting and any communicating doors open Finally repeat with all doors open DO NOT allow the fire to be used until the test is satisfactorily passed BRIEFING THE CUSTOMER All instructions mus...

Page 12: ...ing leg and lift assembly clear The injector pipe can now be checked for debris Remove the nut retaining the injector elbow Blow through the elbow to remove any debris The valve is not field serviceab...

Page 13: ...me and then cuts off Excessive room draught or flue pull rectify Loose or faulty thermocouple rectify ODS system in operation Firebox grommet seal not fitted rectify Lint in pilot aeration hole clean...

Page 14: ...his fire the coals or pebbles must be of the correct type and laid out in accordance with the relevant section of these instructions Failure to do so could create a hazard or lead to soot ing Before t...

Page 15: ...ge test must be taken into consideration when assessing ventilation requirements this will have been car ried out by your registered installer For Republic of Ireland ventilation may be required see I...

Page 16: ...he second row of coals in order to complete the third row The coals may be orien tated as desired to achieve a realistic effect Keep the spacing between the coals even and uniform The two coals at the...

Page 17: ...orts The fuel bed layout is now complete The fire is designed to operate correctly with the pebbles supplied when assembled according to the instructions Never add to the six teen pebbles or change th...

Page 18: ...ld be the problem and removal of the draught should resolve this The fire can then be re lit in accordance with the previous section A grommet seal may also be missing from the firebox causing abnorma...

Page 19: ......

Reviews: