PUREGLOW ANNABELLE Installation And User Instructions Manual Download Page 11

SETTING PRESSURE (continued)

solder flashing across a joint. (NOTE: you will not get an accurate reading of the inlet pressure with a pressure gauge on the end of the sup-
ply pipe - this is the static pressure in the system. You must use a T piece and measure the supply pressure with the fire on High - the dynam-
ic pressure). Refit and tighten the screw into the pressure test point when the test is complete.

FLUE SPILLAGE MONITORING SYSTEM

This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason then several things may be
suspected. If a door or window has been opened creating a draught, then pilot disturbance is the problem, and removal of the draught should
resolve this. The gas pressure reaching the fire must also be checked (again, recall your installer to check and rectify any problem). The ther-
mocouple connection into the back of the gas control valve may also have worked loose during installation, simply get the installer to tight-
en. If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance OFF, check the flue and carry
out any remedial work required. Relight the fire and carry out a spillage test. DO NOT allow the appliance to be used if it continues to fail a
spillage test.

The aeration hole of the pilot must be carefully cleaned out on each annual service to ensure continued function of the ODS.
The spillage monitoring system shall not be adjusted, modified, or put out of operation by the installer. Any spare parts fitted MUST be of a
type supplied for the purpose by the appliance manufacturer. If the fire is not spilling, then further guidance should be sought, using the
Troubleshooting section as a guide.

TESTING FOR SPILLAGE

Close all doors and windows to the room containing the appliance. Let the fire run on HIGH for five minutes. Take a smoke match, light it,

and using a smoke match

tube, hold it at the top edge

of the fire opening, 25mm down and 25mm in. Starting 50mm in from either side, run the smoke match across the opening. All the smoke
should be drawn away up the flue. Any smoke returning into the room indicates that spillage is occurring. If the initial spillage test fails, run
the fire for a further 10 minutes and repeat the test. When the test has been completed satisfactorily, repeat with any extractor fans in the
premises running on the highest setting, and any communicating doors open. Finally, repeat with all doors open.

DO NOT allow the fire to be used until the test is satisfactorily passed.

BRIEFING THE CUSTOMER

All instructions must be handed to the user for safekeeping. Show the customer how to light and control the fire.
After commissioning the appliance, the customer should be instructed on the safe use of the appliance and the need for regular servicing.
Frequency of service depends on usage, but MUST be carried out at least once annually.
Advise that cleaning of the fire may be achieved when the fire is cold using a damp cloth and mild detergent on most surfaces.
Scratched and other superficial damage to the matt black paintwork of the appliance can be covered with matching heatproof spray. Use
only the manufacturers’ recommended spray paint. Paint only when the fire is OFF and cold. Always mask off the surrounding area to pre-
vent contamination with overspray. Ventilate the room during the use of the spray. DO NOT attempt to spray paint the coals or ceramics, or
wash them in water.
Advise that the fire will emit a “newness” smell for a time after initial commissioning and that extra ventilation may be needed during this
time. Advise that the fire is fitted with a spillage safety device (O.D.S.). If the fire shuts down, this system may be in operation. If spillage is
suspected, SWITCH APPLIANCE OFF and call in the installer to investigate any problems.

SERVICING

Isolate the fire from the gas supply. Ensure that the fire is fully cold before attempting service. A suggested procedure for servicing is detailed
below.

1. Lay out the dust sheet and tools.
2. Carefully remove the ceramic components.
3. Remove the firefront.
4. Remove the two screws that retain the data/control plate. 
5. Disconnect the gas supply, and remove the two securing screws in the tray legs.
6. Remove the burner tray.
7. Remove firebox as described.
8. Check the fireplace opening for rubble accumulation and remove. If debris is excessive, initiate remedial work on the flue.
9. Check the flue with smoke pellet for correct operation.
10. Refit firebox using new seals where necessary.
11. Strip off the burner pipes and clean thoroughly.

9

A.25mm down from

top of opening

B. 25mm in from

front of opening.

C. Disregard outer

50mm either side of

fireplace opening

Match

Crimp

Tube

Cross section of smoke match tube

Make a smoke match tube from 10mm diameter tube.
Seal off one end and crimp the tube to prevent the
smoke match from sliding down inside.

C

C

B

A

Fireplace Opening

Smoke Match

In Tube

14.5

14.6

15.0

© 2009 Pure Glow Limited 

14.4

16.0

Summary of Contents for ANNABELLE

Page 1: ...C 11 09 Country s of destination GB IE FULL DEPTH RADIANT GAS FIRE FOR USE WITH CHLOE JULIET NEW WAVE HEAT WAVE MEDIA CHURCHILL ANNABELLE ZARA CARMEN CARMEN HIW Pure Glow Limited Stourvale Road Lye St...

Page 2: ...he appliance is designed for installation on to a non combustible hearth of at least 300mm depth This appliance is factory set for operation on the gas type and at the pres sure stated on the applianc...

Page 3: ...ce with the Gas Safety Installation and Use Regulations 1998 the relevant British Standards for Installation Codes of Practice and in accordance with the Manufacturers Instructions The installation sh...

Page 4: ...is installed into and the one venting the gases into the air A suitable terminal may be fitted such as class GC1 as regulations allow This appliance has been tested for use in a pre cast block flue co...

Page 5: ...e back of the appliance must have a 50mm mini mum clearance between it and the back wall of the opening or any other obstruction The area immediately above the outlet must form a smooth path into the...

Page 6: ...BRICATED FLUE BOXES This appliance can be fitted into a number of proprietary flue boxes provided that the minimum dimensions given in the diagram below are complied with Constructional Note The frame...

Page 7: ...rebox on it s back Lay the tapered panel onto the rear face of the firebox The side panels should be fitted by inserting their front edges into the pre fitted retaining brackets on the front face of t...

Page 8: ...is good Angle the firebox or adjust the spigot outlet as described in the Fitting the Firebox section Ensure that it slides in correctly the sealing face sits flat and square to the wall or infill pan...

Page 9: ...should be posi tioned as close to the correct layout as possible Before finally fitting cables ensure the self adhesive sealing strips are in position on the back of the appliance frame The fireframe...

Page 10: ...control knob in slightly and continue turning anti clockwise to the high position The main burner should light after a few seconds To decrease the setting to LOW turn the control knob clockwise to the...

Page 11: ...highest setting and any communicating doors open Finally repeat with all doors open DO NOT allow the fire to be used until the test is satisfactorily passed BRIEFING THE CUSTOMER All instructions mus...

Page 12: ...ing leg and lift assembly clear The injector pipe can now be checked for debris Remove the nut retaining the injector elbow Blow through the elbow to remove any debris The valve is not field serviceab...

Page 13: ...me and then cuts off Excessive room draught or flue pull rectify Loose or faulty thermocouple rectify ODS system in operation Firebox grommet seal not fitted rectify Lint in pilot aeration hole clean...

Page 14: ...his fire the coals or pebbles must be of the correct type and laid out in accordance with the relevant section of these instructions Failure to do so could create a hazard or lead to soot ing Before t...

Page 15: ...ge test must be taken into consideration when assessing ventilation requirements this will have been car ried out by your registered installer For Republic of Ireland ventilation may be required see I...

Page 16: ...he second row of coals in order to complete the third row The coals may be orien tated as desired to achieve a realistic effect Keep the spacing between the coals even and uniform The two coals at the...

Page 17: ...orts The fuel bed layout is now complete The fire is designed to operate correctly with the pebbles supplied when assembled according to the instructions Never add to the six teen pebbles or change th...

Page 18: ...ld be the problem and removal of the draught should resolve this The fire can then be re lit in accordance with the previous section A grommet seal may also be missing from the firebox causing abnorma...

Page 19: ......

Reviews: