PUREAIR AIR PURIFICATION SYSTEM
PHOTOCATALYTIC OXIDATION (PCO) TECHNOLOGY
Dimensions and Specifications
10
(254)
A
B
PCO14-23
23 (584)
21-1/8 (537)
Model
A
B
PCO16-28
PCO20-28
28-1/2 (724)
21-1/8 (537)
28-1/2 (724)
16-1/2 (419)
Figure 3. Dimensions and Specifications
WEIGHT
PCO14-23
34 lbs.
PCO16-28
36 lbs.
PCO20-28
39 lbs.
ELECTRICAL
PCO14-23
120V, 50/60 Hz,
1.2 Amps -- Maximum,
230 V, 50/60 Hz,
0.65 Amps -- Maximum
PCO16-28
PCO20-28
POWER CONSUMPTION
120VAC
144 Watts Nominal
230VAC
150 Watts Nominal
OPERATING ENVIRONMENT
0°F to 140°F outside of duct.
10 to 60 percent relative humidity.
(Optimal performance at 50 percent relative humidity)
PLEATED FILTER EFFICIENCY
Minimum Efficiency Rating Value (MERV) 16.
LISTINGS
ETL safety listing report 3061144A. Conforms to UL STD
1598. Certified to CSA STD C22.2 no. 250.0.
Approximate Air Flow Resistance (Cabinet and Filter)
Capacity
(Tons)
Flow
Rate
(CFM)
Pressure Drop (in. w.g.)
PCO14-23
PCO16-28
PCO20-28
2
800
0.12
0.11
0.09
2.5
1000
0.17
0.15
0.12
3
1200
0.22
0.20
0.16
3.5
1400
0.28
0.25
0.19
4
1600
*
0.30
0.23
4.5
1800
*
*
0.28
5
2000
*
*
0.32
*Not recommended. Excessive system pressure drop can
damage HVAC system and reduce performance.
Installation
Select a Location
The PCO must be installed in the return air duct upstream
of the supply blower. Allow a 30-inch service clearance in
front of the access door as shown in figure 4. The control
box, pleated filter and PureAir Insert must be removable.
Allow Approximately
30” of Clearance
Figure 4. Service Clearance
NOTICE
The PCO should be installed so that the lamps will
be in the horizontal position.
If the PCO must be installed with the access panel
pointing upward and the lamps suspended vertical
ly from the sockets, retaining clips are required to
lock the lamps in the sockets. Contact the Technical
Support Department at 1-800-953-6669 for addition
al information.