Page
96
Alarms
P210, 220, 230, 240, 250, 260 =1 (Alarm)
The
second parameter
for each relay determines the
function
of the alarm.
P211, P221, P231. P241, P251, P261 - Relay Function
This parameter defines what
function
the
alarm
will respond to as follows.
Option
Description
0= Off (Default)
Relay will not operate.
1 = Level
Alarm is based on the level in the vessel, and the
type of level alarm (P2
1
2, 2
2
2, 2
3
2, 2
4
2, 2
5
2, 2
6
2)
and two setpoints must be set (P2
1
3, 2
2
3, 2
3
3, 2
4
3,
2
5
3, 2
6
3 & P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4).
Setpoints are entered in Display Units or % of span
as referenced to Empty Level
*
.
2 = Temperature
Alarm is based on the temperature, and the type of
temperature alarm (P2
1
2, 2
2
2, 2
3
2, 2
4
2, 2
5
2, 2
6
2)
and two setpoints must be set (P2
1
3, 2
2
3, 2
3
3, 2
4
3,
2
5
3, 2
6
3 & P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4). The
temperature used depends on the temperature
source selected (P852). Setpoints are entered in
o
C.
3 = Loss of Echo
Alarm is raised if the
Failsafe
Timer
(
P809
)
expires. No setpoints are required.
4 = Loss of Clock
Alarm is raised if the real time clock fails. No
setpoints are required.
5 = Wiper Fault
Alarm is raised if the wiper fails on a VT transducer.
No setpoints are required.
6 = High Floc
Alarm*
An alarm is raised if the floc level reaches the level
of intrusion as set in
% intrusion P1-163
.
7 = Service
Alarm**
An alarm is raised when the unit has reached its
service interval (see service manual for details)
*This is only available in units with firmware version 1.1.0 or greater.
**This is only available in units with firmware version 1.1.1 or greater.
Summary of Contents for SLUDGE FINDER 2
Page 1: ...SLUDGE FINDER 2 INSTRUCTION MANUAL ...
Page 2: ......
Page 4: ......
Page 13: ...Page 7 EC Declaration of Conformity ...
Page 14: ...Page 8 This page left blank intentionally ...
Page 18: ...Page 12 The full dimensions of the enclosure are as shown below ...
Page 25: ...Page 19 ...
Page 29: ...Page 23 Transducer Installation Options 1 Stainless steel mounting plate Fig 1 ...
Page 42: ...Page 36 Enclosure Dimensions ...
Page 45: ...Page 39 Receiver and Transmitter Dimensional Details ...
Page 70: ...Page 64 This page left blank intentionally ...
Page 94: ...Page 88 This page left blank intentionally ...
Page 132: ...Page 126 This page is left blank intentionally ...