RUPS824P 

 

 

 

            

RACK POWER 

 

 

CONTENTS: 
1. Technical description. 

1.1. General description 
1.2. Block diagram 
1.3. Description of PSU components and connectors 
1.4. Specifications 

2. Installation. 

2.1. Requirements 
2.2. Installation procedure 

3. Operating status indication. 

3.1. LED indication 
3.2. Technical output 
3.3. Acoustic indication 

4. Operation and use. 

4.1. Overload or short circuit of the PSU output 
4.2. Battery-assisted operation 
4.3. Maintenance 

1.  Technical description. 
 

1.1.  General description. 

    The buffer power supply

 RUPS824P

 is used for uninterrupted supply of devices requiring stabilized voltage 

of 

24V DC (+/- 15%). 

The PSU supplies voltage of 

U=27,6V

 

DC

 and total current capacity of:

  

 

Output current 8A + 1A battery charge. 
Total device c battery: 9A max.

 

 
    In  case  of  power  decay,  a  battery  back-up  is  activated  immediately.  The  PSU  is  fitted  with  8  outputs 

protected independently with polymer fuses PTC 1A. The power supply is fitted with the ALARM output of collective 
failure. In case of failure, relay contacts are switched automatically, which is accompanied by acoustic and optical 
indication (the corresponding led goes on). The power supply construction is based on the switch mode PSU with 
high energy efficiency and is located in an enclosure adapted for mounting in standard 

RACK

 19

” cabinets.  

 

1.2.  Block diagram. 

 

 

Fig.1. The block diagram of the PSU. 

 
1.3.  Description of PSU components and connectors. 
 

Table 1. Elements the front power of the power supply unit. 

Element no. 

[Fig. 2] 

Description 

 

AC

 

OK

 

– green LED, indicating the presence of 230V voltage 

 

DC

 

OK

 

– green LED, indicating the presence of DC voltage

 

 

TEMP 

– red LED, indicating too high temperature of the power supply (>70°C)

 

 

LoB 

– red LED, indicating too low battery voltage (<23V)

 

 

LED ALARM 

– red LED failure indication 

Summary of Contents for RUPS824P

Page 1: ...RUPS824P v 1 0 RUPS 27 6V 8x1A PTC RACK mounted buffer power supply EN Edition 2 from 30 03 2017 Supercedes the edition 1 from 16 08 2016 ...

Page 2: ...arge current 1A batteries 2 7Ah 2x17Ah 2x28Ah control of voltage presence at the AUX1 AUX8 outputs acoustic indication of failure LED optical indication AC DC TEMP LoB ALARM AUX1 AUX8 the ALARM technical output of collective failure relay type activated by 230V AC power loss low voltage of the PSU 23V activation of the output fuse too high temperature of the PSU 70 C the PSU failure protections SC...

Page 3: ...cay a battery back up is activated immediately The PSU is fitted with 8 outputs protected independently with polymer fuses PTC 1A The power supply is fitted with the ALARM output of collective failure In case of failure relay contacts are switched automatically which is accompanied by acoustic and optical indication the corresponding led goes on The power supply construction is based on the switch...

Page 4: ...cal output of collective failure relay BUZZER micro switch turning ON OFF of acoustic indication switch in the top position indication ON switch in the down position indication OFF 230V AC INPUT power socket 230V AC power cable 1 5m included FMAINS fuse in the supply circuit 230V AC T 6 3A 250V Fig 2 The front power of the power supply unit Fig 3 The view of the PSU ...

Page 5: ...e ALARM technical output of collective failure Relay type 1A 30VDC 50VAC FMAINS fuse in the power supply circuit 230V T 6 3A Mechanical parameters tab 3 Enclosure dimensions W 19 H 2U 482 x 88 x 223 mm WxHxD Fixation four point butt mounting to RACK profiles the set include 4 M6 screws cage nuts Net weight 5 8kg 6 2kg Enclosure Steel plate RAL 9005 black Connectors 230V AC input the IEC C14 socket...

Page 6: ...d about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the power supply in a RACK 19 cabinet as shown below Mount M6 cage nuts Secure the enclosure with 4xM6 screws 3 Connect the rece...

Page 7: ...ctive failure can be triggered by the following events 230V AC mains power failure Activation of the polymer fuse PTC Failure of the switch mode power supply Too high temperature of the switch mode power supply 70 C Low battery voltage 23V Fig 4 Electrical diagram of the ALARM collective output of failure CAUTION In Fig 4 the set of contacts shows a potential free status of the relay which corresp...

Page 8: ...ge below 19V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures In case of fuse replacement use a replacement of the same parameters WEEE LABEL Waste electrical and electronic equipment ...