[8] 

I

BAT 

Jumper; 

- battery charging current configuration 

 

J1= 

  J2= 

  J3= 

   Ibat =1A 

 

J1= 

  J2= 

  J3= 

   Ibat =2A 

 

J1= 

  J2= 

  J3= 

   Ibat =3A 

 

J1= 

  J2= 

  J3= 

   Ibat =5A   

Description: 

 jumper on, 

  jumper off 

[9] 

LB  

– LED battery charging indication 

[10] 

OVP - 

LED indicating activation of the over voltage protection OVP

 

 

 

Fig.2. The view of the PSU pcb. 

 

       Table 2. Components of the PSU (See Fig. 3). 

Element no. 

[Fig. 3] 

Description outputs of the PSU 

[1] 

Insolation transformer 

[2] 

PSU board

 

(tab. 1)

 

[3] 

TAMPER  

micro-switch (contacts) of tamper resistance

 (NC) 

[4] 

F

MAIN

 

fuse in the supply circuit (230V AC), T6,3A / 250V

 

[5] 

 L-N  

power supply connector, 230V AC, 

 PE protective connector

 

[6] 

Battery connectors: positive: +BAT = red, negative: - BAT = black 

[7] 

Recorder’s fuse module – 1x12V/ 5A outputs 

[8] 

Recorder’s voltage adjustment (11-13,8V DC) factory setting 12V/DC 

[9] 

Fuse module of CCTV cameras 

– 8x12V/ 0,5A outputs 

[10] 

Cameras’ voltage CCTV adjustment (11-13,8V DC) factory setting 12V/DC 

 

Summary of Contents for PSUPS10A12

Page 1: ...PSUPS10A12 v 1 3 PSUPS 13 8V 12V 10A 40Ah Buffer power supply for 8 cameras and recorder EN Edition 6 from 25 05 2015 Supercedes the edition 5 from 06 08 2014...

Page 2: ...utputs of the OC type to relay adjustable times of 230V AC failure indication protections SCP short circuit protection OLP overload protection OVP over voltage protection OHP overheat protection surge...

Page 3: ...rcuit Board see Fig 2 Element no Description 1 PBAT pin configuration of the battery protection system UVP PBAT discharged battery disconnection system OFF PBAT discharged battery disconnection system...

Page 4: ...ig 3 Element no Fig 3 Description outputs of the PSU 1 Insolation transformer 2 PSU board tab 1 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230V AC T6 3A...

Page 5: ...www pulsar pl PSUPS10A12 5 Fig 3 The view of the PSU...

Page 6: ...olarity connection T10A current limiting FBAT fuse failure requires fuse element replacement Surge protection varistors Over voltage protection OVP U 16V automatic return Deep discharge protection UVP...

Page 7: ...60 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse waves duri...

Page 8: ...to the technical outputs EPS technical output indicating AC power failure PSU technical output indicating PSU failure LoB technical output indicating low battery voltage Optional installation of the M...

Page 9: ...fig 2 red diode indicates activation of the over voltage protection OVP Under normal status the diode is off If the converter s voltage exceeds 16V the diode is permanently illuminated 3 2 Technical o...

Page 10: ...ration of the voltage at the BAT output requires the replacement of the fuse 4 2 Overload or short circuit of the recorder s module or CCTV camera module The modules of the recorder and CCTV cameras a...

Page 11: ...ir period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms b...

Page 12: ...www pulsar pl PSUPS10A12 12 Pulsar Siedlec 150 32 744 apczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl...