PSUPS10A12 

 

 

 

 

 
 

 

1.1.  General description. 

 

A buffer PSU is intended for an uninterrupted supply to CCTV system devices requiring stabilized voltage of 

12V 

DC  (+/-15%)

.  The  PSU  has  two  circuits:  first  12V  DC  5A  for  supplying  the  recorder,  second  8x0,5A/12VDC  for  both 

cameras.  
Current efficiency of the PSU amounts to

 8x0,5A + 1x5A. 

 

Total current of the rec battery: 11A max.

 

 

 

In  case  of  a  mains  power  loss,  a  battery  back-up  is  activated  immediately.  The  PSU  is  mounted  in  a  metal 

enclosure  (RAL  9003  colour)  that  accommodates  a  40Ah/12V  battery.  The  enclosure  is  equipped  with  a  micro-switch 
indicating unwanted opening of the door (faceplate) or detachment from the mounting surface. 

 

1.2.  Block diagram (fig.1). 
 

 

 

Fig.1. Block diagram of the PSU. 

 

1.3 Description of PSU components and connectors (tab.1, tab.2,  fig.2, fig.3). 

     Table 1. Components of the Power supply PCB (Printed Circuit Board) (see Fig. 2). 

Element no. 

 

Description 

[1] 

P

BAT

; pin 

configuration of the battery protection system UVP 

 

P

BAT

 = 

 discharged battery disconnection system OFF 

 

P

BAT

 = 

  discharged battery disconnection system ON 

 

T

AC

 Jumper

- setting the delay time for AC power failure indication 

 

T

AC

 = 

 delay time T= 10s 

 

T

AC

 = 

 delay time T= 60s 

Caption: 

 jumper on, 

  jumper off 

[2] 

START

 button (launching the PSU from a battery) 

[3] 

V

ADJ

 potentiometer, DC power adjustment 12 

÷ 14,5V 

[4] 

F

BAT

 

fuse in the battery circuit,  T10A / 250V 

[5] 

Terminals: 
~AC~    

– AC power input 

EPS 

– technical output of AC power failure indication 

 

 

hi-Z state 

= AC power failure 

 

 

 

0V state  

= AC power - O.K. 

PSU

  

– technical output of PSU failure indication 

 

 

hi-Z state 

= failure 

 

 

0V state  

= PSU status O.K.

  

LoB

 

– technical output of low battery voltage indication 

 

 

hi-Z state 

= battery voltage U

BAT

 <11,5V 

 

 

0V state = battery O.K.  

+BAT-   

 

terminals for battery connection 

+AUX-  

–DC power output, (+AUX= +U, -AUX=GND) 

Description: hi-Z 

– high impedance, 0V – connection to the ground GND 

[6] 

LEDs  

– optical indication:

 

AC  

– AC power

  

AUX, AUX1, AUX2, AUX3 

– output voltage DC 

[7] 

LED indication connector 

Summary of Contents for PSUPS10A12

Page 1: ...PSUPS10A12 v 1 3 PSUPS 13 8V 12V 10A 40Ah Buffer power supply for 8 cameras and recorder EN Edition 6 from 25 05 2015 Supercedes the edition 5 from 06 08 2014...

Page 2: ...utputs of the OC type to relay adjustable times of 230V AC failure indication protections SCP short circuit protection OLP overload protection OVP over voltage protection OHP overheat protection surge...

Page 3: ...rcuit Board see Fig 2 Element no Description 1 PBAT pin configuration of the battery protection system UVP PBAT discharged battery disconnection system OFF PBAT discharged battery disconnection system...

Page 4: ...ig 3 Element no Fig 3 Description outputs of the PSU 1 Insolation transformer 2 PSU board tab 1 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230V AC T6 3A...

Page 5: ...www pulsar pl PSUPS10A12 5 Fig 3 The view of the PSU...

Page 6: ...olarity connection T10A current limiting FBAT fuse failure requires fuse element replacement Surge protection varistors Over voltage protection OVP U 16V automatic return Deep discharge protection UVP...

Page 7: ...60 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse waves duri...

Page 8: ...to the technical outputs EPS technical output indicating AC power failure PSU technical output indicating PSU failure LoB technical output indicating low battery voltage Optional installation of the M...

Page 9: ...fig 2 red diode indicates activation of the over voltage protection OVP Under normal status the diode is off If the converter s voltage exceeds 16V the diode is permanently illuminated 3 2 Technical o...

Page 10: ...ration of the voltage at the BAT output requires the replacement of the fuse 4 2 Overload or short circuit of the recorder s module or CCTV camera module The modules of the recorder and CCTV cameras a...

Page 11: ...ir period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms b...

Page 12: ...www pulsar pl PSUPS10A12 12 Pulsar Siedlec 150 32 744 apczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl...

Reviews: