background image

 

2

CONTENTS: 
1. Technical description. 

1.1. General description 
1.2. Block diagram 
1.3. Description of elements and connectors of the power supply 
1.4. Technical parameters 

2. Installation. 

2.1. Requirements 
2.2. Procedure of installation 

3. Signalling the operation of power supply. 

3.1. Optical signalling 
3.2. Technical output 

4. Service and operation.  

4.1. Overload and short-circuit 

 

4.2. Maintenance 

 

 

1. Technical description. 
 

1.1. General description. 

AC/AC 

PSAC  04244

  power  supply  is  using  for  supplying  alarm  systems  devices  requiring  AC  voltage  of 

24  V

  with  overall 

efficiency of 

4A@24V AC.

  

Basic features of the power supply: 

 

4 outputs 

protected independently by fuses or PTC: failure (short-circuit) within the circuit of any of the outputs will 

result in burnout of the safety device insert/actuation of the PTC and isolation of the circuit from power supply. 

 

regulation of the output voltage

: in case of installation, where significant drops in voltage in effective resistance of 

receiver supply cables can occur, it is possible to correct the value of output voltage with the help of U1/U2 jumper, 
independently for each AUX output. 

 

optical work signalling

 informing about the condition of outputs and/or failure.

 

 

AW technical output

 informing about output failure (activity of the SCP), used for remote control of the activity. 

 

protection:

 short-circuit protection (SCP), overload protection (OLP), overheat protection of the transformer (OHP) 

 

metal casing

 (colour – RAL 9003) with signalling panel.

 

 

 

Information about additional elements of PSAC 04244 power supply 

       -  module  of  the  AC/AC  power  supply  in  ABS  casing,  MSC  1512  (module  of  MSC  12V/1.5A  or  24V/1A  power  supply, 
exchanged voltage) allowing to create a 24 V AC and 12 V DC/24 V DC supply system. 
 
 

Information about types: 

Model 

Description 

PSAC 08246 
PSU-U-24V/AC-6A/8/FTA/PTC-TR-MC 

AC/AC 24 V AC power supply, with overall current efficiency of 6 A@24V 
and switched output voltage of 24.0 V/27.0 V. Equipped with AUX outputs 
condition signaling panel. IP20 metal casing with signaling panel, equipped 
with TAMPER microswitch. 

PSACH 01244 
PSU-U-24V/AC-4A/1/FTA-TR-HC 

AC/AC 24 V AC power supply, with overall current efficiency of 4 A@24V 
and switched output voltage of 24.0 V/27.0 V. ABS IP65 casing equipped 
with TAMPER microswitch. 

PSACH 04244 
PSU-U-24V/AC-4A/4/FTA/PTC-TR-HC 

AC/AC 24 V AC power supply, with overall current efficiency of 4 A@24V 
and switched output voltage of 24.0 V/27.0 V. Equipped with AUX outputs 
condition signaling panel. ABS IP65 casing equipped with TAMPER 
microswitch. 

 

 

 

 

 

 

 

All manuals and user guides at all-guides.com

Summary of Contents for PSU-U-24V/AC-4A/4/FTA/PTC-TR-MC

Page 1: ...PSU U 24V AC 4A 4 FTA PTC TR MC PSAC 04244 v 1 0 AC AC power supply unit EN Edition 1 dated 03 03 2010 Replaces edition All manuals and user guides at all guides com...

Page 2: ...puts and or failure AW technical output informing about output failure activity of the SCP used for remote control of the activity protection short circuit protection SCP overload protection OLP overh...

Page 3: ...amp 5 LAW red diode signalling failure of one of the outputs activation of a safety device 6 AW output signalling failure of one of the outputs OC type normal L status failure hi Z 7 Jumper of the cha...

Page 4: ...er 2 LB4 24V 27V AW fuse block table 1 3 TAMPER anti sabotage protection contact NC 4 F fuse in supply circuit 230 V AC 5 L N connection of 230 V AC power supply PE protection connection Table 2 Termi...

Page 5: ...5 Fig 4 View of the power supply All manuals and user guides at all guides com...

Page 6: ...g LED diodes L1 L4 green LED diode LAW red status of AUX1 AUX4 outputs normal status illuminated failure status not illuminated failure signalling of min one AUX output normal status not illuminated f...

Page 7: ...conductor Power conductors should be connected to proper terminals through seal wire The circuit of the shock protection shall be performed with a particular care i e the yellow and green protection...

Page 8: ...3 Warranty shall cover free repair or provision of functional equivalent the producer shall select the equivalent of the faulty device due to reasons lying in the domain of the producer including prod...