PSBEN3024C   

 

 

 
 

Table 3. A description of the buttons and LEDs of the LED panel. 

 

- parameter selection 

 

 
- selection approval 
 

 

- red LED – indicates presence of the AC voltage  

 

- red LED – indicates overload of the PSU 

 

- red LED – indicates failure of the PSU 

 

- red LED – indicates battery failure 

 

- green LED – indicates power at the AUX output of the PSU 

 

- three yellow LEDs – indicate battery charging level 
 

    
 

 

 

Fig. 5. Menu of the display. 

 
 

 

FLt

 

PSU fault memo (30 last events)

 

 

Io

 

- AUX 

output current measurement 

[A] 

 

Uo

 

- AUX 

output voltage measurement 

[V]

 

 
 

Resolution  for  voltage  measurement  amounts  to  0.1V,  for  current  measurement:  0.1A.  Displayed 
voltage and current rates are only approximate. For higher accuracy, a multimeter shall be used.  

 

            

 

3.2 Overview of current failures. 

If any incorrect electrical parameters occur, the PSU will signal the failure  by illuminating an appropriate LED 

on the panel or by activating an acoustic indication (provided it has not been switched off). After pressing the ‘OK’ 
button,  the  panel  display  will  show  a  code  of  the  fault  that  trigger  the  failure.  If  more  than  one  failure  occurs 
simultaneously, another pressing 

the

 ‘OK’ button will display the next failure code. 

Summary of Contents for PSBEN 3024C

Page 1: ...PSBEN 3024C v 1 0 PSBEN 27 6V 3A 2x17Ah EN Buffer switched mode power supply unit EN Edition 3 from 20 11 2012 Supersedes the 2 from 14 09 2012 edition...

Page 2: ...11 4 4 STANDBY TIME 11 4 5BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 12 5 REMOTE MONITORING OPTION WI FI ETHERNET RS485 USB 13 5 1 COMMUNICATION IN WI FI WIRELESS NETWORK 13 5 2 COMMUNIC...

Page 3: ...d OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical output indicating AC po...

Page 4: ...urce are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 1 5A battery charge General use if the PSU is not mounted within an installation which is...

Page 5: ...ring battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZER acoustic indica...

Page 6: ...ent no Description 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE...

Page 7: ...status indication 3 1 Control panel The PSU is equipped with a panel with buttons and an LED display which enables reading the basic parameters of the device The buttons are for selecting and approvin...

Page 8: ...ment A Uo AUX output voltage measurement V Resolution for voltage measurement amounts to 0 1V for current measurement 0 1A Displayed voltage and current rates are only approximate For higher accuracy...

Page 9: ...ith galvanic isolation which change state if any of the following event occur EPS FLT output indicating AC power loss The output indicates AC power loss Under normal status with the 230V AC supply the...

Page 10: ...IN technical input has been implemented with galvanic isolation between the PSU s systems and the devices attached Fig 7 Electrical diagram of the EXT IN input The electrical diagram below shows the w...

Page 11: ...attery test facility can be switched off Deactivating activating the test during mains powered PSU operation press the STOP button on the main board and hold it for 3 seconds The device will confirm t...

Page 12: ...A Configuration of IBAT jumper 10h12m 1 5 J1 J2 J3 15h18m 1 J1 J2 J3 25h30m 0 6 J1 J2 J3 0 2 J1 J2 J3 4 6 Operation without a battery In case of an expected PSU operation without an attached battery m...

Page 13: ...ge of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 10 WI FI communication with the use of the WI FI INTW interface 5 2 Communi...

Page 14: ...B TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 13 KUSB TTL communication...

Page 15: ...for general use Io 3A 0 2A battery charge Io 2 6A 0 6A battery charge Io 2 2A 1A battery charge Io 1 7A 1 5A battery charge Output voltage setting escalation and keeping time 8ms 35ms 25ms Output vol...

Page 16: ...can be led Convectional cooling Table 8 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input network ci...

Page 17: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 15 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Page 18: ...ers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by soun...

Page 19: ...t voltage 29 4V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 28V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 26V Fault in...

Page 20: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...