4.2 Battery assisted operation.  

In the case of power failure, in the unit will instantly switch to the battery assisted operation.

 

In  order  to  activate  the  operation  of  the  PSU  from  the  battery  itself,  connect  the  BAT  connectors  in 

accordance  with  the  indications:  +BAT red to ‘plus’ and, -BAT black to 'minus’ of the battery and press and keep 
depressed for five seconds the START pushbutton on the equipment board. 

The  PSU  is  equipped  with  the  discharged  battery  disconnection  system  (UPV);  the  configuration  of 
functions through the dip switch ‘JP-B’. The battery protection is on if the dip switch ‘JP-B’ is removed.

 

 

4.3 Maintenance 

Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power supply network. The PSU does not require performing any specific maintenance measures, however, in the 
case  of  significant  dust  rate,  its  interior  is  recommended  to  be  cleaned  with  compressed  air.  In  the  case  of  fuse 
replacement, only the substitutes in conformity to the original ones are allowed. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for PSBD 5012

Page 1: ...PSU B 13 8V S 5A 1 EL TR 40Ah MC PSBD 5012 v 1 1 Buffer switching power supply unit EN Edition 2 from the 21 st June 2010 Supercedes edition 1 from the 21 st April 2009...

Page 2: ...it with the total current capacity 5A and output voltage 11 0V 13 8V Equipped with the AC supply absence indication system battery assisted operation failure and casing sabotage indication system Meta...

Page 3: ...ration 2 x converter DC DC 2 5A 5V ADC 255 2 x LB5 AW fuse block AWZ 536 40Ah 2 x voltage reducer RN 2 5A 12V RN250 2 x LB5 AW fuse block AWZ 536 40Ah 1 x voltage reducer RN 5 0A 12V RN500 2 x LB5 AW...

Page 4: ...5A J1 J2 Ibat 2 0A Legend dip switch installed dip switch removed 8 BAT BAT outputs battery connectors BAT red BAT black 9 TAMPER x2 microswitches contacts contact of antisabotage protection NC 10 F2...

Page 5: ...5 Fig 2 The view of the power supply...

Page 6: ...attery circuit SCP and reverse polarity protection 6 3A current limitation F1 fuse failure requires replace of the fuse element Excessive discharge protection UVP U 10 0 V 5 disconnection of BAT batte...

Page 7: ...and is not equipped with a power switch therefore an appropriate overload protection in the power supply circuit shall be guaranteed Moreover the user shall be informed about the method of isolation o...

Page 8: ...of illumination is dependent on the charging current AUX green diode indicates the DC supply status at the output of the PSU Under normal status the diode is permanently illuminated and in the case o...

Page 9: ...he PSU is equipped with the discharged battery disconnection system UPV the configuration of functions through the dip switch JP B The battery protection is on if the dip switch JP B is removed 4 3 Ma...

Page 10: ...ing of the equipment to the service centre of the manufacturer 7 The repair period mentioned in item 5 may be prolonged if there is no technical capability to carry out the repairs and in the case tha...