FPS - technical output of the power supply

: OC type indicates the PSU failure. In a normal status (under 

proper operation), the output is fault to ground (status L – 0V), in case  of incorrect operation parameters 
(voltage, current,  temperature) the output is switched into hi-Z  - high impedance state. 

 

 

 

Fig. 3. Electrical diagram of OC outputs. 

 
 

 

4. Operation and use. 

      4.1 Overload or short circuit of the PSU module output 

The AUX output of the PSU module is equipped with the PTC polymer fuse assisted protection. If the load 

of the PSU module exceeds I

max

 (load 110% ÷ 150% @25ºC of the PSU module  power), the output voltage is 

automatically cut off and indicated by the green diode going off. To restore the output power, cut off the output load 
for approximately 1 minute. 

In case  of of the short-circuit to the AUX, BAT output, (load 200% ÷ 250% of the PSU module power) or 

incorrect  connection  of  the  battery,  the  fuse  F

BAT

  in  the  battery  circuit  becomes  permanently  damaged  and  the 

restoration of the voltage at the BAT output requires the replacement of the fuse. 

 

4.2 Battery

assisted operation 

Immediate battery reverting in case of main power outage.

 

In order to run the PSU from the battery only, connect the BAT connectors in accordance with the signs:  

+ BAT red to ‘plus’ and, - BAT black to 'minus’ then press the START button on the main board and hold it for 5 
seconds. 

 

The PSU module is equipped with the discharged battery disconnection system (UVP), 
configured through the P

BAT

 pins. The battery protection is on after removing the P

BAT

 

jumper. 

 

4.3 Maintenance 

Any and all maintenance operations may be performed following the disconnection of the PSU module  

from the power supply network. The PSU module  does not require performing any specific maintenance 
measures, however, in the case of significant dust rate, its interior is recommended to be cleaned with compressed 
air. In case of fuse replacement, use a replacement of the same parameters. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for MSRK 3512

Page 1: ...MSRK 3512 v 1 2 MSRK 13 8V 3A Buffer switch mode power supply module EN Edition 4 from 16 09 2013 Supercedes the edition 3 from 28 11 2011...

Page 2: ...tion 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication...

Page 3: ...stment 5 Connectors BAT DC supply output of the battery BAT red BAT black AUX DC supply output AUX U AUX GND FAC AC absence technical output OC type open collector level hi Z status AC power supply fa...

Page 4: ...start the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections 5 A current limitation FBAT fuse in case of a failure fuse element replacement requ...

Page 5: ...ssary connect the device conductors to the technical outputs FAC AC status indication alarm panel controller indicator LED etc FPS PSU operation status 6 Using the IBAT pins determine the maximum batt...

Page 6: ...correct connection of the battery the fuse FBAT in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery...

Page 7: ...www pulsar pl MSRK3512 7...

Page 8: ...ities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried o...

Reviews: