Pulsar MSRK 3512 Manual Download Page 2

www.pulsar.pl   

 

 

 

MSRK3512 

 

 

 

 

 
 

Features: 

  DC 13,8V/3A  uninterruptible power supply  

  high efficiency 77% 

  battery charging and maintenance control 

  excessive discharging (UVP) protection 

  battery output full protection against short-circuit 

and reverse polarity connection 

  jumper selectable battery charge current 0,5A/1A  

  START facility for manual battery connection 

  LED indication  

 

  FAC indication of the AC power collapse 

  FPS output of the PSU failure, tripped by: 

 

short-circuit (SCP)  

 

overload (OLP) 

 

failure of DC/DC converter 

 

protections: 

 

SCP short-circuit protection  

 

OLP overload protection  

 

OHP overheat protection  

 

overvoltage protection 

  warranty – 5 year from the production date

 

 
CONTENTS: 
1. Technical description 

1.1. General description 
1.2. Block diagram 
1.3 Description of components and connectors 
1.4 Specifications 

2. Installation 

2.1. Requirements 
2.2. Installation procedure 

3. Operating status indication. 

3.1 LED indication  
3.2. Technical outputs 

4. Operation and use 

4.1. Overload or short circuit of the PSU module output  
4.2. Battery-assisted operation 

 

4.3. Maintenance 

 

1. Technical description. 
 

1.1 General description 

 

A  buffer  PSU  module  is  intended  for  an  uninterrupted  supply  to  devices  requiring  stabilised  voltage  of 

12V/DC (+/-15%)

. The PSU module provides voltage of 

13,8 V DC 

with current capacity: 

 

    

1. Output current 3,0A + 0,5A battery charge 

 

2. Output current 2,5A + 1,0A battery charge 

        Total device c battery: 3,5A max.

 

In case of power failure, a battery back-up is activated immediately. Battery charging current is preset to 0,5A. 

 

 

1.2. Block diagram (fig.1). 

 

 

Fig.1. Block diagram of the PSU module

Summary of Contents for MSRK 3512

Page 1: ...MSRK 3512 v 1 2 MSRK 13 8V 3A Buffer switch mode power supply module EN Edition 4 from 16 09 2013 Supercedes the edition 3 from 28 11 2011...

Page 2: ...tion 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication...

Page 3: ...stment 5 Connectors BAT DC supply output of the battery BAT red BAT black AUX DC supply output AUX U AUX GND FAC AC absence technical output OC type open collector level hi Z status AC power supply fa...

Page 4: ...start the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections 5 A current limitation FBAT fuse in case of a failure fuse element replacement requ...

Page 5: ...ssary connect the device conductors to the technical outputs FAC AC status indication alarm panel controller indicator LED etc FPS PSU operation status 6 Using the IBAT pins determine the maximum batt...

Page 6: ...correct connection of the battery the fuse FBAT in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery...

Page 7: ...www pulsar pl MSRK3512 7...

Page 8: ...ities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried o...

Reviews: