1.4 Specifications: 

- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operating parameters (tab.5)

 

 

 
Electrical parameters (tab. 3). 

Mains supply 

20V÷22V AC  
80VA min. (np. AWT8161820, AWT039) 

Current up to 

3,7 A  

Power frequency 

50Hz 

Power 

49 W 

Efficiency 

77% 

Output voltage 

11,0 V÷ 13,8 V DC – buffer operation 
10,0 V÷ 13,8 V DC – battery assisted operation 

Output current 

3,0A + 0,5A battery charge 
2,5A + 1,0A battery charge 

Output voltage setting, escalation and keeping 
time 

5ms / 40ms / 18ms 
 

Voltage adjustment range 

12,0 V÷ 14,5 V  

Ripple 

30 mV p-p max. 

Current consumption by PSU module systems 

16 mA – battery assisted operation 

Battery charging current 

0,5A / 1A  -  I

BAT

 jumper selectable 

Short-circuit protection SCP  

200% ÷ 250% of module supply power - current limitation 
and/or fuse damage in the battery circuit (fuse-element 
replacement required) 

Overload protection OLP 

110% ÷ 150% (@25ºC) of power supply - limitation with the 
PTC  automatic fuse, manual restart (the fault requires 
disconnection of the DC output circuit) 

Battery circuit SCP and reverse polarity 
protections 

5 A - current limitation, F

BAT

 fuse (in case of a failure, fuse-

element replacement required) 

Excessive discharge protection UVP 

U<10,0 V (± 5%) – disconnection of (- BAT) battery, 
configuration by the P

BAT

 jumper 

Technical outputs: 
- FAC; indicates AC power failure 
- FPS; indicates the PSU operation status  
 

- OC type, 50mA max. normal status: level L (0V),  failure: 
level hi-Z, 10s time lag. 
- OC type, 50mA max. normal status: level L (0V), failure: 
level hi-Z (automatic recovery after a return to correct 
operation) 

F

BAT  

fuse 

F5A / 250V  

 

 
 
Mechanical parameters (tab. 4). 

Enclosure dimensions 

88 x 93 x 55 (WxLxH) [mm] (+/- 2) 

Fixation 

Dowel pins  

x4 (PCB fi=4,2 mm) 

Net/gross weight 

0,16kg/0,21kg 

Connectors 

Outputs: Ф0,41÷1,63 (AWG 26-14) 
Battery output BAT: 6,3F-2,5, 30cm 

 

 
 
Operating parameters (tab.5). 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 
 
 
 
 

Summary of Contents for MSRK 3512

Page 1: ...MSRK 3512 v 1 2 MSRK 13 8V 3A Buffer switch mode power supply module EN Edition 4 from 16 09 2013 Supercedes the edition 3 from 28 11 2011...

Page 2: ...tion 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication...

Page 3: ...stment 5 Connectors BAT DC supply output of the battery BAT red BAT black AUX DC supply output AUX U AUX GND FAC AC absence technical output OC type open collector level hi Z status AC power supply fa...

Page 4: ...start the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections 5 A current limitation FBAT fuse in case of a failure fuse element replacement requ...

Page 5: ...ssary connect the device conductors to the technical outputs FAC AC status indication alarm panel controller indicator LED etc FPS PSU operation status 6 Using the IBAT pins determine the maximum batt...

Page 6: ...correct connection of the battery the fuse FBAT in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery...

Page 7: ...www pulsar pl MSRK3512 7...

Page 8: ...ities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried o...