1.3. Description of components and connectors 

Table 1.  Elements of the PSU module pcb (refer to chart 2). 

Element no. 

Description 

[1] 

F

BAT

 

fuse in the battery circuit 

[2] 

START

 pushbutton (power activation without AC supply) 

[3] 

P

BAT

; pins 

- configuration of UVP battery protection function 

 

P

BAT

 = 

 protection (disconnection) of the battery off 

 

P

BAT

 = 

  protection (disconnection) of the battery on 

 

Legend: 

  

jumper installed 

  jumper removed 

[4] 

V

ADJ

 potentiometer, voltage DC adjustment 

[5] 

Connectors: 
+BAT- 

DC supply output of the battery 

 (+BAT= red, -BAT=black) 

+AUX-

 DC supply output 

 (+AUX= +U, -AUX=GND) 

FAC -

 AC absence technical output – OC type (open collector) 

level hi-Z = status: AC power supply failure 
level L  = status: AC power supply 

FPS

 - technical output of the PSU module operation status – OC type (open collector) 

level hi-Z = status: failure 
level L = status: correct operation

 

[6] 

LED indication: 
AC 

- LED for AC voltage

  

LB 

- LED for battery charge

 

AUX 

- LED for DC voltage 

[7] 

I

BAT

; jumper 

– battery charging current selection 

 

I

BAT

 = 

  Ibat =0,5 A 

 

I

BAT

 = 

  Ibat =1,0 A 

Legend: 

  

jumper installed 

  jumper removed 

[8] 

Connector to the external LED indicators: AC and AUX.

 

 

 

Fig. 2. View of the power supply PCB. 

Summary of Contents for MSRK 3512

Page 1: ...MSRK 3512 v 1 2 MSRK 13 8V 3A Buffer switch mode power supply module EN Edition 4 from 16 09 2013 Supercedes the edition 3 from 28 11 2011...

Page 2: ...tion 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication...

Page 3: ...stment 5 Connectors BAT DC supply output of the battery BAT red BAT black AUX DC supply output AUX U AUX GND FAC AC absence technical output OC type open collector level hi Z status AC power supply fa...

Page 4: ...start the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections 5 A current limitation FBAT fuse in case of a failure fuse element replacement requ...

Page 5: ...ssary connect the device conductors to the technical outputs FAC AC status indication alarm panel controller indicator LED etc FPS PSU operation status 6 Using the IBAT pins determine the maximum batt...

Page 6: ...correct connection of the battery the fuse FBAT in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery...

Page 7: ...www pulsar pl MSRK3512 7...