5. Setting the communication parameters of the PSU.
Communication in the RS485 bus requires setting appropriate communication parameters in all power
supply units and assigning appropriate addresses. Configuration in PSBEN power supply units is via the
display mount in the faceplate of the enclosure. The configuration procedure is different for an LED and LCD
display.
The address for all power supply units is preset to 1.
5.1 Configuration of the PSU with an LCD display.
Setting the address of the PSU.
- enter the PSU ‘Settings’ menu
(if the main screen is displayed, press the ‘SET’ button)
- with ‘>’ or ‘<’ choose the
Power Supply
menu
- approve your choice with the ‘SET’ button
- with ‘>’ or ‘<’ choose the
Comm. Address
- press the ‘SET’ button
- the prompt will appear at the end of the line
- with ‘>’ or ‘<’ set the address from 1 to 247
- approve your choice with the ‘SET’ button