background image

www.pulsar.pl                                                        HPSB11A12D                                                    

GREEN POWER

 

 

 

2

 

 

Features: 

 

 

DC 13,8V/10A  uninterruptible power supply

*

  

 

fitting battery: 40Ah/12V 

 

wide range 

of mains supply: 176÷264V  

 

high efficiency 83% 

 

battery charging and maintenance control 

 

excessive discharging (UVP) protection 

 

jumper selectable battery charge current 1A/4A 

 

battery output full protection against short-
circuit and reverse polarity connection 

 

 

LED indication  

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage protection (input AC) 

 

against sabotage 

 

overload protection (OLP) 

  warranty 

– 2 year from the production date 

 

 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors. 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication of operating status 

4. Operation and use. 

4.1 Overload or short circuit of the PSU output (SCP on) 
4.2 Disconnection of discharged battery 
4.3 Maintenance

 

 

 
1. Technical description. 
 

1.1 General description. 

A buffer PSU is used for an uninterrupted supply to devices requiring stabilised voltage of 

12V DC (+/-

15%).

 The PSU provides voltage of 

13,8V DC. 

Current efficiency: 

 

  1. Output current 10A + 1A battery charge

*

 

2. Output current 7A + 4A battery charge

Total device c battery: 11A max

*

 

In case of power decay, a battery back-up is activated immediately.  The PSU is constructed based on the 

switch mode PSU, with high energy efficiency. The PSU is housed in a metal enclosure (colour RAL 9003) which 
can accommodate a 40Ah/12V battery. A micro switch indicates door opening (front cover). 

 

OPTIONAL POWER SUPPLY CONFIGURATIONS:  

(visualisation available at: www.pulsar.pl) 

 

1. Buffer power supply unit 13,8V/20x0,5A/40Ah. 

                 - HPSB  2xLB8 16x0,5A (AWZ578 or AWZ580) + LB4 4x0,5A (AWZ574 or AWZ576) + 40Ah 

2. Buffer power supply unit 13,8V/10x1A/40Ah.

 

                 - HPSB  LB8 8x1A (AWZ579 or AWZ580) + LB2 2x1A (AWZ585 or AWZ586) + 40Ah 

3. Buffer power supply unit 13,8V/24x0,3A/40Ah. 

    - HPSB 3xLB8 24x0,3A (AWZ577 or AWZ580) + 40Ah 

4. Buffer power supply unit 13,8V/2x12V/2x5A/40Ah.

 

                 - HPSB 2xRN500(13,8V/12V) + 40Ah 

5. Buffer power supply unit 13,8V/2x12V/16x0,5A/40Ah.

 

                 - HPSB 2xRN500(13,8V/12V) + 2xLB8 16x0,5A (AWZ578 or AWZ580) + 40Ah 

6. Buffer power supply unit 13,8V/2x12V/10x1A/40Ah.

 

                 - HPSB 2xRN500(13,8V/12V) + 2xLB8 10x1A (AWZ579 or AWZ580) + 40Ah 

                                                 

*

 

Refer to chart 1

 

 

Summary of Contents for HPSB 11A12D

Page 1: ...HPSB 11A12D v 1 0 HPSB 13 8V 10A 40Ah Buffer switch mode power supply unit EN Edition 8 from 24 10 2016 Supersedes edition 7 from 11 08 2014...

Page 2: ...rupted supply to devices requiring stabilised voltage of 12V DC 15 The PSU provides voltage of 13 8V DC Current efficiency 1 Output current 10A 1A battery charge 2 Output current 7A 4A battery charge...

Page 3: ...s and connectors tab 1 tab 2 fig 2 Part no Fig 2 Description 1 PSU module 2 connectors see tab 2 3 green LED indicates AC power 4 potentiometer output voltage adjustment 5 BAT GND battery outputs BAT...

Page 4: ...www pulsar pl HPSB11A12D GREEN POWER 4 Fig 2 The view of the PSU...

Page 5: ...ction PTC polymer fuse Surge protection varistors Overvoltage protection OVP 16V activation requires disconnecting the load or supply for about 20 s Excessive discharge protection UVP U 9 5 V 5 discon...

Page 6: ...stallation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required an...

Page 7: ...V V of the PSU module 5 Connect the power 230V 6 Connect the battery mind the colours battery output V BAT cable red battery output 0V BAT cable GND black 7 Check the PSU operation indicator green LE...

Page 8: ...c equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period the...

Reviews: