www.pulsar.pl                                                        HPSB11A12D                                                    

GREEN POWER

 

 

 

6

 

      Operation safety (tab.5). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 
       Operating parameters (tab.6). 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 

 
2. Installation. 

 

2.1 Requirements. 

The buffer PSU shall be mounted by a qualified installer with appropriate  permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -

10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  position  that 

guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 
Before installation, prepare a PSU load balance: 
 

  1. Output current 10A + 1A battery charge

*

 

2. Output current 7A + 4A battery charge

*

 

Total device c battery: 11A max

*

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 
 

 
 

                                                 

*

 

Refer to chart 1

 

 

Summary of Contents for HPSB 11A12D

Page 1: ...HPSB 11A12D v 1 0 HPSB 13 8V 10A 40Ah Buffer switch mode power supply unit EN Edition 8 from 24 10 2016 Supersedes edition 7 from 11 08 2014...

Page 2: ...rupted supply to devices requiring stabilised voltage of 12V DC 15 The PSU provides voltage of 13 8V DC Current efficiency 1 Output current 10A 1A battery charge 2 Output current 7A 4A battery charge...

Page 3: ...s and connectors tab 1 tab 2 fig 2 Part no Fig 2 Description 1 PSU module 2 connectors see tab 2 3 green LED indicates AC power 4 potentiometer output voltage adjustment 5 BAT GND battery outputs BAT...

Page 4: ...www pulsar pl HPSB11A12D GREEN POWER 4 Fig 2 The view of the PSU...

Page 5: ...ction PTC polymer fuse Surge protection varistors Overvoltage protection OVP 16V activation requires disconnecting the load or supply for about 20 s Excessive discharge protection UVP U 9 5 V 5 discon...

Page 6: ...stallation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required an...

Page 7: ...V V of the PSU module 5 Connect the power 230V 6 Connect the battery mind the colours battery output V BAT cable red battery output 0V BAT cable GND black 7 Check the PSU operation indicator green LE...

Page 8: ...c equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period the...

Reviews: