background image

www.pulsar.pl                                                           AWZ222                                                   

GREY POWER plus

  

 

 

Features: 

 

  EN50131-

6 compliance, 1÷2 grades and II 

environmental class 

   mains supply 230VAC  

   13,8V DC uninterrupted supply 

  fitting battery: 17Ah/12V 

   PSU current efficiency: 

  1,1A  

– for grades 1, 2 * 

  2A  

– for general use ** 

(see: chapter 1.1) 

  linear voltage regulator  

  microprocessor-based automation system 

  output voltage control 

  dynamic battery test 

  battery electrical continuity control 

  battery voltage control 

  battery fuse status control 

  battery charge and maintenance control 

  deep discharge battery protection (UVP)  

  battery output protection against short-circuit and 

reverse polarity connection 

   battery charging current 

0,4A/0,9A jumper 

selectable  

  START function of manual switch to battery power 

  STOP facility for manual disconnection during battery-

assisted operation  

  LED indication 

  acoustic indication 

  EPS technical output of 230V power failure 

   

– OC type  

  PSU technical output indicating PSU and battery 

failure - OC type 

   APS technical output indicating battery failure 

   

– OC type 

  Optional installation of the MPSBS relay module  

changing technical outputs of the OC type to relay 
type 

  adjustable times indicating AC power failure 

  protections: 

  SCP short-circuit protection 

  OLP overload protection 

  over voltage protection 

  OHP overheat protection 

  surge protection 

   against sabotage 

  warranty 

– 5 years from the production date 

 

CONTENTS: 
1. Technical description. 

1.1. General description 
1.2. Block diagram 
1.3. Description of PSU components and connectors 
1.4. Specifications 

2. Installation. 

2.1. Requirements 
2.2. Installation procedure 

3. Operating status indication. 

3.1. LED indication 
3.2. Acoustic indication 
3.3. Technical outputs 
3.4. Relay technical outputs. 

4. Battery-assisted operation.  
 

4.1. Launching the PSU from a battery 

 

4.2. Deep discharge battery protection UVP 

 

4.3. Dynamic battery test 

 

4.4. Standby time. 

             4.5. Battery charging time. 
5. Operation and use. 
             5.1. Overvoltage protection of the PSU output OVP 
             5.2. Overload or short-circuit the power supply output (SCP activation) 
             5.3. Maintenance. 
 
 
 
1. Technical description. 
 

1.1. General description. 

The  buffer  power  supply  is  designed  in  accordance  with  the  requirements  of  the  EN  50131-6  standard, 

grade 1÷2 and II environmental class. It is intended for an uninterrupted supply of alarm system devices requiring 
stabilized  voltage  of 

12V  DC  (+/-15%). 

A  linear  stabilizing  system,  which  has  been  used  in  the  unit,  provides 

voltage  with  a  lower  level  of  noise  and  a  quicker  response  to  interference  when  compared  to  a  switched-mode 
regulator. 

Summary of Contents for GREY POWER plus AWZ 222

Page 1: ...AWZ 222 v 2 3 AWZ 13 8V 2A 17Ah LM Linear buffer power supply unit Grade 2 EN Edition 9 from 02 11 2017 Supercedes the edition 8 from 23 01 2017 GREY POWER plus...

Page 2: ...er failure protections SCP short circuit protection OLP overload protection over voltage protection OHP overheat protection surge protection against sabotage warranty 5 years from the production date...

Page 3: ...battery space for a 17Ah 12V battery It is fitted with micro switches indicating unwanted door opening front panel The power supply is pre configured for use in alarm systems stage 1 and 2 in accorda...

Page 4: ...VP optical indication for activating the over voltage system FBAT fuse in the battery circuit F3 15A 250V Terminals TAMPER antisabotage protection microswitch connector APS technical output indicating...

Page 5: ...500mA 250V Battery connectors BAT red BAT black Fig 3 The view of the PSU 1 4 Specifications electrical specifications tab 3 mechanical specifications tab 4 operation safety tab 5 operating specificat...

Page 6: ...ery protection UVP U 10V 0 5V disconnection of battery terminal Tamper protection TAMPER indicates unwanted opening of the enclosure microswitch NC contacts enclosure closed 0 5A 50V DC max Technical...

Page 7: ...ng an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure Caution Before installation make sure that the voltage in the 230V...

Page 8: ...e EPS FLT technical output after some time determined by TAC pins battery disconnection LED indication acoustic indication and the APS FLT technical output after a battery test have been completed 10m...

Page 9: ...e lag T 0s J1 J2 time lag T 5min J1 J2 time lag T 1h J1 J2 time lag T 6h PSU FLT output indicating PSU failure The output indicates PSU failure Under normal status correct operation the output is shor...

Page 10: ...board and hold for 3s Disconnecting the PSU from the battery press the STOP button on the main board and hold for 3s 4 2 Deep discharge battery protection UVP The PSU is equipped with the disconnectio...

Page 11: ...e below shows how long does it take to charge a fully discharged battery up to min 80 of its nominal capacity Table 9 Battery charging time 17Ah battery charging time up to the capacity of 0 8 C Charg...

Page 12: ...l waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the appl...