www.pulsar.pl                                                           AWZ222                                                   

GREY POWER plus

  

 

 

11 

4.3  Dynamic battery test. 

The  PSU  runs  a  battery  test  every  10  minutes.  It  is  done  by  a  momentary  output  voltage  reduction  and 

voltage measurement at the battery terminals. A failure is indicated when voltage drops below ~12,2V. The battery 
test function can be turned off.  

Deactivating/activating the test: 

while mains supply, press the STOP button on the main board and hold it for 3 

seconds. The device will confirm the activation/deactivation in the following ways (Tab. 8).  

 

testing off 

– 12 sounds 

 

testing on 

–  3 sounds

  

 

The battery test is performed immediately after switching on with the STOP button. 

 

 Caution: 

 

test activation/deactivation is stored in the memory even after unplugging of the device     

 

test deactivation turns off the fault indication at  the  APS FLT, output. It does not affect the 
battery complete

 

discharge system, though. 

 

 

4.4 Standby time.

  

Battery-assisted operating depends on battery capacity, charging level and load current. To maintain an 

appropriate standby time, current drawn from the PSU in battery mode should be limited. Characteristics for a 
17Ah/12V SLA: 
       

Grade 1, 2 - standby time 12h 

                          

Output current 1,1A + 0,9A battery charging current  

 
 
4.5 Battery charging time. 

The PSU has a battery circuit charged with direct current. The current selection is done with use of the 

I

BAT

 

jumpers. The table below shows how long does it take to charge a (fully discharged) battery up to min. 80% of its 
nominal capacity. 
 

Table 9. Battery charging time. 
 

17Ah

 battery charging time  

up to the capacity of 0,8*C

 

Charging current

 

[A] 

Configuration of 

I

BAT 

jumper

 

17h  

0,9A 

I

BAT

 = 

 (jumper off) 

38h 15min 

0,4A 

I

BAT

 = 

  (jumper on) 

 
 

5.  Service and operation. 
 

5.1 Overvoltage protection of the PSU output OVP. 

In    case    of    voltage    exceeding  16,5V 

at  the  switching regulator’s  output,  the  system  cuts  off  the  

power  at  the outputs to protect the battery and the receivers from damage. The outputs will be battery-powered. 
The activation of the protection system is indicated by the OVP red LED on the PCB board, blinking red FAILURE 
led on the front panel of the PSU and alarm buzzer. The status of the  PSU FLT technical output is changed. 

 
5.2 Overload or short-circuit the power supply output (SCP activation). 

The PSU is equipped with an output protection due to a PTC polymer fuse. If the load of the PSU exceeds 

Izn (110% ÷ 150%), the output voltage is automatically cut off and indicated by the FAILURE red diode (Tab. 7). 
The load shall be disconnected from the PSU output for approximately 1 minute. 
 

             5.3 Maintenance. 

Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power supply network. The PSU   does not require performing any specific maintenance measures, however, in the 
case of significant dust rate, its interior is recommended to be cleaned with compressed air. In the case of a fuse 
replacement, use a replacement of the same parameters.  
 
 
 
 
 
 
 
 

Summary of Contents for GREY POWER plus AWZ 222

Page 1: ...AWZ 222 v 2 3 AWZ 13 8V 2A 17Ah LM Linear buffer power supply unit Grade 2 EN Edition 9 from 02 11 2017 Supercedes the edition 8 from 23 01 2017 GREY POWER plus...

Page 2: ...er failure protections SCP short circuit protection OLP overload protection over voltage protection OHP overheat protection surge protection against sabotage warranty 5 years from the production date...

Page 3: ...battery space for a 17Ah 12V battery It is fitted with micro switches indicating unwanted door opening front panel The power supply is pre configured for use in alarm systems stage 1 and 2 in accorda...

Page 4: ...VP optical indication for activating the over voltage system FBAT fuse in the battery circuit F3 15A 250V Terminals TAMPER antisabotage protection microswitch connector APS technical output indicating...

Page 5: ...500mA 250V Battery connectors BAT red BAT black Fig 3 The view of the PSU 1 4 Specifications electrical specifications tab 3 mechanical specifications tab 4 operation safety tab 5 operating specificat...

Page 6: ...ery protection UVP U 10V 0 5V disconnection of battery terminal Tamper protection TAMPER indicates unwanted opening of the enclosure microswitch NC contacts enclosure closed 0 5A 50V DC max Technical...

Page 7: ...ng an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure Caution Before installation make sure that the voltage in the 230V...

Page 8: ...e EPS FLT technical output after some time determined by TAC pins battery disconnection LED indication acoustic indication and the APS FLT technical output after a battery test have been completed 10m...

Page 9: ...e lag T 0s J1 J2 time lag T 5min J1 J2 time lag T 1h J1 J2 time lag T 6h PSU FLT output indicating PSU failure The output indicates PSU failure Under normal status correct operation the output is shor...

Page 10: ...board and hold for 3s Disconnecting the PSU from the battery press the STOP button on the main board and hold for 3s 4 2 Deep discharge battery protection UVP The PSU is equipped with the disconnectio...

Page 11: ...e below shows how long does it take to charge a fully discharged battery up to min 80 of its nominal capacity Table 9 Battery charging time 17Ah battery charging time up to the capacity of 0 8 C Charg...

Page 12: ...l waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the appl...

Reviews: