background image

www.pulsar.pl   

 

 

 

PSBEN10A12C  

 

 

 
 

21 

9. PSU FAILURE CODES. 

 

LED indication 

Failure 

code 

EXT 

OVL 

AC 

PSU 

APS 

Acoustic 

indication 

Technical 

outpust 

actvation 

Fault description 

Causes 

F01 

1 beep 

per 10s 

EPS FLT 

Battery-assisted 

operation 

 

- No AC mains 

supply 

- Faulty main fuse 

F

MAIN

 

F02 

ON 

twinkles 

ON 

PSU FLT 

PTC polyswitch 

activation at the 

AUX output 

- Overloaded AUX 

output 

F03 

 
 
 

ON 

twinkles 

ON 

APS FLT 

Blown fuse of the 

battery F

BAT

 

- Short circuit in the 

battery circuit 

- Short circuit in the 

AUX output circuit 
- Overloaded AUX 

output 

F04 

ON 

ON 

ON 

ON 

PSU FLT 

- Overloaded AUX 

output 

F05 

 
 

ON 

ON 

1 beep 

per 10s 

 

APS FLT 

Faulty battery* 

- Drained battery 

- Undercharged 

battery 

- Unplugged battery 

F06 

ON 

1 flash 

ON 

PSU FLT 

Too high output voltage 

- Output voltage 

>14.7V 

F07 

ON 

2 flashes 

ON 

PSU FLT 

Too high battery 

voltage* 

- Battery voltage  

> 14V 

F08 

 
 

ON 

3 flashes 

ON 

PSU FLT 

Battery charging circuit 

failure 

- Too low output 

voltage of the PSU, 

set <13V 

- Fault in the battery 

charging circuit 

F09 

 

ON 

4 flashes 

ON 

 

PSU FLT 

Too low output voltage 

- Output voltage 

<11.8V (during buffer 

operation) 

F10 

ON 

2 signals 

per 10s 

 

APS FLT 

Too low battery voltage 

- Battery voltage 

drops below 11.5V 

(during battery-

assisted operation) 

F11 

ON 

Fast 

audible 

signals 

 

APS FLT 

PSU disconnection 

caused by battery 

discharge 

- Battery voltage 

drops below 10V 

(during battery-

assisted operation) 

F12 

ON 

ON 

ON 

PSU FLT 

Activation of the EXT IN 

collective failure input 

F50 

   - 

ON 

ON 

PSU FLT 

Internal damage of the 

PSU 

F51 

ON 

ON 

PSU FLT 

Error in setting memo 

F60 

No communication 

Broken cord between 

the PSU and the 

display 

F61-64 

Desktop fault 

F65 

Password unblocking 

procedure 

 
* failure indication only during a battery test 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for BLACK POWER PSBEN 10A12C

Page 1: ...PSBEN 10A12C v 1 0 PSBEN 13 8V 10A 17Ah EN Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Page 2: ...4 2 DEEP DISCHARGE BATTERY PROTECTION UVP 12 4 3 DYNAMIC BATTERY TEST 12 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 13 5 REMOTE MONITORING OPTION WI FI ETHERNET R...

Page 3: ...indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technic...

Page 4: ...rce are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 3A battery charge General use if the PSU is not mounted within an installation which is PN...

Page 5: ...T button launching the PSU from a battery STOP button disconnection of the PSU during battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper...

Page 6: ...ption 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE connector 6 B...

Page 7: ...pproving a certain parameter that is to be displayed Fig 4 Control panel Table 3 A description of the buttons and LEDs of the LED panel parameter selection selection approval red LED indicates presenc...

Page 8: ...e codes that can appear during the PSU s operation have been shown Each code is accompanied by an appropriate LED indication on the panel acoustic indication and switching of a dedicated technical out...

Page 9: ...r 9 6 or 19 2 values informing of the transmission s speed with or set the transmission s speed to 19200 which is displayed as 19 2 approve the setting with the OK button the abbr trS will be displaye...

Page 10: ...time lag T 2h 20m Caption jumper on jumper off APS FLT output indicating battery failure The output indicates a failure in the battery circuit Under normal status during correct operation the output i...

Page 11: ...nal Fig 8 Examples of connections In the option with tamper switches the VEXT jumper must be on It polarises the EXT IN input circuit therefore is required in such configuration The EXT IN input has b...

Page 12: ...after unplugging the device from mains The battery failure indication at the APS FLT output is automatically switched off The battery protection system against deep discharged remains on though 4 4 S...

Page 13: ...uration of jumpers In this mode the automation system allows adjustments of PSU s output voltage without indicating a failure connected with working of the battery CAUTION During operation without bat...

Page 14: ...es 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequen...

Page 15: ...thernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correctly...

Page 16: ...on with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and memo r...

Page 17: ...eneral use Io 10A 0 6A battery charge Io 9 1A 1 5A battery charge Io 8 4A 2 2A battery charge Io 7 6A 3A battery charge Output voltage setting escalation and keeping time 8ms 3ms 25ms Output voltage a...

Page 18: ...e Connectors Supply 0 51 2 AWG 24 12 Outputs 0 51 2 AWG 24 12 battery outputs BAT 6 M6 0 2 5 56cm TAMPER output wires 25cm Notes The enclosure does not adjoin the assembly surface so that cables can b...

Page 19: ...ntees indication in case of any attempts of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 17 Fixing a tamper grip 2 Co...

Page 20: ...s to protect the battery and the receivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status...

Page 21: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Page 22: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Reviews: